Press scroll key until the display shows
. Simulate a 60mV signal
to terminals 12 and 13 in correct polarity . Press scroll key for at
least 5 seconds then release scroll key. The display will blink a moment
and a new value is obtained . Otherwise , if the display didn't blink or if the
obtained value is equal to -199.9 or 199.9, then the calibration fails.
Perform
function ( if required ) for input 1.
step 4 to calibrate voltage
Press scroll key until the display shows
. Simulate a 60mV signal
to terminals 12 and 13 in correct polarity . Press scroll key for at
least 5 seconds then release scroll key. The display will blink a moment
and a new value is obtained . Otherwise , if the display didn't blink or if the
obtained value is equal to -199.9 or 199.9, then the calibration fails.
Perform
function ( if required ) for input 1.
step 4 to calibrate voltage
Change the DIP switch for the Voltage input. Press scroll key until
the display shows
. Send a 10 V signal to terminals 12 and
13 in correct polarity. Press scroll key for at least 5 seconds then
release scroll key. The display will blink a moment and a new value
is obtained . Otherwise, if the display didn't blink or if the obtained
value is equal to -199.9 or 199.9 , then the calibration fails.
Change the DIP switch for the Voltage input. Press scroll key until
the display shows
. Send a 10 V signal to terminals 12 and
13 in correct polarity. Press scroll key for at least 5 seconds then
release scroll key. The display will blink a moment and a new value
is obtained . Otherwise, if the display didn't blink or if the obtained
value is equal to -199.9 or 199.9 , then the calibration fails.
Change the DIP switch for the RTD input . Press scroll key until the
display shows
. Send a 100 ohms signal to terminals 11, 12
and 13 according to the connection shown below:
Change the DIP switch for the RTD input . Press scroll key until the
display shows
. Send a 100 ohms signal to terminals 11, 12
and 13 according to the connection shown below:
Perform both
( if required )
for input 1.
steps 5 and 6 to calibrate
function
RTD
Perform both
( if required )
for input 1.
steps 5 and 6 to calibrate
function
RTD
Step 1.
Step 1.
Step 3.
Step 3.
Step 4.
Step 4.
With
on the display short terminals12 and 13 , then press scroll
key for at least 5 seconds and release scroll key. The display will blink a
moment and a new value is obtained. Otherwise, if the display didn't
blink or if the obtained value is equal to -360 or 360, then the
calibration fails.
With
on the display short terminals12 and 13 , then press scroll
key for at least 5 seconds and release scroll key. The display will blink a
moment and a new value is obtained. Otherwise, if the display didn't
blink or if the obtained value is equal to -360 or 360, then the
calibration fails.
Step 2.
Step 2.
Step 5.
Step 5.
Press both the scroll key and down keys simultaneously and release them
quickly.
Will appear on the top display.
In the bottom display.
Continue to press the scroll and down arrow keys simultaneously until
appears on the top display. Then press and hold the scroll key only for at least 5
seconds and release the key. The top Display should now show
You
have now entered into the calibration mode. You can now begin with ADO
calibration routine or use the scroll key to advance to the calibration required.
NOTE: Outputs now transfer to there failure transfer mode values.
Press both the scroll key and down keys simultaneously and release them
quickly.
Will appear on the top display.
In the bottom display.
Continue to press the scroll and down arrow keys simultaneously until
appears on the top display. Then press and hold the scroll key only for at least 5
seconds and release the key. The top Display should now show
You
have now entered into the calibration mode. You can now begin with ADO
calibration routine or use the scroll key to advance to the calibration required.
NOTE: Outputs now transfer to there failure transfer mode values.
11
12
13
FDC-9300
100 ohms
Set the lockout DIP switch to the unlocked condition ( both switches
3 and 4 are off ).Dip switches must be set correctly for calibration performed.
Set the lockout DIP switch to the unlocked condition ( both switches
3 and 4 are off ).Dip switches must be set correctly for calibration performed.
Perform step 1 to ENTER calibration mode.
Perform step 1 to ENTER calibration mode.
*
*
*
*
Press the scroll key for at least 5 seconds then release scroll key. The
display will blink a moment, otherwise the calibration fails.
Press the scroll key for at least 5 seconds then release scroll key. The
display will blink a moment, otherwise the calibration fails.
1
2
3
4
ON
DIP Switch Position
DIP Switch Position
T/C input
T/C input
1
2
3
4
ON
1
2
3
4
ON
DIP Switch Position
DIP Switch Position
DIP Switch Position
DIP Switch Position
0 10V input
0 10V input
RTD input
RTD input
Figure 4.1
RTD Calibration
Figure 4.1
RTD Calibration
39
UM9300 2.0
UM9300 2.0
Manual Calibration Procedures
Manual Calibration Procedures
Perform
converter and
converter. The DIP switch is set for T/C input.
step 2 to calibrate
of A to D
step 3 to
calibrate
of A to D
Zero
gain
Perform
converter and
converter. The DIP switch is set for T/C input.
step 2 to calibrate
of A to D
step 3 to
calibrate
of A to D
Zero
gain