12.SUMMARY SCREEN
12.2. Suction summary screen:
This screen displays the basic status of the suctions.
To configure the Suction lines, go to
Main menu Function settings Suction
. For more information, see Main Menu function
1.1.2
cc
cc
ID of the suction on display:
Suc1
:
Suction 1;
Suc2
:
Suction 2;
Suc3
:
Suction 3.
1
9
11
2
3
5
4
6
10
12
7
8
1
2
3
4
5
6
7
8
9
10
11
12
Control status indication:
Wait
: Awaiting control to start;
On
:
On;
Off
:
Off;
Lock
:
Blocked;
Al
:
In alarm or automatic reset;
Al
(Flashing): Awaiting manual reset;
Cfg
: Missing configuration parameter.
Setpoint:
30
.0 psi
Press:
35
.0 psi
Temp:
-5
.0°C
Super
heat
ing: 5.0°C
Req: 100% Out: 100%
Suc1
Suc1 On
Eco
Pd
M
Eco
: Economy setpoint active.
Pd
: Pump Down in progress.
M
: At least one compressor being serviced.
: Active alarm indication.
Out
: Percentage of power related to the outputs
active in
RCK-602
plus.
Req
: Percentage of power required by the
system related to the operating range.
Superheating
: Calculation of the
superheating based on measured pressure and
temperature and the type of refrigerant used. If the
controller identifies that the suction is working in
the refrigerant's transcritical region, the message
PC is displayed.
Te m p
: It is the value of the suction 1
temperature sensor.
Press
: It is the pressure value read by the
suction transducer.
Setpoint
: Displays the current value of
the setpoint, either the economy pressure setpoint
or main pressure setpoint. (Whichever is active).