6.1 Display the setup

It  is  possible  to  display  controller  settings  without  editing  them.  To  do  so,  press  the 

  and 

  keys 

simultaneously for 4s, until the 

[SL]

 message appears, and then release it. Select the 

[Fn]

 menu (tap  ) 

and confirm the selection by tapping the 

%

 key. You can then view all controller settings. Navigate the menus 

using keys 

$

 (plus) and 

&

 (minus). Confirm the selection with the 

%

 key.

$

&

$

Display the 
desired setup

Press and hold for 4 sec.

release

the keys

Confirm

Pressing  for  4  sec.  takes 

you back to the start menu

5.7 Display minimum and maximum temperatures, voltage and door 
opening number

Press and hold the

 key for 4s, until the 

[LH]

 message appears, and then release it. The controller will 

indicate the minimum and maximum temperatures of the S1 and S2 sensors (if enabled in 

[S1]

 function), in 

addition to the minimum and maximum voltages and the number of times the door was opened.

 

$

6.3 Time for function blocking

With this function enabled, setups are protected against unauthorized changes, and thus are available for 
viewing only. In this condition, when trying to change these values, the 

[LC]

 message will be displayed.

To block functions, select any value different from 

[no]

 (

[15]

 to

[60]

) on 

[L1]

 setup. This is the pressing 

time required to validate function blocking. To block the keyboard, press and hold the 

%

 key for the time set in 

[L1]

. To unblock, turn off the controller and then turn it on again. As soon as the 

[SF]

 message appears, 

press the 

%

 key for 10s, until the 

[LC]

+

[OF]

 message appears, and then release it.

Block:

Pressing for the time 

configured in 

[L1]

On

Off

Unblock:

When powering the controller, 

press for 10 sec.

6.4 Shut down control functions

As control functions are shut down (

[L2]

), the controller starts to operate as a temperature indicator only, 

with all outputs deactivated. This function can operate in the following ways:

[,0]

 Does not allow control functions to shutdown.

[,1]

 Allows the turning on and off of control functions only if the functions are unlocked.

[,2]

 Allows the turning on and off of control functions even if the functions are blocked.

To turn the control functions on/off, press and hold the 

$

 key for 10s, until the 

[Ct]

message

 

appears, and 

then release it.

NOTE:

 When restarting the control functions, the controller will continue with these functions.

[c1]

 (compressor minimum shutdown time) and

[o5]

 (Defrost when powering the controller).

Press and hold for 10 sec.

release
the key

6.5 Parameters table

DESCRIPTION

FUN

MIN

MAX

UNIT

DEFAULT

CELSIUS (FAHRENHEIT)

[t1]
[t2]
[t3]

[t4]
[t5] 
[t6] 

[t7] 

[h1]
[h2]
[h3] 

[h4]
[h5]
[h6] 

This  is  the  control  temperature  of  the  normal  operating  mode.  When  the  S1  sensor 
temperature (ambient) is lower than the configured value for this function, the compressor 
will be turned off.

This is the control temperature when the power-saving mode is active. If the S1 sensor 
temperature (ambient) is lower than the configured value for this function, the compressor 
will be turned off.

Limits preventing the accidental setup of an excessively high or low temperature setpoint, 
which could result in high energy consumption by keeping the system turned on.

This is the difference between turning cooling OFF and BACK ON in normal operating 
mode. 

Example: If adjusted 

[t1]

=

[4.0]

 and 

[h1]

=

[1.0]

, the compressor will be turned 

off when the S1 sensor temperature (ambient) is less than 

[4.0]

 and it will be turned on 

when it is higher than 

[5.0]

 (

[4.0]

[1.0]

).

This is the difference between turning cooling OFF and BACK ON in power-saving mode.

FUNCTION

-50 (-58)

60 (99)

ºC (°F)

-6.0 (21)

-50 (-58)

60 (99)

ºC (°F)

-50 (-58)

0.1 (01)

8.0 (14)

ºC (°F)

3.0 (05)

-50 (-58)

60 (99)

ºC (°F)

-1.0 (30)

-50 (-58)

60 (99)

ºC (°F)

2.0 (36)

-50 (-58)

60 (99)

ºC (°F)

-6.0 (21)

-50 (-58)

60 (99)

ºC (°F)

-1.0 (30)

-50 (-58)

60 (99)

ºC (°F)

2.0 (36)

-50 (-58)

60 (99)

ºC (°F)

60 (99)

0.1 (01)

8.0 (14)

ºC (°F)

3.0 (05)

Desired temperature (setpoint) (r1)
Desired temperature (setpoint) (r2)
Desired temperature (setpoint) (r3)

Desired temperature (power-saving setpoint) (r1)
Desired temperature (power-saving setpoint) (r2)
Desired temperature (power-saving setpoint) (r3)

Minimum desired temperature (setpoint) allowed to 

the user

Maximum desired temperature (setpoint) allowed to 

the user

[t8]

Control differential of operating setpoint (r1)
Control differential of operating setpoint (r2)
Control differential of operating setpoint (r3)

Control differential of power-saving setpoint (r1)
Control differential of power-saving setpoint (r2)
Control differential of power-saving setpoint (r3)

On

Off

release 
the key

release 
the key

5.6 Display the current temperature on sensor 2 (evaporator) and 
power grid voltage

Press  and  hold  the    key  for  4s,  until  the 

[S2]

  message  appears,  and  then  release  it. The  following 

information will be shown:

NOTE:

 Audible alarm must be turned off.

%

Press and hold for 4 sec.

Evaporator Sensor (S2) (if ena. on S1)

Voltage

Min.Temp. 

1.2ºC)

(ex: 

Max.Temp. 

2.0ºC)

(ex: 

Hundred

Unit

(ex: 120V)

release 
the key

6.2 Changing the configured setup

To change the setup, press and hold the 

 keys simultaneously for 4s, until the 

[SL]

 message 

appears, and then release it. Select the 

[Cd]

 menu (tap  

%

 ) insert the code 

[23]

 and confirm. It is possible 

to change all controller configurations. Navigate the menus using the 

$

 (plus) and 

&

 (minus) keys. Confirm 

selection with the  

%

  key.

$

 and 

&

Insert the access 
code 23

Switches the
desired setup

Confirm

release

the keys

Confirm

Pressing  for  4  sec.  takes

you back to the start menu

Press and hold for 4 sec.

Insert the access
code 31

Insert the 
temperature unit

release

the keys

Press and hold for 4 sec.

5.8 Selecting the unit temperature

The controller temperature can be displayed either in Celsius (ºC) or Fahrenheit (ºF). To set the unit, press 
and hold the 

$

 

and 

&

 keys simultaneously for 4 seconds, until 

 is displayed.

Insert the access code 

[31]

. When accessing the 

[Fn]

 menu, it is possible to switch between the two units. 

Every time the unit changes, the setup should be reconfigured, as all settings return to the "default" values.

[SL]

Confirm

Confirm

Pressing  for  4  sec.  takes 

you back to the start menu

6. ADVANCED OPERATIONS

Voltage

Press and hold for 4 sec.

Appears in the display

Ambient Sensor (S1)

Min. temperature (ex: 1.2ºC)

Max. temperature (ex: 

 

2.0ºC)

Min. temperature (ex: 

 

1.2ºC)

Hundred

Unit

(ex: 135)

Max. temperature (ex: 2.0ºC)

release 
the key

Evaporator Sensor (S2) (if ena. on S1)

Door opening No.

Minimum Voltage (ex: 112V)

Maximum Voltage (ex: 125V)

NOTE: 

If L3 is at 0, the first touch will be to enable the keyboard.

NOTE:

 To reset the values, press key 

$

 

before finalizing the view, and the display 
will show the 

[rt]

 message

NOTE: If L3 is at 0, the first touch will be to enable the keyboard.

Содержание MT-444 eXpress

Страница 1: ...ss and hold for 10 sec release the key On Off release the key On Off 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 Power Saving Mode LED indicator Light LED indicators LED indicator for pre defrost and defrost on or draining blinking Fan LED indicators Compressor LED indicators Power Saving Mode Key Temperature unit LED indicator Plus Key Preset 1 Set Key Preset 2 Minus Key Preset 3 DIGITAL COOLING CO...

Страница 2: ... mode Example If adjusted t1 4 0 and h1 1 0 the compressor will be turned off when the S1 sensor temperature ambient is less than 4 0 and it will be turned on whenitishigherthan 5 0 4 0 1 0 ThisisthedifferencebetweenturningcoolingOFFandBACKONinpower savingmode FUNCTION 50 58 60 99 ºC F 6 0 21 50 58 60 99 ºC F 50 58 0 1 01 8 0 14 ºC F 3 0 05 50 58 60 99 ºC F 1 0 30 50 58 60 99 ºC F 2 0 36 50 58 60 ...

Страница 3: ...ivatedtogetherwiththecompressor This is the amount of time the fan will remain ON if F1 and F2 are configured as automatic whilethecompressorisoff 50 58 60 99 ºC F 5 0 23 no 99 min 10 no 99 min no 50 58 60 99 ºC F 40 99 50 58 60 99 ºC F 20 68 1 99 H 12 1 99 min 30 no 99 min 15 OF On OF no 99 min 1 A d d 1 99 min 1 d3 d4 d5 Determines how often defrost will be performed which is the time counted fr...

Страница 4: ...2 10 10 V 0 2 30 s 4 no 48 H no 0 1 01 20 36 ºC ºF 10 18 0 1 01 50 90 ºC ºF 50 90 no 99 min 1 P3 M Time in minutes H Time in hours M H m F4 F5 F6 F7 F8 P1 P2 This is the amount of time the fan will remain OFF if F1 and F2 are configured as automatic whilethecompressorisoff The fan can be set to remain activated or deactivated in the period when the door is kept open The purpose of this function is...

Страница 5: ...ard If no key is pressed within 10 seconds the keyboard will be hidden again This prevents unwantedactivationsfrombeingperformed 1 The keys always remain on In this mode the first touch is enough to perform functions no 2 no 0 1 0 When control functions are shutdown the controller starts to operate purely as a temperature indicator with all outputs deactivated This function can operate in the foll...

Страница 6: ...essor COMP Defrost DEFR Power supply 115 Vac or in the version 230 Vac Fan FANS Interconnection Cable Sensor S1 Sensor S2 Digital input Door Switch screws not included Copyright 2014 WARRANTY FULL GAUGE CONTROLS Products manufactured by Full Gauge Controls as of May 2005 have a two 02 year warranty as of the date of the consigned sale as stated on the invoice They are guaranteed against manufactur...

Отзывы: