Full Gauge Controls PCT-410Ri plus Скачать руководство пользователя страница 3

It is important to note that digital output capacities can be configured in any order, for instance: 20%, 40%, 
10%, and30%for outputs OUT1 to OUT4.

5.5  Control  Mode  4  -  Analog  and  digital  outputs  with  linear 

activation

In this mode the drive of the digital outputs will always be after the analog output reaches its maximum 
value (100%). The activation sequence of digital loads will be linear as in the item 5.2. Because this 
operation mode uses the digital and analog outputs, the hysteresis that the controller consider will be the 
sum of the functions: ”hysteresis of digital outputs” and “hysteresis of analogic output”.
When the operation mode is in depressurize, the controller works to decrease the read pressure until 
reaches setpoint value. If it is working in the pressurize mode, the controller works to increase the read 
pressure until reaches setpoint value.
If the Start / Stop function is enabled. The drive will take place when the pressure reaches the value for 
each step even if the analog output does not reach 100%, the first digital output starts to act as control for 
enabling a frequency inverter. At depressurize mode, if the read pressure is less than or equal to the 
setpoint, the OUT 1 output will be with the relay off, otherwise, if the read pressure is greater than the 
setpoint, the OUT 1 output will be with the relay on.

Setpoint: 30 psi
Hysteresis of digital outputs: 20 psi
Number of stages: 4
Hysteresis of analog output: 25 psi

5.2 Control Mode 1 - Only digital outputs with linear activation

The digital outputs will be used in this control mode, and thus the controller will assume only the hysteresis 
value configured in the function: "digital output hysteresis." The controller will add digital outputs as the 
pressure deviates from the setpoint. The activation point for each output is calculated in accordance with 
the hysteresis value and the number of stages configured.

Example:

Setpoint: 30 psi
Hysteresis of digital outputs: 8 psi
Number of stages: 4

In this example the step for each digital output is 2 psi (8 psi divided by 4). The first digital stage will be 
activated when the pressure reaches 32 psi (setpoint plus step), the second at 34 psi (setpoint plus 2 times 
the step), the third at 36 psi (setpoint plus 3 times the step) and the fourth at 38 psi (setpoint plus 4 times 
the step). Please note that at 38 psi (setpoint plus digital hysteresis) all digital outputs will be on. 

Example 2: Using the same values as in example 1.

Pressurize

Start/Stop Off

Example 4: Using the same values as in example 1.

Pressurize

Start/Stop On

Example 3: Using the same values as in example 1.

Depressurize

Start/Stop On

25%

0%

50%

75 %

100%

Setpoint

-5 psi

-10 psi

-15 psi

Measured
pressure

Analog

output

+5 psi

Setpoint

-15 psi

-10 psi

-5 psi

-20 psi

-20 psi

-25 psi

25%

0%

50%

75 %

100%

Setpoint

+5 psi

+10 psi

+15 psi

+20 psi

+25 psi

Measured
pressure

Analog

output

OUT1

(Start Stop)

-5 psi

+20 psi

+15 psi

+10 psi

+5 psi

+5 psi

Setpoint

Digital

ouputs

25%

0%

50%

75 %

100%

Setpoint

+5 psi

+10 psi

+15 psi

Measured
pressure

Analog

output

OUT1

(Start Stop)

+5 psi

Setpoint

-15 psi

-10 psi

-5 psi

+20 psi

-20 psi

-25 psi

Digital

ouputs

5.3 Control Mode 2 - Only digital outputs with activation by time 

(rotation)

Similarly to the previous mode, only the digital outputs will be used, and thus the controller will assume 
only the hysteresis value configured in the function: "digital output hysteresis." In this mode the digital 
outputs are controlled in accordance with the number of working hours, so that for switching on a new 
stage the controller checks which one has the least working time, and for switching off one stage it checks 
which one has the most working hours. This is aimed at ensuring balance in the operating time of the 
digital outputs.

Example:

Setpoint: 30 psi
Hysteresis of digital outputs: 8 psi
Number of stages: 4

5.4  Control  Mode  3  -  Only  digital  outputs  with  activation  by 

capacities

The digital outputs will be used in this control mode, and thus the controller will assume only the hysteresis 
value configured in the function: "digital output hysteresis." 
The activation point for each output is calculated in accordance with the output capacity and the number of 
stages  configured.  The  activation  will  occur  in  accordance  with  the  demand  of  the  system,  and  the 
controller will always activate the set with the smallest number of outputs meeting the current demand.
The calculation of the demand is made considering the following formula:

+ 2 psi

+ 4 psi

+ 6 psi

+ 8 psi

Setpoint

OUT1

OUT1+OUT2

OUT1+OUT2+OUT3

OUT1+OUT2+OUT3+OUT4

Hysteresis

Time

Setpoint

OUT1

OUT1+OUT2

OUT1+OUT2+OUT3

OUT1+OUT2+OUT3+OUT4

OUT2+OUT3+OUT4

OFF

Hysteresis

Time

OUT3+OUT4

OUT4

+ 2 psi

+ 4 psi

+ 6 psi

+ 8 psi

                         Measured pressure - Setpoint

                 Hysteresis total

x 100

  Demand (%) =

Example:

Capacity of digital output 1 (OUT1):10%
Capacity of digital output 2 (OUT2):20%
Capacity of digital output 3 (OUT3):30%
Capacity of digital output 4 (OUT4):40%
Setpoint: 10 psi
Hysteresis of digital outputs: 10 psi

The performance levels of each digital output will be:

Measured pressure = 11 (demand of 10%) 

OUT1

Measured pressure = 12 (demand of 20%) 

 OUT2

Measured pressure = 13 (demand of 30%) 

 OUT3

Measured pressure = 14 (demand of 40%) 

 OUT4

Measured pressure = 15 (demand of 50%) 

 OUT2+OUT3

Measured pressure = 16 (demand of 60%) 

 OUT2+OUT4

Measured pressure = 17 (demand of 70%) 

 OUT3+OUT4

Measured pressure = 18 (demand of 80%) 

 OUT1+OUT3+OUT4

Measured pressure = 19 (demand of 90%) 

 OUT2+OUT3+OUT4

Measured pressure = 20 (demand of 100%) 

 OUT1+OUT2+OUT3+OUT4

OUT4

OUT3

OUT2

OUT1

Time

Time

Digital

ouputs

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

Demand

Setpoint

                 Digital hysteresis

                   Number of stages

  Step =

Pressure to activate the output "N"

Activation = Se (N x Step)

Pressure to deactivate the output "N"

Activation = Se ((N-1) x Step)

Outputs activation step

    Step  = Digital hysteresis

  Number of stages

Содержание PCT-410Ri plus

Страница 1: ...2 Capacityofthedigitalstage3 Capacityofthedigitalstage4 Capacityoftheanalogstage Digital outputs state when a sensor error is detected Analog output value when a sensor error is detected Minimum time...

Страница 2: ...uish between one of the alarm situations or a transitory condition of the system Numberofstages Functionthatindicateswhichstageswillbeactivated Capacityofthedigitalstage1 This function sets the capaci...

Страница 3: ...Setpoint 5 psi 10 psi 15 psi 20 psi 25 psi Measured pressure Analog output OUT1 Start Stop 5 psi 20 psi 15 psi 10 psi 5 psi 5 psi Setpoint Digital ouputs 25 0 50 75 100 Setpoint 5 psi 10 psi 15 psi Me...

Страница 4: ...alog Hyteresis Digital Hyteresis Digital Hyteresis 5 psi 10 psi 15 psi 20 psi 25 psi 30 psi 35 psi 40 psi 45 psi 45 psi 40 psi 25 psi 0 psi 5 psi 10 psi 15 psi 20 psi 30 psi 35 psi Measured pressure M...

Страница 5: ...T2 100 OUT1 60 10 70 20 80 30 90 40 100 50 Time Time Time Digital outputs Example 4 Pressurize Start Stop On Hysteresis of digital outputs 20 psi Number of stages 3 Hysteresis of analog output 25 psi...

Страница 6: ...r will operate between with the access code 312 on the function and confirm with the key The indication will appear press or tochoosebetween dischargepressureswi Confirm the selection with the key and...

Страница 7: ...nection of supresors to contactors Suppresor A1 A2 A1 and A2 are the contactor coil terminals Schematic for the connection of supresors to direct activation loads Load Suppresor For direct activation...

Отзывы: