Functional Devices, Inc. RIBTW2401B-WIUI-N4T Скачать руководство пользователя страница 15

A1848

14

Network Compatible Relay

# Relays & Contact Type:

Expected Relay Life:

Operating Temperature:

Operate Time:

Pink LED:

Green LED:  

Yellow LED:

Green LED:

Red LED:

Dimensions:

Wires:

Approvals:

Housing Rating:

Gold Flash:

Relay Override Switch:

Wifi:

One (1) SPDT Continuous Duty Coil

10 million cycles minimum mechanical

-30 to 140° F

18ms

Digital Input Status

Wifi Ad-Hoc Status

Wifi Infrastructure Status

Device Status

Relay Status

4.28˝ x 7.00˝ x 2.00˝ with .75˝ NPT Nipple

16˝, 600V Rated

UL Listed, UL916, C-UL

 

FCC, CE, RoHS, Wifi Certified ASD Device

UL Accepted for Use in Plenum,  NEMA 4X 

No

DIP Switch Control

IEEE 802.11 b/g/n Compatible, (G)

54 Mbps Data Rate

–95 dBm Sensitivity

+16 dBm Output Power

Currently Unsecured Connection

(WPA-PSK or WPA-2-PSK Available)

Supports PING and ARP

DSSS Modulation

RIBTW2401B-WIUI-N4

Wifi IEEE 802.11 Network Enclosed I/O Device: One Discrete Output (20 Amp Relay SPDT +  

Override), One Discrete Input (Dry Contact, Class 2); Two Universal Inputs; 24 Vac/dc, 120 Vac Power

Code Version 3.3.9

Power Input:

 

24 Vac = Terminal Strip (20 Vac min. ; 28 Vac max.)

24 Vdc = Terminal Strip (24 Vdc min. ; 28 Vdc max.)

120 Vac = Wht/Blk Wire

Neutral = Wht/Yel Wire

Device Settings by Network:

 Power up default relay state

 Host name and location labels

 Relay bound to digital input

Device Settings:

 

 Local Override

 Reset to Network Defaults Pushbutton 

Specifications

Power Input Ratings:

158 mA Max  @  24 Vac 

110 mA Max  @  24 Vdc

55 mA Max  @  120 Vac

Available TCP/IP Settings:

 

 IP Address (Static)

 Port Number

 Subnet Mask

 Gateway Address

 Ad-Hoc mode (Default)

 Infrastructure mode

 Scan for wireless networks

Contact Ratings:

 

20 Amp Resistive  @  277 Vac

5 Amp Resistive  @  480 Vac

20 Amp Ballast  @  277 Vac

16 Amp Electronic Ballast  @  277 Vac (N/O)

10 Amp Tungsten  @  120 Vac (N/O)

1110 VA Pilot Duty  @  277 Vac

770 VA Pilot Duty  @  120 Vac

1 HP  @  120 Vac

2 HP  @  277 Vac

Made in USA

Meets

 

Buy American

 

of ARRA 2009

COM

N/C

N/O

Pink LED = DI S

ta

tus

Gr

een LED = D

evic

e S

ta

tus

Red LED = R

ela

y S

ta

tus

Yello

w LED = I

nfr

astruc

tur

e S

ta

tus

Gr

een LED = A

d-Hoc S

ta

tus

+ 5V

UI1 COM

Universal Input 1

+ 5V

UI2 COM

Universal Input 2

Relay

Operation

AUTO

OFF

ON

SW 1
SW 2

X

COM

General

Purpose

Dry Contact

Input

Relay Contacts

DI

RESET to Factory

Defaults Pushbutton

(Activate with insulated tool)

UI1

420

UI2

420

COM

24Vac

24Vdc

24V Optional

Power Input

Term A: (Not used)

Term B: 120 Vac

Term C: Neut

120 Vac Optional

Power Input

Shown

With

Cover

CAUTION: Remove all connections to UI 1 and UI 2 when setting input.  

Universal Input: Configurable by internal device web page, accessible in either Ad-Hoc or Infrastructure.

• Analog value returned, user configurable min. and max. scale, and label, 0-5 Vdc, 0-10 Vdc, or 4-20 mA

*

• Direct temperature reading from Type T2 Thermistor.
• Digital Input, connect b5 Vdc and UI input.

4-20 mA, when used, requires jumper to be installed on UI set for 4-20 mA input. Jumper MUST be  removed when UI input used as anything other than 4-20 mA.

Wi-Fi RIB

RIBTW2401B-WIUI-N4 BULLETIN

Содержание RIBTW2401B-WIUI-N4T

Страница 1: ...A1848 EXPAND YOUR NETWORK EXPAND YOUR CONTROL Wi Fi RIB USER MANUAL...

Страница 2: ...s Wi Fi RIB can do the job for you RIBTW2401B WIUI N4 RIBTW24B WI N4 Wi Fi RIB 01 From the design engineering aspect to the installation of the Wi Fi RIB lower cost and flexibility enables our wireles...

Страница 3: ...trol with results throughout network On Off control throughout network RIBTW2401B WIUI N4Tur RIBTW24B WI N4 02 Parking Lot Lights Air Handling Units Unit Ventilators Temperature Humidity Current Flow...

Страница 4: ...LED DI Status Green LED Device Status Red LED Relay Status Yellow LED Infrastructure Status Green LED Ad Hoc Status 5V UI1 COM Universal Input 1 Universal Input 2 Relay Operation AUTO OFF ON SW 1 SW...

Страница 5: ...A1848 Ad Hoc Wireless Application Single Zone Application BAS CONTROLLER ROUTER 04...

Страница 6: ...A1848 Single Wireless Zone Application using Gateway BAS CONTROLLER ROUTER GATEWAY DEVICE 05...

Страница 7: ...A1848 Multi Device Multi Zone Application Wireless Zone BAS CONTROLLER ROUTER GATEWAY DEVICE SWITCH ROUTER BAS CONTROLLER 06...

Страница 8: ...A1848 ROUTER SWITCH ROUTER ROUTER Proprietary Software ROUTER SWITCH ROUTER ROUTER Software 07 Multi zone Application using Proprietary Software...

Страница 9: ...A1848 BAS CONTROLLER BRIDGE POE ROUTER BRIDGE POE Long Distance Control 08...

Страница 10: ...OUTER WiFi RIB Installations Classroom Classroom Classroom Classroom Classroom Classroom Classroom Classroom Classroom Unit Ventilators Wi Fi RIB Installations PC SOFTWARE BASED ROUTER 09 Energy Savin...

Страница 11: ...A1848 Energy Savings Application Building Automation System Automated Demand Response Load Shed Application Access Point RIBTW24B WI N4 Air Handling Unit 10...

Страница 12: ...Power up default relay state Host name and location labels Relay bound to digital input Device Settings Local Override Reset to Network Defaults Pushbutton Specifications Power Input Ratings 200 mA M...

Страница 13: ...deliberate power cycle or due to power loss Make selection for relay to come on stay off or return to last commanded state After power up the relay will follow commanded states if communications are r...

Страница 14: ...te BOUND User defined label User defined label Factory firmware version relayState OVERRIDDEN OFF relayState lastCommand OFF lastCommand digtalInputState CLOSED digtalInputState powerOnState OFF power...

Страница 15: ...atings 158 mA Max 24 Vac 110 mA Max 24 Vdc 55 mA Max 120 Vac Available TCP IP Settings IP Address Static Port Number Subnet Mask Gateway Address Ad Hoc mode Default Infrastructure mode Scan for wirele...

Страница 16: ...e Settings can be viewed on Main Page status or in the xml status page 1 Change the RIB default IP address port number subnet mask or gateway if desired click save after each setting Note The Wi Fi RI...

Страница 17: ...be necessary to manually return to Ad Hoc Mode Pressing the RESET pushbutton about 5 seconds on the Wi Fi RIB will return it to factory default settings including returning it to Ad Hoc Mode Note 2 Y...

Страница 18: ...4 5 volts the digital input status will show CLOSED When the input voltage is in between the digital input status will show NULL 2 010 0 10Vdc input mode 3 420 4 20mA input mode with additional hardw...

Страница 19: ...entered by customer Universal Input 2 DI status analog range 0 5V must be selected and scale set to 0 5 Other default power on states ON LASTSTATE Other binding state BOUND User defined label User def...