IMPORTANT
According to the chapters from the IEC60364 standard:
1.
Install protectors against over voltage on power supply.
2.
Sensor cables and computer signals can be together, however not at the same place where power
supply and load wires pass for.
3.
Install suppresors of transients (RC filters) in parallel to loads to increase the usefull life of the relays.
4.
The withdrawal or substitution of the adhesive panel frontal as well as alterations in the electronic
circuit on the part of the user implies in the cancellation of guarantee.
For more information contact our application eng. department through e-mail
or dial +55 51 3475.3308.
A1 and A2 are the
contactor coil.
Suppresor
A1
A2
Wiring diagram of suppresor in contactors
Carga
Suppresor
Wiring diagram of suppresor linking in loads
direct drive
For direct drive,
consider the maximum
load current specified.
PROTECTIVE VINYL:
This adhesive vinyl (included inside the packing) protects the instruments against
water drippings, as in commercial refrigerators, for example.
Do the application after finishing the electrical connections.
Remove the protective paper
and apply the vinyl on the entire
superior part of the device,
folding the flaps as indicated by
the arrows.