25mA Low Power Sinking Outputs (LSNK)
The 25mA sinking option, referred to as lower power sinking (LSNK), are capable of sinking up to 25mA
per output. The voltage range for the outputs is 5-24 VDC. These outputs should not be used to drive
inductive loads directly.
Electrical Specifications
Output PWR (OPnB)
Max Voltage
24 VDC
Output PWR (OPnB)
Min Voltage
5 VDC
ON Voltage (No Load, Output PWR= 5 VDC)
1.2 VDC
Max Drive Current per Output
25 mA, sinking
Wiring Information
The output power supply will be connected to Output PWR (labeled OPnB) and the power supply return
will be connected to Output GND (labeled OPnA), where n denotes 0, 1, or 2 referring to Bank 0, Bank 1,
and Bank 2 respectively. Note that the load is wired between Output PWR and DO. The wiring diagram for
Bank 0 is shown in Figure 4.4 , Bank 1 in Figure 4.6, and Bank 2 in Figure 4.5. Refer to Connectors for RIO-
47xxx in the Appendix for pin-out information.
Chapter 4 I/O ▫ 43 RIO-47xxx Rev 1.0r
Figure 4.3: 500mA Sourcing wiring diagram for Bank 2, DO[23:16]
Figure 4.4: 25mA Sinking wiring diagram for Bank 0, DO[7:0]
Figure 4.5: 25mA Sinking wiring diagram for Bank 1, DO[15:8]