HIGH/LOW LIMIT OPERATION
HIGH/LOW LIMIT OPERATION
If Hi.Lo is selected for OUT1, the unit will perform high/low limit control.
When power is applied the OUT1 relay is de-energized. After 6.5
seconds self-test period, if the process is below the high limit set point
(HSP1) and above the low limit set point (LSP1), the output 1 relay will
be energized and OP1 indicator will go off. If the process goes above
the high limit set point or below the low limit set point, the relay will be
de-energized, the OP1 indicator will go on and the display will show
the process value. After the process is within the normal operation
range, and the RESET key is pressed or the remote reset input is
applied, the relay will be energized and the OP1 indicator will go off.
LSP1+O1.HY
HSP1
LSP1
HSP1 O1.HY
ON
OFF
OUT1 Relay
A, B, C, D, E, F =Reset is applied
O1.HY= Output1 hysteresis
Figure 1-6 High/Low Limit Operation
Figure 1-6 High/Low Limit Operation
A
B C
D
E F
15
UM L41-Rev 2