Full Gauge Controls Microsol Ri Скачать руководство пользователя страница 1

DIFFERENTIAL THERMOSTAT

FOR SOLAR HEATING

Ver.06

MICROSOL Ri

1. DESCRIPTION

The 

MICROSOL Ri

 is a 

that commands a water circulation 

pump through the temperature differential that exists between the solar collector panels and the thermal 
reservoir or pool in solar heating systems. 

MICROSOL Ri

 has functions that improve the absorption of solar energy, prevent the freezing in 

the pipes during winter and control the overheating.

2. TECHNICAL SPECIFICATIONS

- Power Supply: 

 MICROSOL Ri      115/230 Vac ±10% (50/60 Hz) 

                            MICROSOL RiL     12/24 Vac/dc

- Temperature control:  

-50 to 105°C

- Resolution: 

0.1°C

- Load current: 

16(8)A / 250 Vac 1HP

- Dimensions:

 71 x 28 x 71mm

- Operation temperature: 

0 to 50 ºC

- Operation humidity: 

10 to 90% RH (without condensation)

   This instrument can measure and control up to 200ºC temperatures, since used with silicone cable 
sensor (ex.: SB59).

differential thermostat for solar heating 

3. CONFIGURATIONS

3.1 - To access the function menu

a) 

Press the key          for 2 seconds until            appears, release it after that.

b) 

When         appears, press       (short touch) and insert the access code (123) through the keys        

         and          . To confirm press         .

c) 

Through the keys          and          access the other functions and do the same to adjust them.

 

d) 

To reset the menu and return normal operation, press         (long touch) until            appears.

SET

SET

SET

SET

Fun

Descripton

Access code 123 (one hundred and twenty-three)

Preferential indication

Differential (t1-t2) to turn on the pump 

Differential (t1-t2) to turn off the pump 

Temperature of anti-freeze (S1) in the collectors to turn on the pump

Overheating temperature (S1) to turn off the pump 

Overheating temperature (S2) to turn off the pump

Overheating temperature (S3) to turn off the pump

Cooling (S3)

Overheating temperature hysteresis of S2 sensor

Overheating temperature hysteresis of S3 sensor

3.2 - Parameters table

Standard

0

1.0

1.0

2.9

0.0

0.0

0.0

0.1

0.1

0

8.0

4.0

8.0

90.0

90.0

1.0

1.0

-

-

°C

°C

°C

°C

°C

°C

-

°C

°C

Min

Max Unit

999

40.0

40.0

10.0

105

105

105

5.0

5.0

3.3 - Parameters description

Access code (123)

This  code  is  required  to  change  configuration  parameters,  while  it  is  not  required  to  display  the 
parameters. 

Preferential indication (what will be displayed)

Sensors differential (S1 - S2)
Collector temperature (S1)
The thermal reservoir or pool (S2)
Surface temperature.

The other temperatures can be quickly checked by holding down         or         keys for a few seconds and 
then returning automaticly to the indication that was select in            as preferential. 

S1 Display offset

S2 Display offset

S3 Display offset ( ** )

    This parameter allows adjustments up to 200ºC but to work on these conditions it has to be used with 
silicone cable sensor (ex.: SB59).

-5.0

-5.0

-5.0

0.0

0.0

0.0

°C

°C

°C

5.0

5.0

5.0

Differential of temperature (T1-T2) to turn on the pump

While  the  solar  collectors  receive  energy,  the  sensor  1  temperature  will  increase.  When  this 
temperature is higher then the sensor S2 temperature, the pump is turned on and circles down the 
heated water, storing in the thermal reservoir, for example.

Differential of temperature (T1-T2) to turn off the pump

With the pump on, the hot water circles down and the cold water circle up. Then the diference between 
S1 and S2 temperature tends to decrease.
When the temperature decreases to a determined value, the pump is turned off, stopping the water 
circulation.

Temperature of anti-freeze (S1) in the collectors to turn off the pump

When  the  collectors  temperature  (sensor  S1)  is  low  (winter  nights,  ex.),  the  pump  is  turned  on, 
periodically, to avoid water from freezing in the hoses. The hysteresis is fixed in 5°C. 
To disable this function set the adjustment to the minimum until appears            .

Overheating temperature (S1) to turn the pump off 

When temperature in collectors (sensor S1) will be above of a determinable value, the pump is turned off 
to hinder that the overheated water circulates for the pipes and it damages them (case PVC pipes are 
used). The fixed hysteresis is in 2°C.

Overheating temperature (S2) to turn the pump off

When the temperature in sensor S2 reaches a determinable value, the pump is turned off to prevent   
thermal discomfort . This function is used in heating systems for pools that do not use the third sensor.  
The hysteresis can be adjusted from 0,1 to  5,0 °C. (See function            ).

Overheating temperature (S3) to turn the pump off 

When the temperature in sensor S3 reaches a determinable value, the pump is turned off to prevent the 
thermal discomfort. This function is used in heating systems for pools that use the third sensor to 
measure temperature in surface. The hysteresis can be adjusted from   0,1 to 5,0 °C. (See function                     
          ).

Note: 

This function also serves to disable sensor S3 (when it is not used), being enough to dislocate the 

adjustment for maximum until appearing the indication           .

Cooling

This function only appears if S3 sensor will be qualified. It has the purpose to cool the pool during the 
night  always  that  overheating  temperature  of  this  sensor  will  be  exceeded  and  the  difference  of 
temperature between S1 and S2 to reach -4°C. Then the pump is turned on using the collector as 
radiator to coll the water of pool.
When the difference (S1-S2) lower or the temperature in the S3 sensor to reset overheating, the pump 
is off. 

Overheating temperature hysteresis of S2 and S3 sensors 

Case the pump will be off for overheating in sensors S2 or S3, through these functions a time 

interval can be defined where the pump will keep off.

Indication locking of sensors (S1, S2, S3)

It allows to compensate eventual shunting lines in the reading of sensors S1 (collectors), S2
(reservoir) and S3 (surface), proceeding from the exchange of the sensor or  alteration of cable

lenght. (It only can be visualized if third sensor will be qualified).

PS: 

To disable the third sensor see explanation in the function           .

IMPORTANT: 

The adjusted value in the function             must be bigger than the value adjusted in

the function           . Thus being,

 MICROSOL Ri

 does not allow that invalid adjustments are made 

similar to guarantee its perfect functioning.

Ex.: Current configuration

You want to change for

{

10.0°C

5.0°C

{

4.0°C

2.0°C

First adjust            for 2.0°C and after soon adjust            for 4.0°C.
 

4. SIGNALLING

PUMP

 signal the pump status.

T1 

and 

T2 i

ndicate which temperature

is being displayed.

While programming, parameters T1 and T2 keep blinking.
If the sensors are disconected or out of the specified range, a message will appear on the display, 
indicating the sensor.

Sensor 1 irregular
Sensor 2 irregular
Sensor 3 irregular

If the instrument shows in the display the message         , it means that was detected some parameter 
value outside the acceptable range and it needs to be corrected.    

Sensor 1

Sensor 2

Sensor 3

Differential S1-S2

T1

T2

Indication

6. 

WIRING DIAGRAM

Note: 

The sensors cables length can be increased by the user until 200 meters using the PP 2 x 24 AWG 

cable. For immersion in water use thermometric well.

1

2

4

5

6

7

8

9

10

11

12

3

1

2

4

5

6

7

8

9

10

11

12

3

S

en

so

r 1

B

la

ck c

ab

le

 (

co

lle

ct

or

s)

S

en

so

r 2

G

ra

y c

ab

le

(r

es

er

vo

ir/

po

ol

)

*S

en

so

r 3

(s

ur

fa

ce

)

7 - 8
7 - 9

MICROSOL Ri

115V
230V  

Load

COMMON 

NO

NC

PUMP

MICROSOL RiL

12V
24V

72 mm

Tear dimensions

to position the instrument

in the panel

29 mm

Power

supply

Load

supply

Above the current specified

 use contactor

0

115V

(12V   )

230V

(24V   )

*Sensor 3 sold separately

5. PARAMETER WITH EASY ACCESS

The            setting, if enabled by the user, can be easily accessed by a quick touch on          key. 
To enable the easy access mode press          for 15 seconds until appears             or            . 
The default mode from factory is “disabled”. When used in swimming pools this parameter allows setting 
the water temperature to turn off the circulation pump, avoiding thermal discomfort.

SET

SET

MCSOLRi6-05T

-1

1020

E251415