RELAY ACTIVATION PROCEDURES FOR FA2 UNITS

 

 

1.  To activate the relays so the remote feature can be used the software will need to be reprogramed via a flash 

drive with a configuration file (fumex.ini) and the USB port on the control board. (Contact Fumex to  acquire 

the correct configuration file for your unit). 

2.  Apply incoming  power  to  the  unit  by  connecting  the  power  cord  and turning the power  switch located near 

the power cord on.  Make sure the blower is not running and the green power light is off.  This is called the 
“Soft On” state.  

3.  Reprogramming will lock out the Control Board  power button.  The ON/OFF function  will only be able to be 

controlled remotely.  

4.  Copy the fumex.ini file onto a flash drive and make sure it is the only file on the flash drive.  If anything else is 

on the flash drive the control board will not know which file to read. 

5.  Plug the flash drive with the desired fumex.ini file into the USB port on the front of the control board.  (Make 

sure the unit is in the 

“Soft On” state before plugging in the flash drive.)  

6.  Initially  the  light  above  the  USB  port  will  be  red.    After  the  reprogramming  is  complete  the  light  above  the 

USB port will turn green and remain lit until the flash drive is removed from the USB port. 

7.  Remove the flash drive and apply 0-24 VDC to the start relay according to the wiring diagram in Figure 1 to 

start the unit. 

 
   

Once  the  relays  have  been  activated  the  unit  will  only  start  by  applying  the 
proper voltage to the start/stop relay.    

 
 
 

RELAY DE-ACTIVATION PROCEDURES FOR FA2 UNITS 

 
1.  To de-activate the relays so the remote feature cannot be used the software will need to be reprogramed via a 

flash  drive  with  a  configuration  file  (fumex.ini)  and  the  USB  port  on  the  control  board.  (Contact  Fumex  to 

acquire the correct configuration file for your unit). 

2.  Apply incoming  power  to  the  unit  by  connecting  the  power  cord  and turning the power  switch located near 

the power cord on.  Make sure the blower is not running and the green power light is off.   This is called the 
“Soft On” state.  

3.  Reprogramming  will  unlock  the  Control  Board  power  button.    The  ON/OFF  function  will  now  be  able  to  be 

controlled at the unit.  

4.  Copy the fumex.ini file onto a flash drive and make sure it is the only file on the flash drive.  If anything else is 

on the flash drive the control board will not know which file to read. 

5.  Plug the flash drive with the desired fumex.ini file into the USB port on the front of the control board.  (Make 

sure the unit is in the 

“Soft On” state before plugging in the flash drive.)  

6.  Initially  the  light  next  to  the  USB  port  will  be  red.    After  the  reprogramming  is  complete  the  light  above  the 

USB port will turn green and remain lit until the flash drive is removed from the USB port. 

7.  Remove the flash drive and start the unit as described in the 

“Controls” section. 

 
 

Once the relays have been de-activated the unit will only start by using the front 
control panel.  All relays will become non-functional.     

Содержание FA2 Series

Страница 1: ...th any solid state speed control device WARNING For general ventilating use only Do not use to exhaust hazardous or explosive materials or vapors WARNING Use only a 15 Amp fuse CAUTION Do not operate without having all filters in place Do not operate any fan with a damaged cord or plug Discard fan or return to an authorized service facility for examination and or repair Do not run cord under carpe...

Страница 2: ...f the cabinet L o c a t i n g t h e a i r c l e a n e r Placing the FA2 as close as possible to the pollution source reduces the amount of ducting needed reduces back pressure lowers power consumption and improves overall performance Placement should minimize hose length and the number of bends Use capture hoods with high efficiency entry whenever possible Make sure to allow top access to the filt...

Страница 3: ...ase in 20 increments until the filter is loaded Red lights will indicate that a filter change is necessary The FA2 contains a VOC sensor to detect odors gases in the exhaust stream The system continually monitors the exhaust stream which is indicated on the bar graph labeled GAS When the gas odor filter becomes saturated and breakthrough of the VOC occurs the GAS warning light will illuminate GENE...

Страница 4: ...d in industrial manufacturing processes GENERAL MAINTENANCE 1 The blower motor s is a sealed unit 24 000 hr MTBF rated It is permanently lubricated and does not require oiling keep it free of dust accumulations to prevent overheating 2 Remove any loose accumulations of dust debris from the air filter chamber periodically This product employs overload protection fuse A blown fuse indicates an overl...

Страница 5: ...ired or replaced at our option free of charge provided it has not been misused abused or otherwise damaged and is returned PREPAID to Fumex LLC 1150 Cobb International Pl Kennesaw GA 30152 There are no warranties which extend beyond the descriptions set forth in this warranty notwithstanding any knowledge of Fumex LLC regarding the use or uses intended to be made of goods proposed changes or addit...

Страница 6: ...e relays have been activated the unit will only start by applying the proper voltage to the start stop relay RELAY DE ACTIVATION PROCEDURES FOR FA2 UNITS 1 To de activate the relays so the remote feature cannot be used the software will need to be reprogramed via a flash drive with a configuration file fumex ini and the USB port on the control board Contact Fumex to acquire the correct configurati...

Страница 7: ...7 Figure 1 ...

Отзывы: