DIGITAL CONTROLLER FOR

REFRIGERATION AND DEFROST

TC-900Ri

power

Ver.01

4. CONFIGURATIONS

- Press

for 2 seconds until appears

, and release it after that. The adjusted operation

temperature will appear.
- Use

and

to change the value and then press

to record it.

4.1 - Control temperature adjust (SETPOINT):

SET

SET

TC900RIPWV02-1T

-1

1548

1. DESCRIPTION

3. TECHNICAL SPECIFICATIONS

TC-900Ri

power

is a control for low temperature ventilated units which automates defrosting

processes, providing great energy saving.
It has two sensors, one for environment temperature and other that, mounted to the evaporator,
commands the end defrost process and puts the fans back to work.

• Counters
• Refrigerating balconies

TC-900Ri power: 90 - 264Vac ±10%( 50/60 Hz)
TC-900RiL power: 12/24 Vac/dc

-50 to 75° C

0 to 50°C

10 to 90% RH (without condensation)

0.1°C from -10 to 75°C and 1°C outside this range /1°F in all range

COMP: 16(8)A/ 250Vac 1HP (compressor, solenoid valve or contactor)

DEFR:

(defrost resistance or hot gas)

FANS: 5(3)A/ 250Vac 1/8HP (evaporator fans)

71 x 28 x 71mm

S1: ambient sensor (black cable)
S2: evaporator sensor (gray cable)

2. APPLICATION

- Power supply:

- Control temperature:
- Operating temperature:
- Operating humidity:
- Resolution:
- Load current (outputs):

- Dimensions:
- Sensors:

Product complies with UL Inc. (United States and Canada).

/ -58 to 167°F
/ 32 to 122°F

8(3)A/ 250Vac 1/4HP

4.2 - Parameters table

Description

Fun

Access code:123 (one hundred and twenty-three)

Control differential (hysteresis)

Offset indication for ambient sensor

Minimum setpoint allowed to the end user

Maximum setpoint allowed to the end user

Delay when the instrument is powered on

Act point of high ambient temperature alert

Refrigeration time (interval between defrosts)

Compressor delay after on (on - off)

Compressor delay after off (off - on)

Compressor status with detached ambient sensor (S1)

Defrost when the instrument is powered on

Evaporator temperature (S2) for end defrost

Maximum duration of defrost (for security)

Fan turned on during defrost

Defrost type

Min

Max

Unit

Standar

CELSIUS

FAHRENHEIT

-

0.1

-20.0

-50.0

-50.0

0

-50.0

0 - off

0 - no

-50.0

0=disable

0 - no

0 - electric

1

0

0

-

1

-36

-58

-58

0

-58

1

0

0

-58

0 - off

0 - no

0=disable

0 - no

0 - electric

-

20.0

20.0

75.0

75.0

30

75.0

999

999

999

1 - on

1 - yes

75.0

90

1 - yes

1 - hot gas

-

36

36

167

167

30

167

999

999

999

167

90

1 - on

1 - yes

1 - yes

1 - hot gas

-

º C

º C

º C

º C

min.

º C

min.

sec.

sec.

-

-

º C

min.

-

-

-

1.5

0

-50.0

75.0

0

75.0

240

0

0

1 - on

0 -no

40.0

45

0

0

-

°F

°F

°F

°F

min.

°F

min.

°F

sec.

sec.

-

-

min.

-

-

-

3

0

-58

167

0

167

240

0

0

0 -no

104

45

0

0

1 - on

Min

Max

Unit

Standar

Locked temperature indication (S1) during defrost

Draining time (dripping of defrost water)

Evaporator temperature (S2) for fan return after draining

Maximum time of fan return after draining (fan-delay)

Fan on with compressor off (refrigeration)

Fan stopped for high temperature in the evaporator

Intensity of the digital filter applied to the sensor 1 (0-off)

0 - no

0

-50

0

0 - no

-50

0

1 - yes

30

75.0

30

1 - yes

75.0

9

-

min.

º C

min.

-

º C

-

0 - no

0

-58

0

0 - no

-58

0

1 - yes

30

167

30

1 - yes

167

9

-

min.

min.

-

-

°F

°F

0 - no

10

0

1

1 - yes

75.0

0

0 - no

10

0

1

1 - yes

167

0

4.3 - Parameters description

F01 - Access code (123)

F02 - Control differential (hysteresis)

F03 - Offset indication for ambient sensor

F04 - Minimum setpoint allowed to the end user

F05 - Maximum setpoint allowed to the end user

F10 - Compressor delay after off (off-on)

F11 - Compressor status with detached ambient sensor (S1)

F12 - Defrost when the instrument is powered on

F13 - Evaporator temperature (S2) for end defrost

To change the parameters it is necessary to use the access code.It is not necessary to use the access
code to visualize the adjusted parameters.

It is the difference of temperature (hysteresis) between to turn OFF and turn ON the refrigeration output.
Example: To control the temperature in 4.0°C with differential of 1.0°C. Soon, the refrigeration will be
turned off in 4.0°C and turned on again in 5.0°C (4.0 + 1.0)

It allows to compensate eventual shunting lines in the reading of ambient temperature (S1) proceeding
from the exchange of the sensor or cable length alteration.

Electronic limits whose purpose is to prevent that too high or too low setpoint temperatures are
regulated.

It is the minimum time that compressor will keep off, it means, space of time between the last stop and
the next drive. It serves to alliviate the discharge pressure and to increase the time of useful life of the
compressor.

If the ambient sensor (S1) will be damaged or outside the specified range, the compressor assumes the
configured status in this function.
Example: For counters of fruits, it is better to keep the compressor off. In counters of meat it is better to
keep the compressor on.

It makes possible the accomplishment of a defrost at the moment that controller is energized, for
example, in the return of electrical energy (in case of energy lack)

If the temperature in the evaporator (sensor S2) reaches the adjusted value, the end of defrost will be for
temperature. With this, the defrost process is optimized.

F06 - Delay when the instrument is powered on

F07 - Act point of high ambient temperature alert

F08 - Refrigeration time (interval between defrosts)

F09 - Compressor delay after on (on-off)

When the instrument is powered on, its control is kept disabled during a time, delaying the start of
process. During this time, it works only as temperature indicator. It serves to prevent demand of electric
energy peaks, in case of lack or return of the same and when exists a lot of equipment connected on the
same net. For this, just adjust different times for each equipment. This delay may be of compressor or
defrost (when exist defrost on turn on).

If the ambient temperature (sensor S1) reaches this point during refrigeration, this will be signaled
visually through the indication blinking on display.

It is the time which compressor will turn on and turn off only for ambient temperature and starts to be
counted when the fan is turned on , after fan-delay stage (fan return after draining).

It is the minimum time that compressor will keep on, it means, space of time between the last drive and
the next stop. It serves to prevent high voltage events in the electric network.

COMP

www.fullgauge.com

FANS

DEFR

TC-900Ri

power