If LOCK is selected for EIFN, terminals 16 & 17 will act as remote lock input.
Turning the remote lock switch on will keep all the parameter setting from been
changed. If the switch is opened the lock indicator is extinguished and the
up/down key is enabled.
Setup
Setup
EIFN = LOCK
EIFN = LOCK
Figure 3-7
Remote Lock
Figure 3-7
Remote Lock
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Remote
Lock
EI+
EI
If L_AN (Limit annunciator) is selected for OUT2, the output 2 will act as a Limit
Annunciator. If the limit is or has been reached and the RESET key (or remote
reset contacts)has not been pressed since the limit was reached, then the limit
annunciator output will be energized and the OP2 indicator will be lit and
remain unchanged until the RESET key or remote reset input is applied.
There are three reference data contained in setup menu. The reference
data are read only data. The maximum historical PV, displayed by
,which shows the maximum process value since the last UNLOCK
operation. The minimum historical PV, displayed by , which shows
the minimum process value since the last UNLOCK operation. The
abnormal time, displayed by ,which shows the total accumulated
time (minutes) during the process has been in abnormal condition since
the last UNLOCK operation.
The values of reference data will be initiated as soon as the RESET key is
pressed for 4 seconds (UNLOCK operation). After UNLOCK operation, the
PV.HI and PV.LO values will start from the current process value and T.ABN
value will start from zero.
There are three display mode strategies. DISP=SAFE, unit will display the
word SAFE in the setpoint display whenever L41 is in a Non-Limit condition.
If a Limit condition occurs, SAFE is replaced by the set limit value .Once
the limit temperature returns to a Non-Limit condition, SAFE will be
displayed again.
Selecting either HSP1 or LSP1 will show the appropriate limit setpoint during
all operation of the L41.
Limit process variable is displayed at all times, regardless of DISP selection
Содержание LIMIT L41
Страница 1: ...R R RoHS RoHS...
Страница 38: ...Examples Examples 38 UM L41 Rev 2 SP2 200 AL MD NORM Examples Examples AL HY 10 0 AL FN PV H A...
Страница 42: ...Chapter 5 Calibration Chapter 5 Calibration 42 UM L41 Rev 2...
Страница 50: ...Table 5 1 Input Characteristics Table 5 1 Input Characteristics 50 UM L41 Rev 2...
Страница 51: ...51 UM L41 Rev 2...
Страница 52: ...UM L41 Rev 2 Future Design Controls Inc...