Section 50
00-02-1032
2020-12-08
-
11 -
Stops, Faults and Alarms
Normal Stop
When a normal stop is issued and the unit is running, the system will start a normal shut-down sequence.
1. To issue a normal stop, touch and hold the Run Stop icon on the display for 2 seconds.
2. On the display, the Unit State will read Cooldown, and the Cooldown state delay will begin timing (if
configured).
3. After the Cooldown is completed, the Unit State will read Stopping.
4. When everything has been recognized as back to normal, the Unit State will read Panel Ready.
Fault Shutdown
The Centurion will continually monitor for Fault or ESD shutdown events which require the equipment to stop
immediately or prevent it to start.
On the display, the Unit State will read Shutdown, and an Alarm Shutdown Banner will appear on most Operating
screens.
The cause of the event is recorded and can be viewed on the Shutdown History screen with time and date of
occurrence.
1. The Shutdown History screen displays information of the fault, touch the Book icon for troubleshooting.
a. <Centurion Home Screen / FN / Shutdown History>
2. The Shutdown Snapshot screen displays the values of the unit running at the time a fault occurred.
a. <Centurion Home Screen / FN / Shutdown History/ Right Arrow to scroll >
3. Once the corrections are made, clear the Shutdown condition by touching the Reset icon on the screen.
4. Always make corrections on the unit before attempting to restart the equipment.
Alarms
If an alarm condition is detected, the Alarm/Shutdown banner on the bottom of the screen shows the active alarm
messages in the system. Alarms may be configured as self-clearing or as requiring acknowledgement. Self-
clearing alarms will auto clear if
they’re no longer present. Alarms requiring acknowledgement will persist until the
ACK key is pressed.
1. Select alarm from the Active Alarms screen. (This screen displays up to 20 active alarms.)
a. <Centurion Home Screen / FN /Active Alarms>
2. Touch the ESC ACK icon to acknowledge the Active Alarm.