ESD5500E Series Speed Control Unit 2-2021-F2  PIB1002

6

START ThE ENgINE

The speed control unit governed speed setting is factory set at approximately engine idle speed. (1000 Hz., speed sensor signal or 600 RPM) 

If the engine does not start, adjustment of the speed potentiometer may be required.

Crank the engine with DC power applied to the governor system.  The actuator will energize to the maximum fuel position until the engine 

starts. The governor system should control the engine at a low idle speed.  If the engine is unstable after starting, refer to Section 8 ADJUST-

ING FOR STABILITY.

7

gOvERNOR SPEED SETTINg

5

ADJUSTmENTS BEFORE ENgINE STARTUP

Make sure the following adjustments are set before starting the engine.

GAIN

Middle Position

STABILITY

Middle Position

SPEED TRIM CONTROL

Middle Position

STARTING FUEL

Full CW (MAX fuel)

SPEED RAMPING

Full CCW (fastest)

The governed speed set point is increased by clockwise rotation of the 

SPEED adjustment control. Remote speed adjustment can be obtained 

with an optional 5 kΩ Speed Trim Control 

potentiometer

8

ADJUSTINg FOR STABIlITy

 

Once the engine is running at operating speed and at no load, the 

following governor performance adjustments can be made to increase 

engine stability.

Parameter

ProceDure

GAIN

1.  Rotate the GAIN adjustment clockwise until instability develops. 

2.  Gradually move the adjustment counterclockwise (CCW) until stability returns.

3.  Move the adjustment one division further counterclockwise to ensure stable performance (270° potentiometer). 

4.  If instability persists, adjust the next parameter.

STABILITY

Follow the same adjustment procedure, steps 1 - 3, as the GAIN parameter.

Normally, adjustments made at no load achieve satisfac-

tory performance. If further performance improvements 

are required, refer to Section 12 

TROUBLESHOOTING

note

IMPORTANT:

Speed Adjustment Is a 25 

Turn Potentiometer 

Содержание ESD5522E

Страница 1: ...precisely in response to transient load changes The ESD5500E controls a wide variety of engines in isochronous or droop mode when connected to a proportional electric actuator and magnetic speed senso...

Страница 2: ...trol Unit 2 2021 F2 PIB1002 Mount in a cabinet engine enclosure or sealed metal box Vertical orientation allows fluids to drain in moist environ ments Dimensions Avoid Extreme Heat 3 Installation Outl...

Страница 3: ...5 Magnetic speed sensors Terminals C and D must be twisted and or shielded for the entire length 6 The gap between the speed sensor and the ring gear teeth should be smaller than 0 02 in 0 5 mm usual...

Страница 4: ...tion STARTING FUEL Full CW MAX fuel SPEED RAMPING Full CCW fastest The governed speed set point is increased by clockwise rotation of the SPEED adjustment control Remote speed adjustment can be obtain...

Страница 5: ...on for the ESD5500E may be selected Operating Speed or Idle METHOD 1 Operating Speed PROCEDURE Start the engine and accelerate directly to the operating speed Gen erator Sets etc METHOD 2 IDLE SPEED 1...

Страница 6: ...position is OFF Use the ON position if you experience fast erratic engine behavior between the engine and generator due to a soft coupling LEA DROOP IDLE SPEED C1 OFF ON LEAD CIRCUIT OFF ON C2 SOFT C...

Страница 7: ...ide range of droop is available with the internal control droop level requirements of 10 are unusual If droop levels experienced are higher or lower than those required contact GAC for assistance NOTE...

Страница 8: ...e possibility of missed or extra pulses The speed control unit will govern well with 1 0 V RMS speed sensor signal A speed sensor signal of 3 V AC or greater at governed speed is recommended Measureme...

Страница 9: ...V DC then check for actuator binding linkage binding If the voltage reading is below 0 8 V DC Defective speed control unit Actuator does not energize fully 1 Measure the voltage at the battery while...

Отзывы: