![FW Murphy Centurion C5 M-VIEW Touch 10 Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/fw-murphy/centurion-c5-m-view-touch-10/centurion-c5-m-view-touch-10_operation-manual_2352709009.webp)
Section 50
00-02-1032
2020-12-08
-
3 -
C5-1 Digital Input LED Indicators
– Digital Inputs
Green LED:
On - Input active (DC+ or -)
Off - Input active (open)
C5-1 Digital Output LED Indicators
– Relay Outputs, FET DC+, FET DC-
Green LED:
On - Output on
Off - Output off
C5-1 Communication LED Indicators
- RS232, RS485, CAN bus
RED LED:
Flash - Unit is transmitting data to device
Off - No communication active
GREEN LED:
Flash - Unit is receiving data
Off - No communication active
RS232
RS485
CAN bus
C5-1 DIP Switch Setting
Switch 1-8:
Modbus Slave Address function for RS485-2 / RS232-2
Selectable 1-253
If set to address 0, RS485-2 and RS232-2 ports default to 9600 baud.
Set to address 1 to connect to the controller if settings are not known. This is the
default setting from the factory.
Switch 9:
Set to ON to enable CAN1 line termination if C5-1 is at the end of the CAN bus
network.
Switch 10:
Set to ON to enable CAN2 line termination if C5-1 is at the end of the CAN bus
network.