A1848
17
Wi-Fi RIB
™
– Control and Status by HTTP Commands and XML
HTTP Get commands to control relay and get status bypassing Wi-Fi RIB™ webpage. Status returned in XML format.
To turn relay on and off:
http://192.168.100.10/index.htm?relay=on
http://192.168.100.10/index.htm?relay=off
To configure relay power up state:
http://192.168.100.10/config.htm?pwr=on
http://192.168.100.10/config.htm?pwr=off
http://192.168.100.10/config.htm?pwr=last
To configure whether relay is bound or unbound to digital input:
http://192.168.100.10/config.htm?dry=on
http://192.168.100.10/config.htm?dry=off
To set name and location:
http://192.168.100.10/config.htm?host=user defined text* (16 characters max)
http://192.168.100.10/config.htm?loc=user defined text* (16 characters max)
* Follow standard URL encoding. Avoid non-alphanumeric characters as they may be interpreted as Escape Codes and may cause errors.
To reset device:
http://192.168.100.10/reset.htm
To configure Universal Inputs 1 and 2:
The universal inputs can be set up via 4 different methods; manually through the web page via a PC/Smart Phone, sending HTTP GET commands to the
device over the network from a controller, or thru a web browser, or by clicking on predefined setup links, similar to bookmarks in a web browser, or click-
able links within a Word document.
There are 5 different modes that the universal inputs support.
1. di05 – 0-5Vdc input mode with OPEN or CLOSED feedback. If input is less than or equal to 0.5 Volts, the digital input status will show “OPEN”. When the
input voltage is greater than or equal to 4.5 volts, the digital input status will show “CLOSED”. When the input voltage is in between, the digital input status
will show “NULL”.
2. 010 – 0-10Vdc input mode.
3. 420 – 4-20mA input mode – with additional hardware jumper installed.
4. therf – Type 2 thermistor input mode with results in Fahrenheit.
5. therc – Type 2 thermistor input mode with results in Celsius.
The 0-5Vdc, 0-10Vdc, and the 4-20mA inputs all support using minimum and maximum scaling (floating point values), and provide a measurement units
entry field. i.e. If input is set to 0-5Vdc input, with a minimum scale value of 0.00, and a maximum scale value of 100, with units set to Volts. A 2.5 Volt input
would produce a 50% result. If scales were changed to min of 0, and a max of 5, then a 2.5Vdc input would produce a 2.5Vdc one for one result.
Example usage for setup for UI1 and UI2, via controller, or web browser.
http://192.168.100.10/ config.htm?ui1=di05&min1=0.00&max1=100.00&unt1=Vdc
http://192.168.100.10/ config.htm?ui1=therf
http://192.168.100.10/ config.htm?ui2=010&min2=0.00&max2=10.00&unt2=Vdc
http://192.168.100.10/ config.htm?ui2=therc
ui1 = Universal Input Mode 1. Set to any of 5 listed modes above
ui2 = Universal Input Mode 2. Set to any of 5 listed modes above
min1 = minimum scale for use with UI1 in floating point format
max1 = maximum scale for use with UI1 in floating point format
min2 = minimum scale for use with UI2 in floating point format
max2 = maximum scale for use with UI2 in floating point format
unt1 = Units used for UI1 – up to 9 characters of text
unt2 = Units used for UI2 – up to 9 characters of text
Example commands use factory default IP address:
192.168.100.10. If you have changed the IP address
of the Wi-Fi, then use your address in the commands.
RIBTW2401B-WIUI-N4 BULLETIN (CONT.)
Содержание RIBTW2401B-WIUI-N4T
Страница 1: ...A1848 EXPAND YOUR NETWORK EXPAND YOUR CONTROL Wi Fi RIB USER MANUAL...
Страница 5: ...A1848 Ad Hoc Wireless Application Single Zone Application BAS CONTROLLER ROUTER 04...
Страница 6: ...A1848 Single Wireless Zone Application using Gateway BAS CONTROLLER ROUTER GATEWAY DEVICE 05...
Страница 9: ...A1848 BAS CONTROLLER BRIDGE POE ROUTER BRIDGE POE Long Distance Control 08...