BIOMETRIC READERS 

GCS-HW-0117-SG-RDRWIR-QRG

 

www.

galaxysys

.com

 

Page 3 of 10 

 

5.0

 

IDEMIA (Morpho) SIGMA Biometric Reader - Cable Specs & Wiring  

 

3-conductor, 20 - 24 AWG, overall shielded; non-stranded; max cable distance is 500 feet.  

 

2-conductor, 16 AWG for at +12vdc (18 AWG for +24vdc) for 500 feet distance.  Reader draws 1A at 12v (0.5A at 24v). 

 

Cat-5e Ethernet cable for TCP/IP communication back to the server; max cable distance 300 feet. 

 

Separate power supply required (current draw is 1A). You must common the reader's power supply ground to controller ground. 

 

Ground the drain-wire at one end only - land drain wire at the DRM Board (GND). 

 

Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy specs). 

 

635-DRM Board (Dual Reader Module) – PN 20-0235-10  

 

DRM Relay-2 is used to control Sigma “Wait for Panel Decision” for Voice/Prompt synchronization.  

 

635-DRM Terminal Functions (PN 20-0235-10)

 

Wiegand Reader  

LED

 

(LED control line) 

 

D 1

 

(Data 1) 

WIEG DATA 1 

VDC

 

(+12 VDC)   

( Do not use for reader power! )

 

VDC

 (to separate power supply.) 

GND

 

(common the reader p.s. ground to controller p.s. ground) 

GND

 (common to controller ground) 

D 0

 

(Data 0) 

WIEG DATA 0 

 

635-DRM RELAY-2  

SIGMA “Wait for Panel Decision”  

COM 

(must tie to ground of the reader’s power supply) 

-  - 

NO

 

(for voice/prompt control line) 

LED1   

 

NOTES: 

 

“Wait for Panel Decision”: connect Sigma LED1 to the ‘NO’ leg of Relay-2. The ‘COM’ leg of Relay-2 must be tied to DRM GND. 

 

Set Relay-2 for Timed Mode (1 to 2 secs) and “Valid Unlock” checkbox must be "checked" in System Galaxy Reader 
Properties. 

 

 

6.0

 

Invixium (IXM) Biometric Reader - Cable Specs & Wiring  

 

3-conductor, 22 AWG, overall shielded; non-stranded; max cable distance is 500 feet.  

 

2-conductor, 18 AWG for at +12vdc for 500 feet distance. Reader draws 1A at 12v . 

 

Cat-5e Ethernet cable for TCP/IP communication back to the server; max cable distance 300 feet. 

 

Separate power supply required (current draw is 1A). Must common reader's p.s. ground to controller ground. 

 

Ground the drain-wire at one end only - land drain wire at the DRM Board (GND). 

 

Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy specs). 

 

635-DRM Board (Dual Reader Module) – PN 20-0235-10  

 

635-DRM LED is used to control reader’s for Voice Command when configured for “Wait for Panel Decision”.  

 

635-DRM Terminal Functions (PN 20-0235-10) 

Invixium Reader  

LED 

(LED control line) 

ACP LED1  

(used to control Voice Command) 

D 1 

(Data 1) 

W DATA_OUT1 

 

VDC 

(+12 VDC)   

( Do not use for reader power! )

 

 

 

GND 

(common ground; drain wire) 

VIN 

 (GND)  

(bond to controller GND) 

D 0 

(Data 0) 

W DATA_OUT0 

 

 

VIN + (VDC)  

to separate power supply 

 

VIN 

 (GND)  

to separate power supply 

 

NOTES: 

 

The IXM Reader must be configured to “follow panel decision” in the IXM-WEB software in reader configuration screen. 

 

Galaxy controller must be set for Door Lock = Steady-High; Door Unlock = Steady-Low in the 

LED Options tab

 of the 

Loop/Cluster Properties

 screen.  

 

Содержание 635-DRM

Страница 1: ...VDC GND Power Supply Ground GND D 0 Data 0 DATA 0 2 0 ABA Reader Cable Specs Wiring 5 conductor 22 AWG overall shielded max cable distance is 500 feet Reader will require separate power supply if the...

Страница 2: ...Board Requirement 635 DRM Board Dual Reader Module PN 20 0235 10 DRM Relay 2 must be use for Mode Factor Control MODES FACTORS Mode 1 Card Only high Mode 2 Card Pin low 635 DRM Terminal Functions PN...

Страница 3: ...a LED1 to the NO leg of Relay 2 The COM leg of Relay 2 must be tied to DRM GND Set Relay 2 for Timed Mode 1 to 2 secs and Valid Unlock checkbox must be checked in System Galaxy Reader Properties 6 0 I...

Страница 4: ...Requirement 635 DRM Board Dual Reader Module PN 20 0235 10 DRM Relay 2 must be use for Mode Factor Control MODES FACTORS Mode 1 Card Only Mode 2 Card Pin 635 DRM Terminal Functions PN 20 0235 10 SCM R...

Страница 5: ...ader The STid Reader with Proximity Module acts as pass through data can read 125KHz cards EM HID PROX AWID IOPROX INDALA in addition to the 13 56 MHz STid PC2 Smart Cards Do not mix non mobile STid R...

Страница 6: ...m PC2 smart cards but cannot read the secure area The STid Reader with Proximity Module acts as pass through data can read 125KHz cards EM HID PROX AWID IOPROX INDALA in addition to the 13 56 MHz MIFA...

Страница 7: ...en you add the 635 Series Clusters into the SG Loop Cluster Properties screen do the following On the Advanced tab set the Card Data Mode droplist to Extended Card 256 Bits On the LED Options tab set...

Страница 8: ...Module PN 20 0235 10 Min Board Requirement 635 DSI Board Dual Serial Interface PN 20 0655 10 for Mode Factor Control READER MODES FACTORS Mode 1 Card Only Mode 2 Card Pin Mode 3 Card Pin Bio 635 DRM...

Страница 9: ...s instructions for wiring manufacturer s specs may supersede Galaxy specs 635 DRM Terminal Functions Device State COM Common LED Control CNT Door Contact NC Normally Closed Contact Door Closed Contac...

Страница 10: ...m controller 22 AWG 2 conductor overall shielded wired normally closed NC Lock Hardware 500 ft from controller 18 AWG 2 conductor minimum shielded Separate Power Supply Refer to manufacturer s instruc...

Отзывы: