393313 • 08/03/20
Functional Devices, Inc.
101 Commerce Drive
Sharpsville, IN 46068
Toll Free:
(800) 888-5538
Office:
(765) 883-5538
Fax:
(765) 883-7505
Email:
Website:
www.functionaldevices.com
2
26 ft.
32 ft.
26 ft.
0ft
0m
8
10
12
0ft
6
12
18
24
6
12
18
24
SIDE VIEW
DETECTION AREA
TOP VIEW
PIR Optical View Pattern
Ultrasonic Detection Pattern
Major Motion, e.g. body Smaller Body Movement
PIR Detection Range PIR Detection Range
Ultrasonic Detection Range Ultrasonic Detection Range
3
1
4
2
1
1
2
2
4
4
3
3
Detection Range
at 8 ft height
a. Test Mode:
This mode is used to set the Delayed-OFF Time to 5 seconds for
test mode.
1. Ensure Power is On
2. Remove the cover from the Operation Control Console
defaulted to the OFF position.
4. To enter Test Mode, move the switch from OFF to ON and then back to OFF. IF
B3 is already in the ON position, test mode can be entered by just moving it
back to the OFF position.
b. Notes for Test Mode:
1. The Delayed-OFF Time will remain in the 5 second test mode for 15 minutes. It
the black adjustment knob in the control console and exit test mode.
2. To manually take the sensor out of the test mode, move switch B3 from OFF to
ON and back to OFF again.
Infrared Range
Range setting
Full CCW = min.(OFF)
Full CW = max.
Ultrasonic Range
Range setting
Full CCW = min.(OFF)
Full CW = max.
Factory Default
Factory Default
Delayed-OFF time
30sec
5min 10min 20min 30min
Full CCW = min.(5 sec.)
Full CW = max.(30 min.)
Factory Default
Day light Sensor
20 FC
40 FC
80 FC 160 FC 320 FC
Full CCW = Lights stay OFF
Full CW = Lights always turn ON (NO daylight override)
Factory Default
SETTINGS:
(Fig. Operation control console)
All aspects of sensor operation can be adjusted here
a. Ultrasonic Adjustment-
For maximum range, set fully clockwise (CW).
If reduced range is required, then turn counterclockwise (CCW) and test
Detection.
b. Infrared Adjustment-
For maximum range, set fully clockwise (CW). If
reduced range is required, then turn counterclockwise (CCW) and test
c. Delayed-OFF Time Adjustment:
Each time motion is detected, the
load remains activated for a pre-set time, which is set by the
Delayed-OFF Time Adjustment, The fully CCW setting (30 seconds) can
be used for testing. The fully clockwise setting is 30 Minutes. If motion is
detected during the ON time, then the load remains activated until the
full ON time has passed since the latest motion detection.
d. Daylight Sensor Adjustment:
This level needs to be set in a room
where natural light is at the desired level for the lighting load to not be
turned on. The sensor will still see motion (indicated by the red LEDS)
1. Set the daylight sensor knob to fully counter clockwise (lowest level)
3. Turn the daylight sensor knob clockwise until the light turns on.
5. This will be the setting
A
B
will then automatically reset to the Delayed-OFF Time setting as defined by