Functional Devices, Inc. RIBTW2401B-WIUI-N4T Скачать руководство пользователя страница 18

A1848

17

Wi-Fi RIB

 – Control and Status by HTTP Commands and XML

HTTP Get commands to control relay and get status bypassing Wi-Fi RIB™ webpage. Status returned in XML format.

To turn relay on and off:

http://192.168.100.10/index.htm?relay=on

http://192.168.100.10/index.htm?relay=off

To configure relay power up state:

http://192.168.100.10/config.htm?pwr=on

http://192.168.100.10/config.htm?pwr=off

http://192.168.100.10/config.htm?pwr=last

To configure whether relay is bound or unbound to digital input:

http://192.168.100.10/config.htm?dry=on

http://192.168.100.10/config.htm?dry=off

To set name and location:

http://192.168.100.10/config.htm?host=user defined text*  (16 characters max)

http://192.168.100.10/config.htm?loc=user defined text*  (16 characters max)

* Follow standard URL encoding. Avoid non-alphanumeric characters as they may be interpreted as Escape Codes and may cause errors.

To reset device:

http://192.168.100.10/reset.htm

To configure Universal Inputs 1 and 2:

The universal inputs can be set up via 4 different methods; manually through the web page via a PC/Smart Phone, sending HTTP GET commands to the 

device over the network from a controller, or thru a web browser, or by clicking on predefined setup links, similar to bookmarks in a web browser, or click-

able links within a Word document.

There are 5 different modes that the universal inputs support.

1.  di05 – 0-5Vdc input mode with OPEN or CLOSED feedback. If input is less than or equal to 0.5 Volts, the digital input status will show “OPEN”. When the 

input voltage is greater than or equal to 4.5 volts, the digital input status will show “CLOSED”. When the input voltage is in between, the digital input status 

will show “NULL”.

2.  010 – 0-10Vdc input mode.

3.  420 – 4-20mA input mode – with additional hardware jumper installed.

4.  therf – Type 2 thermistor input mode with results in Fahrenheit.

5.  therc – Type 2 thermistor input mode with results in Celsius.

The 0-5Vdc, 0-10Vdc, and the 4-20mA inputs all support using minimum and maximum scaling (floating point values), and provide a measurement units 

entry field. i.e. If input is set to 0-5Vdc input, with a minimum scale value of 0.00, and a maximum scale value of 100, with units set to Volts. A 2.5 Volt input 

would produce a 50% result. If scales were changed to min of 0, and a max of 5, then a 2.5Vdc input would produce a 2.5Vdc one for one result.

Example usage for setup for UI1 and UI2, via controller, or web browser.

http://192.168.100.10/ config.htm?ui1=di05&min1=0.00&max1=100.00&unt1=Vdc

http://192.168.100.10/ config.htm?ui1=therf

http://192.168.100.10/ config.htm?ui2=010&min2=0.00&max2=10.00&unt2=Vdc

http://192.168.100.10/ config.htm?ui2=therc

ui1 = Universal Input Mode 1. Set to any of 5 listed modes above

ui2 = Universal Input Mode 2. Set to any of 5 listed modes above

min1 = minimum scale for use with UI1 in floating point format

max1 = maximum scale for use with UI1 in floating point format

min2 = minimum scale for use with UI2 in floating point format

max2 = maximum scale for use with UI2 in floating point format

unt1 = Units used for UI1 – up to 9 characters of text

unt2 = Units used for UI2 – up to 9 characters of text

Example commands use factory default IP address: 

192.168.100.10. If you have changed the IP address 

of the Wi-Fi, then use your address in the commands.

RIBTW2401B-WIUI-N4 BULLETIN (CONT.)

Содержание RIBTW2401B-WIUI-N4T

Страница 1: ...A1848 EXPAND YOUR NETWORK EXPAND YOUR CONTROL Wi Fi RIB USER MANUAL...

Страница 2: ...s Wi Fi RIB can do the job for you RIBTW2401B WIUI N4 RIBTW24B WI N4 Wi Fi RIB 01 From the design engineering aspect to the installation of the Wi Fi RIB lower cost and flexibility enables our wireles...

Страница 3: ...trol with results throughout network On Off control throughout network RIBTW2401B WIUI N4Tur RIBTW24B WI N4 02 Parking Lot Lights Air Handling Units Unit Ventilators Temperature Humidity Current Flow...

Страница 4: ...LED DI Status Green LED Device Status Red LED Relay Status Yellow LED Infrastructure Status Green LED Ad Hoc Status 5V UI1 COM Universal Input 1 Universal Input 2 Relay Operation AUTO OFF ON SW 1 SW...

Страница 5: ...A1848 Ad Hoc Wireless Application Single Zone Application BAS CONTROLLER ROUTER 04...

Страница 6: ...A1848 Single Wireless Zone Application using Gateway BAS CONTROLLER ROUTER GATEWAY DEVICE 05...

Страница 7: ...A1848 Multi Device Multi Zone Application Wireless Zone BAS CONTROLLER ROUTER GATEWAY DEVICE SWITCH ROUTER BAS CONTROLLER 06...

Страница 8: ...A1848 ROUTER SWITCH ROUTER ROUTER Proprietary Software ROUTER SWITCH ROUTER ROUTER Software 07 Multi zone Application using Proprietary Software...

Страница 9: ...A1848 BAS CONTROLLER BRIDGE POE ROUTER BRIDGE POE Long Distance Control 08...

Страница 10: ...OUTER WiFi RIB Installations Classroom Classroom Classroom Classroom Classroom Classroom Classroom Classroom Classroom Unit Ventilators Wi Fi RIB Installations PC SOFTWARE BASED ROUTER 09 Energy Savin...

Страница 11: ...A1848 Energy Savings Application Building Automation System Automated Demand Response Load Shed Application Access Point RIBTW24B WI N4 Air Handling Unit 10...

Страница 12: ...Power up default relay state Host name and location labels Relay bound to digital input Device Settings Local Override Reset to Network Defaults Pushbutton Specifications Power Input Ratings 200 mA M...

Страница 13: ...deliberate power cycle or due to power loss Make selection for relay to come on stay off or return to last commanded state After power up the relay will follow commanded states if communications are r...

Страница 14: ...te BOUND User defined label User defined label Factory firmware version relayState OVERRIDDEN OFF relayState lastCommand OFF lastCommand digtalInputState CLOSED digtalInputState powerOnState OFF power...

Страница 15: ...atings 158 mA Max 24 Vac 110 mA Max 24 Vdc 55 mA Max 120 Vac Available TCP IP Settings IP Address Static Port Number Subnet Mask Gateway Address Ad Hoc mode Default Infrastructure mode Scan for wirele...

Страница 16: ...e Settings can be viewed on Main Page status or in the xml status page 1 Change the RIB default IP address port number subnet mask or gateway if desired click save after each setting Note The Wi Fi RI...

Страница 17: ...be necessary to manually return to Ad Hoc Mode Pressing the RESET pushbutton about 5 seconds on the Wi Fi RIB will return it to factory default settings including returning it to Ad Hoc Mode Note 2 Y...

Страница 18: ...4 5 volts the digital input status will show CLOSED When the input voltage is in between the digital input status will show NULL 2 010 0 10Vdc input mode 3 420 4 20mA input mode with additional hardw...

Страница 19: ...entered by customer Universal Input 2 DI status analog range 0 5V must be selected and scale set to 0 5 Other default power on states ON LASTSTATE Other binding state BOUND User defined label User def...

Отзывы: