5). Rx Function Setting:
Item
Title
Content
Description
1 Passive Act 1. Relay-off
2. Power-off
Passive Act:
The function of this item is
used to set the reaction of Receiver when no
command signal received from Transmitter
in certain time (the default time is 0.5
second).
Relay Off:
means the Main Relay is still “on”
but the other relays with the function of
“Normal” are all de-energized. It is not
necessary to recommence the procedure of
“Power-On” again to continue operating.
Power-Off:
means the Main Relay and all of
the other relays with the function of “Normal”
and “Control by EMS” are going to de-
energize and it is essential to recommence
the procedures of “Power-On” again to
continue operating.
2 Passive Act
Timing
0.5 ~ 4.0 sec
The duration working time of Receiver
between passive act is activated and the
power or relay is really off.
3 Auto-off
(RX)
1. None-execute
2. 10 mins ~ 4 hrs
Power-off
None-execute:
The main relay of Receiver
will remain energized unless was Power-off
manually
10 mins ~ 4 hrs Power-off:
If Receiver doesn’t receive the correct
control data within a certain time, then the
main relay on Receiver will be de-energized
automatically (i.e. Receiver Power-off).
Normally this function is used with “non-
continuous transmitting mode” in case
operator forgot to turn off the transmitter.