![Functional Devices RIB RIBTW2401B-WIUI-N4 Скачать руководство пользователя страница 1](http://html.mh-extra.com/html/functional-devices/rib-ribtw2401b-wiui-n4/rib-ribtw2401b-wiui-n4_manual_2346123001.webp)
Functional Devices, Inc.
• p: 800.888.5538 • f: 765.883.7505 • www.functionaldevices.com • [email protected]
082014
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Operate Time:
Green LED:
Green LED:
Yellow LED:
Pink LED:
Red LED:
Dimensions:
Wires:
Approvals:
Housing Rating:
Gold Flash:
Relay Override Switch:
Wifi:
One (1) SPDT Continuous Duty Coil
10 million cycles minimum mechanical
-30 to 140° F
18mS
Device Status
Wifi Ad-Hoc Status
Wifi Infrastructure Status
Digital Input Status
Relay Status
4.28˝ x 7.00˝ x 2.00˝ with .75˝ NPT Nipple
16˝, 600V Rated
UL Listed, UL916, C-UL
FCC, CE, RoHS, Wifi Certified ASD Device
UL Accepted for Use in Plenum, NEMA 4X
No
DIP Switch Control
IEEE 802.11 b/g/n Compatible, (G)
54 Mbps Data Rate
-91 dBm Min. Sensitivity
+102 Bm Max Output Power
Currently Unsecured Connection
(WPA-PSK or WPA-2-PSK Available)
Supports PING and ARP
DSSS Modulation
RIBTW2401B-WIUI-N4
Wifi IEEE 802.11 Network Enclosed I/O Device: One Discrete Output (20 Amp Relay SPDT +
Override), One Discrete Input (Dry Contact, Class 2); Two Universal Inputs;
24 Vac/dc, 120 Vac Power
Code Version 3.3.9
Power Input:
24 Vac = Terminal Strip (20 Vac min. ; 28 Vac max.)
24 Vdc = Terminal Strip (24 Vdc min. ; 28 Vdc max.)
120 Vac = Wht/Blk Wire
Neutral = Wht/Yel Wire
Device Settings by Network:
•
Power up default relay state
•
Host name and location labels
•
Relay bound to digital input
•
Current threshold for go/no-go status
•
Load voltage entry for power conversion
Device Settings:
•
Local Override
•
Reset to Network Defaults Pushbutton
Specifications
Network Compatible Relay
Power Input Ratings:
158 mA Max @ 24 Vac
110 mA Max @ 24 Vdc
55 mA Max @ 120 Vac
Available TCP/IP Settings:
•
IP Address (Static)
•
Port Number
•
Subnet Mask
•
Gateway
•
Ad-Hoc mode
•
Infrastructure mode
•
Scan for wireless networks
Contact Ratings:
20 Amp Resistive @ 277 Vac
5 Amp Resistive @ 480 Vac
20 Amp Ballast @ 277 Vac
16 Amp Electronic Ballast @ 277 Vac (N/O)
10 Amp Tungsten @ 120 Vac (N/O)
1110 VA Pilot Duty @ 277 Vac
770 VA Pilot Duty @ 120 Vac
1 HP @ 120 Vac
2 HP @ 277 Vac
•
Setup Instructions available
on website.
http://www.functionaldevices.com/pdf/
bulletins/B1783_393223.pdf
Or scan QR code with your smart phone.
Made in USA
Meets
“
Buy American
”
of ARRA 2009
COM
N/C
N/O
Pink LED = DI S
ta
tus
Gr
een LED = D
evic
e S
ta
tus
Red LED = R
ela
y S
ta
tus
Yello
w LED = I
nfr
astruc
tur
e S
ta
tus
Gr
een LED = A
d-Hoc S
ta
tus
+ 5V
UI1 COM
Universal Input 1
+ 5V
UI2 COM
Universal Input 2
Relay
Operation
AUTO
OFF
ON
SW 1
SW 2
X
COM
General
Purpose
Dry Contact
Input
Relay Contacts
DI
RESET to Factory
Defaults Pushbutton
UI1
420
UI2
420
COM
24Vac
24Vdc
24V Optional
Power Input
Term A: (Not used)
Term B: 120 Vac
Term C: Neut
120 Vac Optional
Power Input
Shown
With
Cover
CAUTION: Remove all connections to UI 1 and UI 2 when setting input.
Universal Input: Configurable by internal device web page, accessible in either Ad-Hoc or Infrastructure.
• Analog value returned, user configurable min. and max. scale, and label, 0-5 Vdc, 0-10 Vdc, or 4-20 mA
*
• Direct temperature reading from Type T2 Thermistor.
• Digital Input, connect b5 Vdc and UI input.
*
4-20 mA, when used, requires jumper to be installed on UI set for 4-20 mA input. Jumper MUST be
removed when UI input used as anything other than 4-20 mA.
Wi-Fi RIB™