Install indoor unit
2
2
1.
2.
3.
Install of Drain Hose
Connect the drain hose to the outlet pipe of the indoor unit.
Bind the joint with rubber belt.
Put the drain hose into insulating tube.
Wrap the insulating tube with wide rubber belt to prevent
the shift of insulating tube. Slant the drain
hose
downward
slightly for smooth drainage of
condensate.
Note: The insulating tube should be connected reliably with
the sleeve outside the outlet pipe. The drain hose should be
slanted downward slightly, without distortion, bulge or
fluctuation. Do not put the outlet in the water.
bulge
distortion
outlet pipe of
indoor unit
insulating tube
connected
insulating tube
drain hose
outlet pipe of
indoor unit
rubber belt
rubber belt
Flooded
drain hose
outlet pipe of
indoor unit
outlet pipe of
indoor unit
rubber belt
Connect indoor and outdoor electric wires
Fig.6
1.Open the surface panel.
2.Remove the wiring cover Fig.6.
3.Route the power connection cord from the back of the indoor unit and pull it toward the front
through the wiring hole for connection.
4.Connect the interconnection cord to the terminal block, and then fix the cord with cord anchorage.
5.Reassemble the clamp and wiring cover.
6.Recover the surface panel .
yellow-
green
brown
Wiring cover
Outdoor unit connection