ESD5550-5570 Series Speed Control Unit

   

9-2020-E

   

PIB1003

InSTaBILITY

InSTaBILITY 

SYmPTom

ProBaBLe SoLUTIon

Fast Periodic

The engine seems 

to jitter with a 3Hz 

or faster irregularity 

of speed. 

1.  Readjust the GAIN and STABILITy for optimum control.

2. 

Turn off any local electrical equipment that may be causing EMI interference.

3.  Set the Lead Circuit DIP switch SW1 to OFF

4.  If system is still unstable, set Soft Coupling SW2 to ON.  This may indicate soft or worn couplings in drive 

train. 

5.  Remove E1 to E2 jumper. See section 4, Wiring diagram.

Slow Periodic An irregularity 

of speed below 

3Hz. (Sometimes 

severe)

1. 

Readjust GAIN and STABILITy 

2.  Set Lead Circuit and Soft Coupling DIP switches SW1 and SW2 to ON in the following order: First SW1, 

Second SW2, and Third SW1 & SW2. 

3.  Check fuel system linkage during engine operation for:

• 

binding

• 

high friction

• 

poor linkage

4.  Adjust DEAD TIME COMPENSATION by adding a capacitor from posts E1 to E2. See section 4, Wiring 

diagram. Start with 10 mF and increase until instability is eliminated.

5.  Add small amount of droop (jumper K and L). See section 4, Wiring diagram.

Non-Periodic

Erratic Engine 

Behavior

1.  If increasing GAIN does not reduce the instability but not totally correct it issue may be with engine.

2.  If this is the case, there is most likely a problem with the engine itself.  Check for:

•  engine mis-firings

• 

an erratic fuel system

• 

load changes on the generator set voltage regulator.

3.  If throttle is slightly erratic, but performance is fast, move SW1 to the OFF position.

UnSaTISfacTorY Performance

SYmPTom

normaL reaDInG

ProBaBLe caUSe

Engine Overspeeds

1.

Do Not Crank. Apply DC power to 

the governor system.

After the actuator goes to full fuel, disconnect the speed sensor at Terminal 

C & D. If the actuator is still at full fuel-speed then the speed control unit is 

defective. 

2.

Manually hold the engine at the 

desired running speed. Measure 

the DC voltage between Terminals 

A(-) & F(+) on the speed control 

unit.

1.  If the voltage reading is 1.0 to 2.0 V DC:

• 

SPEED adjustment is set above desired speed

• 

Defective speed control unit

2.  If voltage reading is above 2.0 V DC then check for:

• 

actuator binding

• 

linkage binding

3.  If the voltage reading is below 1.0 V DC it may be a defective speed 

control unit

4.  Check if Gain is set too low.

Overspeed Shuts Down En-

gine After Running Speed is 

Reached

• 

Speed adjustment set too high.

• 

OVERSPEED set to close to running speed.

• 

Actuator or linkage binding.

• 

Speed control unit defective.

Overspeed Shuts Down En-

gine Before Running Speed 

is Reached

Check impedance between 

Terminals C & D. Should be 160 

to 1200 Ω

OVERSPEED set too low. Adjust 5-6 turns CW.

Erroneous speed sensor signal. Check wiring.

Actuator does not energize 

fully

1.

Measure the voltage at the battery 

while cranking.

If voltage for a 12 V DC system is less than 7 V DC, or for a 24 V DC system is 

less than 14 V DC, replace the battery if weak or undersized

2.

Momentarily connect Terminals A 

and F. The actuator should move 

to the full fuel position.

• 

Actuator or battery wiring in error

• 

Actuator or linkage binding

• 

Defective actuator

• 

Fuse opens. Check for short in actuator or harness.

Engine remains below 

desired governed speed

1.

Measure the actuator output, Ter-

minals A & B, while running under 

governor control.

If voltage measurement is within 2 V DC of the battery supply voltage level, 

then fuel control is restricted from reaching full fuel position, possibly due to 

mechanical governor, carburetor spring, or linkage interference.
SPEED parameter set too low

7

SySTEM TROUblESHOOTINg  (CONTINUED)

Содержание ESD-5550 Series

Страница 1: ...er DNV GL Bureau Vertas PHYSICAL Dimension See Section 3 Installation Weight 1 8 lbf 0 82 kgf Mounting Any position vertical preferred The ESD5550 5570 series speed control unit is an all electronic device de signed to control engine speed with fast and precise response to transient load changes This closed loop control when connected to a proportional electric actuator and supplied with a magneti...

Страница 2: ...ed Control Unit 9 2020 E PIB1003 3 Installation Mount in a cabinet engine enclosure or sealed metal box Vertical orientation allows fluids to drain in moist environments Dimensions Avoid extreme heat in mm Take into account the following preferences when mounting the speed controller ...

Страница 3: ...1003 4 Wiring An overspeed shutdown device independent of the governor system must be provided to prevent loss of engine control which may cause personal injury or equipment damage Do not rely exclusively on the governor system to prevent over speed A secondary shutoff device such as a fuel solenoid must be used ...

Страница 4: ...sure no other part of the shield comes in contact with engine ground otherwise stray speed signals may be introduced into the speed control unit With the engine stopped adjust the gap between the magnetic speed sensor and the ring gear teeth The gap should not be any smaller than 0 020 in 0 45 mm Usually backing out the speed sensor 1 4 to 1 2 turn after touching the ring gear teeth will achieve a...

Страница 5: ...g The overspeed function is now set to approximately 10 above the requested speed 1 2 ON STABILITY GAIN SPEED OVERSPEED ADJUSTING OVERSPEED ADJUSTMENT SWITCH POTENTIOMETER SWITCH FACTORY SETTING NOTES SPEED 25 turn 1470 Hz 50 Hz w min trim GAIN 270 turn 50 Middle position STABILITY 270 turn 50 Middle position DROOP 270 turn 0 CCW IDLE 270 turn 1075 75 Hz STARTING FUEL RAMP 270 turn 100 CW Maximum ...

Страница 6: ...obtained with an optional 5K Speed Trim Control See section 4 Wiring diagram Once the engine is at operating speed and at no load the following governor performance adjustment can be made PARAMETER PROCEDURE GAIN 1 Rotate the GAIN adjustment clockwise until instability develops 2 Gradually move the adjustment counterclockwise until stability returns 3 Move the adjustment one division further count...

Страница 7: ...t governs well with 0 5 volts RMS speed sensor signal A speed sensor signal of 3 volts RMS or greater at governed speed is recommended Measurement of the signal is made at Terminals C and D The amplitude of the speed sensor signal can be raised by reducing the gap between the speed sensor tip and the engine ring gear The gap should not be any smaller than 0 02 in 0 5 mm When the engine is stopped ...

Страница 8: ... governor system After the actuator goes to full fuel disconnect the speed sensor at Terminal C D If the actuator is still at full fuel speed then the speed control unit is defective 2 Manually hold the engine at the desired running speed Measure the DC voltage between Terminals A F on the speed control unit 1 If the voltage reading is 1 0 to 2 0 V DC SPEED adjustment is set above desired speed De...

Отзывы: