DIGITAL CONTROLLER FOR COOLING

WITH NATURAL DEFROST

AND FOR HEATING

Ver.01

MT-512G

MT512GV01-01T

-12371

The

is a temperature controller and indicator.

Controls cooling and defrosts through compressor shutdowns.

MT-512G

· Counters
· Cooled chambers
· Greenhouses

90 to 264Vac (50/60Hz)

-50 to 99°C (-58 to 99°F)

0,1°C (between -10 and 10 °C) and 1°C in the rest of the range

16(8)A/ 250Vac 1HP

0 to 50 °C

10 to 90% RH (without condensation)

- Power supply:
- Control temperature:
- Resolution:
- Maximum current:
- Operating temperature:
- Operating humidity:

Access code: 23 (twenty three)

Control differential (hysteresis)

Minimum setpoint allowed for the end user

Maximum setpoint allowed for the end user

Additional time at the end of the first cycle

Cooling time

Defrosting time

(*)

(heating)

(**)

Operation mode

Initial state up on energizing the instrument

Temperature indication locked during defrost

Delay on the activation of the instrument

Delay to turn the cooling output on

Situation of the compressor with the damaged sensor

Indication offset

Intensity of the digital filter

Fun

CELSIUS

FAHRENHEIT

MT-512G

allows changing from refrigeration to defrost or vice-versa, regardless of what is

programmed:
1. Press the key for 4 seconds until

is displayed;

2. If the controller is in the refrigeration cycle, when the key is released the display will show

and

the defrost cycle will start;
3. If the controller is in the defrost cycle, when the key is released the display will show

and the

refrigeration cycle will start.

– Sensor disconnected or temperature out-of-range;
– Indicates the defrost cycle;

– Indicates that the defrost cycle is turned on;
– Indicates that the defrost cycle is turned off (starts the refrigeration cycle);

– Indicates the refrigeration cycle;

– Indicates that the controller is operating in heating mode;
– Indicates the initial delay;
– Invalid configuration parameters;
In this situation the outputs are automatically turned off.
Check which parameters have invalid data and correct them to return to normal operation.

LED flashing – The controller is in cooling mode (heating) and with the output on;
LED off

– The controller is in cooling mode (heating) and with the output on off;

LED on

– The controller is in defrost mode.

Configuration parameters protected by access code (except setpoint).

After entering the access code, be careful not to leave the key idle (without being pressed)

between parameter changes for more than 15 seconds.
If this happens, the message

will be displayed and the access to the adjust mode

is automatically blocked, requiring entering the code again to make any changes.

After entering the access code:

Note:

1. Press the frontal key of the panel for 8 seconds until

appears;

2. Releasing the button it will appears

;

3. Use the key to insert the code 23 (twenty-three). This operation must be done in 4 seconds, otherwise
the indication of ambient temperature returns automatically;
4. Wait 4 seconds to the instrument record the access code. At this time

appears in the display

and then the temperature.

If the access code is correct, the controller allows the user to view and change the parameters.
5. Press the key as many times as necessary until you reach the desired parameter.
6. Wait 2 seconds and then appears the adjusted value.
7. Use the key to modify the value;
8.Wait 4 seconds until the new value is recorded and the instrument returns to show the room
temperature;
9. To change another parameter, repeat steps 5, 6, 7 and 8.

- Press the frontal key for 12 seconds until appears

;

- Releasing th key, the set control temperature will appear.;
- Use the key to change the value. This operation must be done in 4 seconds, otherwise the indication of
ambient temperature returns automatically.
- Wait 4 seconds to record and return to the normal operation.

* Frozen display indication - If

is active, the indication is only released in the following refrigeration cycle and when the

temperature reaches the "locked" value again, or after 15 minutes in refrigeration (as a safety measure).

This filter aims at simulating an increase of environment sensor mass, thus increasing its response time (thermal inertia). The

larger the value adjusted in this function, the longest the response time of the sensor.
A typical application requiring this filter is the freezer for ice cream or frozen goods, because when the door is opened a hot air mass
reaches the sensor directly, causing a quick rise in the indication of the measured temperature, thus causing the compressor to be
activated unnecessarily many times.

**

Press the key and then release it (short touch). Soon the display will show the process that is
running and the elapsed time.
Example:

The controller is in refrigeration mode for 192 minutes.

The controller is in defrost mode for 25 minutes.

The controller is executing the delay time to power the instrument on for 2 minutes.

The controller is in heating mode.

- Press the frontal key of the panel for 8 seconds until

appears;

- Releasing the button it will appears

;

- Use the keys to enter code 31 (thirty-one). This option must be executed within four seconds, otherwise
the display will automatically return to showing the room temperature;
- Wait 4 seconds to save the access code;
- Then the display will show the measurement unit in use (

or

);

- Press the keys to change the value between

and

and vice-versa;

-After 4 seconds without pressing any other keys the controller will save the selected unit;
- If the measurement unit is changed,

will be displayed and the parameters will assume their

default values.

1

2

3

4

5

6

7

8

9

10 11 12 13

Load - 16(8)A / 250Vac 1HP

Power supply

90~264Vac

Above specified current use a contactor

Sensor

Load supply

1. DESCRIPTION

2. APPLICATIONS

3. TECHNICAL SPECIFICATION

4. CONFIGURATIONS

4.1 - Control temperature adjust (SETPOINT)

4.2 - Parameters alteration

4.3 - Parameters table

5. FUNCTIONS WITH FACILITATED ACCESS

5.1- Show current status

5.2 - Manual defrost

6. SIGNALLING

7. UNIT SELECTION (°C / °F)

8. WIRING DIAGRAM

Note:

The length of the sensor cable may be increased by the user up to 200 meters, using a PP 2 x 24

AWG cable. For immersion in water, use thermometric we

Description

Min

Max

Unit Standard

Min

Max

Unit Standard

-

3

-1

5

0

30

25

0-refrig.

1-yes

0

18

0-off

0

5

0-refrig.

-

20

99

99

99

99

99

1-defrost

1-yes

99

99

1-on

5

9

1-heat.

-

°C

°C

°C

min.

x10min.

min.

-

-

min.

x10sec.

-

°C

-

-

-

1

-58

-58

0

1

1

0-refrig.

0-no

0

0

0-off

-9

0

0-refrig.

-

40

99

99

99

99

99

1-

1-

99

99

1-

9

9

1-

defrost

yes

on

heat.

-

°F

°F

°F

min.

x10min.

min.

-

-

min.

x10sec.

-

°F

-

-

-

0.1

-50

-50

0

1

1

0-refrig.

0-no

0

0

0-off

-5

0

0-refrig.

-

37

30

41

0

30

25

0-refrig.

1-yes

0

18

0-off

0

5

0-heat.