The UPS is equipped with a redundant auxiliary power supply that enables the UPS to run on an automatic bypass even 
when a failure occurs in the main auxiliary power supply. If a fault occurs in the UPS shutting off the main auxiliary power 
supply, the load is powered by the automatic bypass. The multiprocessor board and the control panel are not powered so 
the LEDs and the display are off. 

 

 
 
 

P

ROGRAMMABLE 

A

UXILIARY 

S

OCKET 

(

POWER SHARE

)

 

 

The  UPS  has  an  output  socket  that  enables  the  load  applied  to  it  to  be  disconnected  automatically  under  certain 
operating conditions. The events that determine the automatic disconnection of the Power share socket may be selected 
using the configuration software UPSTools (see the 

Configuration software 

and 

UPS Configuration 

paragraphs). 

For example, the socket can be disconnected after a given time of battery operation, or when the battery low prealarm 
threshold is reached or an overload occurs. 

 

 
 
 

P

OWER WALK

-

IN

 

 

The  UPS  has  a  Power Walk-in  mode  which  can  be  enabled  and  configured  using  the  software 

UPS  Tools

. When  the 

mode is enabled and mains power is restored after a period of battery operation, the UPS starts to draw progressively 
from it so as not to stress (due to the peak) any generating set installed upstream. The transient time may be set from 1 
to  30  seconds.  The  default  value  is  10  seconds.  During  the  transient,  the  necessary  power  is  drawn  in  part  from  the 
batteries and in part from the mains, maintaining sinusoidal absorption. The battery charger is turned on again once the 
transient has passed. 

 

 
 
 

R

EDUCING THE 

L

OAD 

(

TO 

200V 

AND 

208V)

 

 

If the output voltage is set to 200V and 208V (see “Configuring the UPS” paragraph), the maximum power output of the 
UPS is reduced with respect to its rated value, as shown in the graph below: 

 
 
 
 
 
 
 
 

 

 

 

 
 
 
 
 
 
 

 

 

 

 

 
 

Содержание Sirius 20 kVA

Страница 1: ...UPS SIRIUS...

Страница 2: ...anual contains detailed instructions on how to use and install the product For information on how to use your equipment to its full potential this manual should be kept close at hand beside the UPS an...

Страница 3: ...ONTENTS 13 INSTALLING THE UPS AND THE BATTERY BOX 13 STEPS TO BE TAKEN TO GAIN ACCESS TO THE TERMINALS OF THE UPS BATTERY BOX 13 ELECTRICAL CONNECTIONS 14 WIRING DIAGRAMS FOR CONNECTING TO THE ELECTRI...

Страница 4: ...E BYPASS SWMB 31 REDUNDANT AUXILIARY POWER SUPPLY FOR AUTOMATIC BYPASS 32 PROGRAMMABLE AUXILIARY SOCKET POWER SHARE 32 POWER WALK IN 32 REDUCING THE LOAD TO 200V AND 208V 32 CONFIGURING THE UPS 33 COM...

Страница 5: ...ion 1 Due to its modern innovative design large graphic display and above all greater power provided by the battery charger up to 6A recharge the Sirius series represents a new reference point in the...

Страница 6: ...elease the area marked X From left Battery fuse holder isolator Manual bypass switch Battery start button COLD START 1 0 main power switch From left Input switch Separate bypass switch optional Output...

Страница 7: ...PARATE BYPASS optional OUTPUT Connection for remote maintenance bypass command Connection for external Battery Box temperature probe Connection for external synchronization signal Connection for R E P...

Страница 8: ...communication cards RS232 communication port Powershare sockets max total 10A on two sockets USB communication port Powershare socket thermal protector manual reset Ventilation fans Contact holder for...

Страница 9: ...r LED Battery low LED Battery power LED ECO mode LED Load on bypass LED Graphic display Stand by alarm LED F1 F2 F3 F4 FUNCTION KEYS The function of each key is indicated at the bottom of the display...

Страница 10: ...e battery voltage of the Battery Box corresponds to that supported by the UPS Additional Battery Boxes may be connected in a chain to obtain the desired autonomy time during a power failure This serie...

Страница 11: ...ction IP20 Cable input From bottom on rear INSTALLATION ALL THE OPERATIONS DESCRIBED IN THIS SECTION ARE TO BE PERFORMED EXCLUSIVELY BY QUALIFIED STAFF The company declines all liability for damage ca...

Страница 12: ...should not exceed 90 non condensing Check that the ambient temperature with the UPS running remains between 0 and 40 C The UPS may be operated with an ambient temperature of between 0 and 40 C The rec...

Страница 13: ...Open the door and remove the slides NOTE 2 The slides are fixed to the pallet by a screw marked C B in the figure C B B Remove the 4 brackets securing A A A the UPS to the pallet the screws are marke...

Страница 14: ...for it to be turned on off and maintenance operations to be performed on it 1 5 mt The rear part of the UPS should be set at least 30 cm from the wall to enable the air blown by the ventilation fans...

Страница 15: ...e earth of the TT TN or IT type in accordance with the IEC 60364 3 standard the phase rotation must therefore be respected There are optional TRANSFORMER BOXES to convert the distribution systems from...

Страница 16: ...ypass input UPS with galvanic isolation and with separate bypass input UPS with galvanic isolation at output and separate bypass input Separate bypass if the separate bypass option is present protecti...

Страница 17: ...lation transformer would have to be used on one of the inputs UPS without any variation in neutral condition and with separate bypass input connected to independent power supply line UPS with separate...

Страница 18: ...ed load PF 0 9 and an input voltage of 346V and a battery charger charged with 4A SHORT CIRCUIT If a failure occurs on the load the UPS protects itself by limiting the value and duration of the curren...

Страница 19: ...is connected to the neutral of the UPS output the neutral condition of the system is not modified THE UPS INPUT NEUTRAL IS CONNECTED TO THE UPS OUTPUT NEUTRAL THE DISTRIBUTION SYSTEM THAT POWERS THE...

Страница 20: ...maximum length of the cables for connecting the Battery Box optional is 3 metres Note the maximum cross section of the cables that may be inserted in the terminal board is 10mm2 for cables with lugs...

Страница 21: ...circuit and connect to the normally closed contact of the stop device using a cable that provides a double isolation connection In case of emergency by activating the stop device the R E P O control...

Страница 22: ...ulated cable with a cross section of 1mm2 to connect the SERVICE BYPASS terminal to the auxiliary contact of the remote maintenance bypass isolator Whenever the UPS is equipped with internal isolation...

Страница 23: ...iven in Internal Protective Devices of the UPS OUTPUT switch isolator conforming to the indications given in Internal Protective Devices of the UPS SERVICE BYPASS switch isolator conforming to the ind...

Страница 24: ...Battery Box are open Remove the terminal cover of the Battery Box see Opening the UPS and the Battery Box Connect the earth terminals of the UPS and the Battery Box using the yellow green wire of the...

Страница 25: ...panel of the UPS Installing and running UPSTools Follow the installation and operating instructions given in the software manual present in the UPSTools folder of the CD ROM Making the setting from t...

Страница 26: ...plied the internal temperature and the state of efficiency of the batteries The block diagram below shows each of the parts that make up the UPS Block diagram of the UPS IMPORTANT Our UPS are designed...

Страница 27: ...information as provided in the Connecting the Battery Box to the UPS paragraph this can lead to the battery fuses becoming damaged If this happens contact the customer services department immediately...

Страница 28: ...s present check which terminal board input and or bypass the error code shown on the display corresponds to see the Alarm Codes paragraph correct the position of the wires of the terminal board indica...

Страница 29: ...sition Keep the Battery Start button situated behind the door pressed for about 5 sec The UPS will be started and the display turned on Press the button to gain access to the power on menu When prompt...

Страница 30: ...s containing all the data related to the menu chosen UPS STATUS ERRORS FAULTS Area indicating the operating status of the UPS The first line is always active and constantly shows the current status of...

Страница 31: ...29 DISPLAY MENUS...

Страница 32: ...f may result in injury to the operator and damage the equipment Below is a list of the operations to be performed in order to carry out maintenance work on the equipment without shutting off the power...

Страница 33: ...ation paragraphs For example the socket can be disconnected after a given time of battery operation or when the battery low prealarm threshold is reached or an overload occurs POWER WALK IN The UPS ha...

Страница 34: ...CP Autonomy limitation Sets the maximum time of operation on battery power Disabled Disabled complete battery discharge 1 65000 in steps of 1 sec SW Battery low prealarm Sets the estimated autonomy ti...

Страница 35: ...vity Enabled High sensitivity Enabled Low sensitivity Disabled with input output synchronization Disabled without input output synchronization SW Inverter synchronization External Sync Selects the sou...

Страница 36: ...programmable contacts RS232 AND USB CONNECTORS RS232 CONNECTOR USB CONNECTOR 4 3 1 2 PIN NAME TYPE SIGNAL 1 IN 2 TX OUT Serial line TX 3 RX IN Serial line RX 4 5 GND POWER 6 OUT 7 8 15V POWER Isolate...

Страница 37: ...when the mains voltage is present the UPS resumes operation from the inverter If the jumper is removed when there is no mains voltage present the UPS resumes operation from the battery 4 5 12 BATTERY...

Страница 38: ...ted when the UPS switches to bypass to compensate for the surge current due to the activation of a distorting load Sound C The signal is emitted when the UPS switches to battery operation before the b...

Страница 39: ...llow the instructions given by the installation program For more detailed information on how to install and use the software consult the manual present in the Manuals folder of the CD Rom provided To...

Страница 40: ...SWITCH BEHIND DOOR IS SET TO 0 Set the switch to 1 ISOLATOR BEHIND DOOR SWIN IS OPEN Close the isolator MAINS VOLTAGE NOT PRESENT BLACKOUT Check that the mains voltage is present If necessary power o...

Страница 41: ...the maintenance bypass SWMB turn the UPS off and on again Exclude the maintenance bypass If the problem persists call your local service centre THE DISPLAY SHOWS ONE OR MORE OF THE FOLLOWING CODES F0...

Страница 42: ...S THE CODE S06 THE BATTERIES ARE DISCHARGED THE UPS WAITS FOR THE BATTERY VOLTAGE TO EXCEED THE THRESHOLD SET Wait for the batteries to recharge or force power on from the System On menu THE DISPLAY S...

Страница 43: ...local service centre THE DISPLAY SHOWS ONE OR MORE OF THE FOLLOWING CODES F37 L37 AMBIENT TEMPERATURE IS OVER 40 C HEAT SOURCES CLOSE TO THE UPS VENTILATION SLITS OBSTRUCTED OR TOO CLOSE TO WALLS FAU...

Страница 44: ...recharge S08 Economy mode enabled S09 Ready for power on S10 UPS locked load not powered S11 UPS locked load on bypass S12 BOOST stage or battery charger locked load not powered Command indicates that...

Страница 45: ...utside tolerance limits A18 Voltage on bypass line out of range A19 Overcurrent peak on output Phase 1 A20 Overcurrent peak on output Phase2 A21 Overcurrent peak on output Phase 3 A22 Load on Phase1 u...

Страница 46: ...acitors failed F10 Precharge of negative branch capacitors failed F11 BOOST stage anomaly F12 Incorrect bypass phase direction F14 Sine wave of inverter phase1 distorted F15 Sine wave of inverter phas...

Страница 47: ...tage L16 Phase3 inverter overvoltage L17 Phase1 inverter undervoltage L18 Phase2 inverter undervoltage L19 Phase3 inverter undervoltage L20 Direct voltage at output of inverter or Sine wave of Phase1...

Страница 48: ...of output voltage with respect to output voltage 400Vac 1 Static stability 3 0 5 Dynamic stability 3 resistive load 4 EN62040 3 performance class 1 distorting load Output voltage harmonic distortion...

Страница 49: ...190Kg 195Kg Modes and efficiency values Operating modes True on line double conversion ECO mode Smart Active mode Stand by Off Emergency AC AC efficiency in on line mode 93 5 94 AC AC efficiency in Ec...

Страница 50: ...put voltage within the range of precision indicated it may have to be recalibrated after a long period of operation 2 If the mains frequency is within 5 of the selected value the UPS is synchronized w...

Отзывы: