background image

 

function Innovation & Technology AS 

 

- 11 - 

Manual – KNX MultiLight Art.nr 44001 

Doc.no. D-TS-ML-K-005-A 

 

5.2

 

LUX sensor 

5.2.1

 

Parameters

 

The lux sensor has two communication objects, one for the LUX value (Current Value) 

and a threshold switch (Lux threshold switch). The object, “Lux threshold switch", will be 
high or low based on the LUX value and the parameters below. 
 

 

Figure 6 - Lux sensor parameter  window 

 

1.

 

High threshold value:

 If the Lux value goes above this value the "Lux threshold 

switch" will be set low or no action (depending on the parameter “Action above high 

threshold value”). 

 
2.

 

Hystereses for lower value: “

High threshold value” – “hysteresis for lower value” 

will give the lower limit for the ”Lux threshold switch”. If the current lux value is 
below this value, the Lux threshold switch is set high or no action (depending on the 

parameter “Action below low threshold value”) 

 
3.

 

Time delay

 can be specified both for turning on and off the lux threshold switch. 

The time delay can be between 1 and 255 seconds. The value “0” will disable the 
time delay. 

 

4.

 

Cyclic sending

 of the lux threshold switch can be activated with a cycle time 

between 1 and 255 minutes. 

 

5.2.2

 

LUX calibration 

The lux level object, “Lux  Sensor: Current value (lux)”, can be calibrated by writing to 
the object. The raw lux value will be subtracted from the written value and stored 
permanently in EEPROM/flash. 

 
 

Both raw values and the resulting calibrated values are shown in Figure 7. The pink line 
is the raw value (V) from the sensor, the blue line is the wanted value (W) set by the 

user. The calibration factor is: C=1-(V-W/V)  
 
If the raw value V=1000, and the object is updated with 800, then the calibration factor 

will be: c=1-(1000-800)/1000=0.8. See the graph in Figure 7. 
 

The formula for calculating the lux is: Lux=c*V 

Содержание KNX MultiLight

Страница 1: ...function Innovation Technology AS User s manual KNX MultiLight ML K Article number 44001 Picture KNX MultiLight User Panel ...

Страница 2: ...function Innovation Technology AS 2 Manual KNX MultiLight Art nr 44001 Doc no D TS ML K 005 A ...

Страница 3: ...14 6 3 PARAMETERS 15 6 3 1 Comfort mode 15 6 3 2 Standby mode 16 6 3 3 Night mode 16 6 3 4 Frost Heat protection 16 6 3 5 Basic heating and cooling stage 17 6 3 6 Additional heating and cooling stage 17 6 4 LOCAL TEMPERATURE ADJUSTMENT 18 6 5 REGULATOR FUNCTION 19 6 6 PI REGULATOR 20 6 7 OBJECT LIST 21 7 SWITCH ACTUATOR 24 7 1 PARAMETER 24 7 1 1 Staircase function 24 7 1 2 ON OFF Delay function 25...

Страница 4: ...ght is a demand controlled two step temperature regulator for separate cooling and heating control The functionality of the product can be configured and connected to the rest of the KNX automation system by using the ETS Tools Software see www knx org Example 1 Heating regulator The KNX MultiLight is configured as a two step heating regulator The regulator has one temperature set point for a room...

Страница 5: ... for the room because of lower air temperature in the supplied air The cooling regulator of the KNX MultiLight can trigger the need for extra ventilation based the room temperature Example 4 User control The KNX MultiLight will usually control the climate and lighting automatically Occupants may want to take control over their own environment and change lighting temperature and shutters manually T...

Страница 6: ... 2 Learn mode buttons The red programming LED on the KNX node and inside the lens of the movement detector will be lit when the KNX MultiLight is in learn mode The programming LED will blink when the MultiLight is not programmed un programmed node The node will check communication with movement detector and panel If communication has failed the object Device self test status will be set to 1 When ...

Страница 7: ... that will be removed after the first ETS download 1 The digital inputs will toggle the relay Digital input 1 can be connected to an impuls switch for the luminaire pull cord Pulling the cord will toggle the light on and off 2 Detection of movement is shown by blinking the red LED inside the movement detector lens Figure 3 KNX MultiLight node movement detector and user panel ...

Страница 8: ...anel The calibration mode is activated if both the and buttons are pressed for 5 seconds or more In this mode the temperature LED will start to blink for the calibration setting The and buttons will increase or decrease the measured temperature in steps of 0 5 C So the measured temperature will be adjusted 1 5 C lower if the 3 LED is blinking The adjustment has to be acknowledged by pressing both ...

Страница 9: ...neral can be enabled or disabled The cycle time can be between 1 and 255 minutes 0 disable the function 4 Action for end of detection can be OFF or no reaction 5 Separate Movement Local object The movement detector can be configured with an additional communication object named Movement Local This object can have the following functionality a Semi automatic Movement Local object is not transmitted...

Страница 10: ...neral object 5 1 2 Slave function Movement General The Movement General could be configured with Slave functionality The slave functionality can be enabled by setting the recovery time and the cyclic sending time to a lower value than the Master master detector recovery time or staircase timer The reaction at the end of detection must be set to No reaction 5 1 3 Cyclic sending If the value of cycl...

Страница 11: ...set high or no action depending on the parameter Action below low threshold value 3 Time delay can be specified both for turning on and off the lux threshold switch The time delay can be between 1 and 255 seconds The value 0 will disable the time delay 4 Cyclic sending of the lux threshold switch can be activated with a cycle time between 1 and 255 minutes 5 2 2 LUX calibration The lux level objec...

Страница 12: ...nd the raw value is used if 0 is written to the Current value lux object The object should be set to 0 to clear the current calibration before re calibrating the lux level The lux level calibration is limited to 2 times the raw lux level so the calibration is limited to 2000 if the raw lux level is 1000 5 3 Block diagram Figure 8 Block diagram of movement and lux sensor ...

Страница 13: ... mode it will only transmit at the end of detection In Full automatic the object will transmit both at the start of detection and at the end of detection This object is not cyclic The object can also be dependent on the Lux Threshold Switch 1 bit 1 001 C T Table 3 Object list for the LUX Sensor ID Name Description Configuration OBJ 005 Lux Sensor Current value lux Writing a LUX value to this obj w...

Страница 14: ...mperature set point is defined in parameter Base setpoint in ºC and is shown by object Thermostat Base setpoint This object can also be configured for write access selectable to be stored in permanent memory or not The working regulator set point is shown by the object Thermostat Actual setpoint The base setpoint is only settable to whole degrees eg 21 or 22 C Parameters for heating and cooling te...

Страница 15: ... will turn off the heat at 21 0 ºC with the parameter settings shown in Figure 9 The cooling system will turn on at the temperature Base setpoint in ºC Deadzone between heating and cooling in 0 1K High hysteresis in 0 1K The cooling system will be turned off when the temperature falls below the base set point deadzone The cooling system will be turned off at 21 0 2 0 23ºC with the parameter settin...

Страница 16: ...al setpoint will be 21ºC 2ºC 3ºC 26ºC 6 3 4 Frost Heat protection The Frost Heat protection regulator mode will set fixed temperature setpoints for the heating and cooling regulators The heating system is turned on if the temperature falls below 10ºC 0 5ºC hysteresis The heating system is turned off if the temperature goes above 10ºC The cooling system will turn on if the temperature goes above 35...

Страница 17: ...as dropped 2ºC below the parameter settings in the thermostat parameter window see Figure 9 The hysteresis for the additional heating stage is fixed to 0 5ºC The additional heating stage will turn on if the temperature falls below 21ºC 2 0ºC 19ºC and turn off at 21ºC 2 0ºC 0 5ºC 19 5ºC in comfort mode according to the parameter settings shown in Figure 9 and Figure 10 Figure 10 Heating parameter w...

Страница 18: ... the parameters shown in Figure 9 The cooling system will be turned on at 21ºC 3ºC 2ºC 0 5ºC 20 5ºC and Off if the temperature drops below 20 0ºC It is possible to limit the temperature adjustment up or down for example to 3 to 1C 1 5C to 0 5C and 0 5 to 0C The LED indicating 3 to 3 on the user panel will still show the full scale so the user will not notice the limitation The temperature sensor i...

Страница 19: ...function Innovation Technology AS 19 Manual KNX MultiLight Art nr 44001 Doc no D TS ML K 005 A 6 5 Regulator function Figure 12 Asymmetric regulator functionality ...

Страница 20: ...e value has changed a specific percentage see Figure 13 Figure 13 Heating PI regulator The PI regulator is configured with a proportional factor Kp and a reset time Ti The equation for the regulator output is shown in 3 The integration of the error for each regulator evaluation is substituted by the step number 30 second increments multiplied with the last error function e n n divided by the time ...

Страница 21: ...Table 5 Object list for the Thermostat ID Name Description Configuration OBJ 007 Thermostat Actual temperature This object shows the measured room temperature 0 5K resolution This value can also be combined with obj 008 External temperature The actual temperature is used as the feedback to the regulator This object will be sent automatically when the temperature has changed 0 5K or more This objec...

Страница 22: ...t is set This mode has 2 priority 1 bit 1 001 C W OBJ 013 Thermostat Night mode The regulator goes to Night Mode regulator setting if this bit is set This mode has 3rd priority 1 bit 1 001 C W OBJ 014 Thermostat Frost Heat protection mode The regulator goes to frost heat protection mode regulator setting if this bit is set Frost mode setpoint is permanent at 10ºC Heat protection setpoint is 35ºC f...

Страница 23: ...r than the target cooling temperature hysteresis The cooling will be turned off when the actual temperature obj 007 falls below the target cooling temperature Cyclic sending every 40 min 1 bit 1 001 C R T OBJ 020 Thermostat Control value basic cooling Continuous The output of the PI regulator with the proportional factor and reset time from parameter settings The object can automatically be transm...

Страница 24: ...r the staircase time b Activation and de activation of the staircase function 2 Time delay for turning ON and OFF the relay a Extra object for activation and de activation of the delay function 3 Extra communication object for logical AND or OR function Figure 15 Default parameters for the relay 7 1 1 Staircase function The staircase function is specified by a time duration parameter in minutes Th...

Страница 25: ...ll the other switch actuator functions 7 2 Initial start up and power failure considerations The relay is turned ON for MultiLight units that have not been programmed with ETS This will make the light turn ON as default The digital inputs will toggle the relay When the application program is downloaded to the unit the start up procedure will not include turning on the relay at start up A programme...

Страница 26: ... staircase timer function 1 bit 1 001 C W OBJ 025 Relay Disable delay function Disables the ON OFF delay function 1 bit 1 001 C W OBJ 026 Relay Change duration Object for changing the timer value for the Staircase function The value is stored until next program download 2 byte 9 010 C R W OBJ 027 Relay Logic AND The object works as a AND gate for the relay output regardless of which function is en...

Страница 27: ...e object is high or low depending on the detection of rising or falling edge for the input Parameter choices for the Switch function Rising edge On Rising edge Off Rising edge Toggle Rising edge On Falling edge Off Rising edge Off Falling edge On 8 1 2 Dimming Light dimming functionality with one communication object for Short operation Switch and one for Long operation dimming Parameter choices f...

Страница 28: ...ject for Long operation up down Parameter choices for the shutter control Reaction short operation Stop up Stop down or Stop toggle up down Reaction long operation Up Down or Toggle up down Please note that the action for long operation is locked to Toggle up down if the reaction for short operation is Stop toggle up down 8 2 Block diagram Figure 18 Block diagram for binary inputs ...

Страница 29: ...cted on external input 1 Action on rising edge The action can be Stop down Stop Up or Stop Toggle Up Down depending on parameter 1 bit 1 001 C W T OBJ 030 Binary input 1 Switch This object appears if the input is set to switching The object is transmitted if the pulse on the external input is at least 50mS with no maximum duration Action on rising edge and falling edge Rising On Rising Off Rising ...

Страница 30: ... can be Stop down Stop Up or Stop Toggle Up Down depending on parameter 1 bit 1 001 C W T OBJ 032 Binary input 2 Switch This object appears if the input is set to switching The object is transmitted if the pulse on the external input is at least 50mS with no maximum duration Action on rising edge and falling edge Rising On Rising Off Rising Toggle Rising On Falling Off Rising Off Falling On 1 bit ...

Страница 31: ...44001 Doc no D TS ML K 005 A 9 Mechanical dimensions The KNX node is shown Figure 19 and Movement sensor in Figure XX Figure 19 Mechanical dimensions of ML K in mm 30x120x17 5 Figure 20 Mechanical dimensions of ML M in mm Ø31x21 Figure 21 Mechanical dimensions of ML P ...

Страница 32: ...t Table 8 6p Wago connector for Relay and KNX J1 Table 9 3pin Wago connector J2 Signal Pin number 0 V 1 Binary input 1 2 Binary input 2 3 Table 10 4pin Molex connector two paralel connectors J4 and J5 Signal Pin number 3 7V 1 0 V 2 Com 3 20V 4 Signal Pin number Relay Common 1 Relay Normally Open 2 Not in use 3 Not in use 4 KNX Bus 5 KNX Bus 6 J1 J4 J5 J2 ...

Страница 33: ...function Innovation Technology AS 33 Manual KNX MultiLight Art nr 44001 Doc no D TS ML K 005 A 10 Wiring Diagram ...

Страница 34: ...rent In Permitted cable lengths 2 3 6V 0 5mA 2m Connections KNX Load current circuits and inputs Connection of sensor via connection terminal without screws Wiring 0 5 1 0 mm2 4 pol plug Movementdetector Sensor Detection area 4 m if mounted in a hight of 2 meters EIB KNX operating and display elements Thru separate control panel with plug and LEDs Housing IP20 EIB KNX voltage SELV 24 V DC safety e...

Страница 35: ...function Innovation Technology AS 35 Manual KNX MultiLight Art nr 44001 Doc no D TS ML K 005 A ...

Страница 36: ...4001 Doc no D TS ML K 005 A Producer function Innovation Technology AS fabrikkgaten 5 N 5059 Bergen Norway Doc no D TS ML K 005 A Distributor function Product Solution AS fabrikkgaten 5 N 5059 Bergen Norway Tlf 47 55 38 50 80 Epost post function no Web www function no ...

Отзывы: