33
FUNCTION
DESCRIPTION
DEFAULT
POSSIBLE SETTINGS
MOD.
Advanced Functions
Input frequency
tolerance
Selects the allowed
input frequency range
for the switch to bypass
and synchronization of
the output
± 5%
•
± 0.25%
•
± 0.5%
•
± 0.75%
•
± 1 ÷ ±10 in steps of 1%
SW
Bypass voltage
thresholds
Selects the voltage
range allowed for the
switch to bypass
Low:
180V
High:
264V
Low: 180 ÷ 200 in steps of 1V
High:
250 ÷ 264 in steps of 1V
SW
Bypass voltage
thresholds for ECO
Selects the allowed
voltage range for
operation in ECO mode
Low:
200V
High:
253V
Low: 180 ÷ 220 in steps of 1V
High:
240 ÷ 264 in steps of 1V
SW
Activation
sensitivity for ECO
Selects the activation
sensitivity for operation
in ECO mode
Normal
•
Low
•
Normal
•
High
CP
Power supply of
load in stand-by
Power supply of load on
bypass with UPS off
(stand-by status)
Disabled (load
NOT powered)
•
Disabled (not powered)
•
Enabled (
powered
)
SW
Bypass operation
Selects operating mode
of bypass line
Enabled /
High sensitivity
•
Enabled / High sensitivity
•
Enabled / Low sensitivity
•
Disabled with input / output
synchronization
•
Disabled without input / output
synchronization
SW
Inverter
synchronization
(External Sync)
Selects the source of
synchronization for the
inverter output
From bypass
line
•
From bypass line
•
From external input
SW
Power-on delay
Selects the pause time
for automatic
reactivation after mains
power has been
restored
5 sec.
•
Disabled
•
1 ÷ 255 in steps of 1 sec.
CP
Power Walk-in
Enables the mode for
gradual return to mains
power
Disabled
•
Enabled
•
Disabled
SW
Duration of
Power Walk-in
Sets the duration of the
gradual return to mains
power (only if Power
Walk-in is enabled)
10 sec
Min.: 1 sec. - Max.: 30 sec.
SW
Speed of
synchronization
between inverter
and bypass line
Selects the speed of
synchronization
between the inverter
and the bypass line
1 Hz/sec
•
0.5 Hz/sec
•
1 Hz/sec
•
1.5 Hz/sec
•
2 Hz/sec
SW
External
temperature probe
(
optional
)
Enables reading of the
external temperature
probe
Not enabled
•
Not enabled
•
Enabled
SW
* When these output voltage values are set, the output power of the UPS is reduced (see “Reducing the Load (to 200V
and 208V)” paragraph)