7.4
Object list
Table 6 - Object list for the switch actuator
ID
Name
Description
Configuration
OBJ 023
Relay 1 - Switch
The switch object to open or close
the relay. The object works for
switch actuator, delay function and
staircase function (1=closed,
0=open).
1 bit
1.001
Flag: C - W -
O
BJ 024
Relay: Force
operation
The relay will be forced open or
closed by setting this object high
according to the ”Forced operation”
parameter setting (”Relay on” or
”Relay off”). This object has the
highest priority for operating the
relay.
1 bit
1.001
Flag: C - W -
OBJ 025
Relay: Disable
staircase function
Disables the staircase timer function
1 bit
1.001
C W - -
OBJ 025
Relay: Disable
delay function
Disables the ON/OFF delay function.
1 bit
1.001
C W - -
OBJ 026
Relay: Change
duration
Object for changing the timer value
for the Staircase function. The value
is stored until next program
download.
2 byte
9.010
C R W -
OBJ 027
Relay: Logic AND
The object works as a AND gate for
the relay output regardless of which
function is enabled. Forced
operation will override the AND
gate. This object has the initial
value of “1” after power-on.
1 bit
1.001
C - W -
OBJ 027
Relay: Logic OR
The object works as an OR gate for
the relay output regardless of which
function is enabled. Forced
operation will override the OR gate.
This object has the initial value of
“0” after power-on.
1 bit
1.001
C - W -
OBJ 028
Relay: Status
switch
Holds the status information about
the relay output (1=relay closed,
0=relay open)
1 bit
1.001
Flag:
C R - T