6.2 TABLE OF PARAMETERS

Min

Max

Unit

Min

Max

Unit

CELSIUS

FAHRENHEIT

 Fun

[CoDE]
[,F01]
[,F02]
[,F03]
[,F04]
[,F05]
[,F06]
[,F07]
[,F08]
[,F09]
[,F10]
[,F11]
[,F12]
[,F13]
[,F14]
[,F15]

6.3 DESCRIPTION OF PARAMETERS

[Code]

– Access code (123):

Required when you want to change the advanced configuration parameters. This code is not 
required to only view the set parameters.

[,F01]

– Preferred indication:

This function allows you to choose the temperature that is normally shown on the display. You 
can choose between:

[,DIF]

– T1-T2 differential. Shows the temperature difference in degrees between the 

solar collector (T1) and pool (T2).

[,,T1]

 – Temperature of the collectors (T1).

[,,T2]

 – Temperature of the pool/thermal reservoir (T2).

[,F02]

– Differential (T1-T2) to turn on the pump:

Allows you to configure the temperature difference between the solar collector and the pool at 
which the circulation pump is switched on. As the collectors receive energy, the temperature of 
sensor T1 increases. When this temperature is a set value above the temperature of sensor T2, 
the pump is switched on and circulates the heated water, storing it in the pool.

[,F03]

– Differential (T1-T2) to switch off the pump:

Allows you to configure the temperature difference between the solar collector and the pool at 
which  the  circulation  pump  is  switched  off.  With  the  pump  on,  the  temperature  difference 
between the collector and the pool (T1-T2) tends to decrease. When this value falls to a set 
value, the pump is switched off, stopping the circulation of water.

[,F04]

– Antifreeze temperature (T1) to switch the pump on:

When the temperature of the collectors (T1) is very low (e.g. winter nights), the pump is switched 
on according to the temperature set in this parameter, in order to prevent water from freezing in 

the solar collector

 and damaging them. The hysteresis of this control is fixed and set at 2.0 ºC. 

To disable this function, move the setting to the minimum until 

[,,No]

 appears.

[,F05]

– Minimum antifreeze time:

This minimum time with the pump switched on serves as a safety measure to ensure that the 
water  passes  by  all  the  collectors.  Even  if  the  temperature  of  the  T1  sensor  exceeds  the 
antifreeze temperature (

[,F04]

parameter), the controller respects the time programmed in 

this parameter. This function is often used in large projects due to the number of installed plates. 
To disable this function, move the setting to the minimum until 

[,,No]

 appears.

[,F06]

– Overheating temperature (T1) to switch off the pump:

When the temperature in the collectors (T1) is above the value set in this parameter, the pump is 
switched off to prevent the overheated water circulating through pipes and damaging them, if 
PVC pipes are used, for example. The hysteresis of this control is fixed and set at 2.0 ºC.

[,F07]

– Cooling (T2):

This is intended to cool the pool during the night whenever the heating temperature (

[TEMP]

 

parameter)  is  exceeded  and  the  difference  between  the  collector  (T1)  and  reservoir  (T2) 
reaches -4.0 °C (fixed). The pump is then switched on, using the collector as a radiator to cool 
the pool water. When the differential (T1-T2) is less than -2.0 °C (fixed) or the temperature (T2) is 
lower than the heating temperature of the reservoir (

[TEMP]

 parameter), the pump is switched 

off.

[,F08]

– Vacuum tube function:

When enabled, this function switches the pump on for 20 seconds (fixed) for every 30 minutes 
(fixed) the pump is switched off, while the collector temperature (T1) is above 20.0 °C (fixed) and 
the temperature differential (T1 -T2) is positive. 
Some  models  of  vacuum  tube  collectors  do  not  allow  direct  measurement  of  the  collector 
temperature since they are not set up for immersion sensors. For correct measurement of the 
water temperature at the collector output, there must be a minimum flow of water. For this 
reason, the solar circuit must switch on the pump briefly, at regular intervals, so that the water 
heated by the collector reaches the T1 sensor.

Note:

 The controller prioritizes the protection settings (overheating), ignoring the vacuum tube 

function in the event both of these functions are called at the same time.

[,F09]

– Hysteresis of the pool heating temperature (T2):

If the pump is switched off due to reservoir heating (

[TEMP]

), this function allows you to set a 

temperature range within which the pump will remain switched off.

For example: If set to

 [temp]

 = 

[,30.0]

 and 

[,F09]

 = 

[,,1.0]

, the pool heating will be 

switched off when the temperature of sensor T2 reaches 30.0 °C, and will only switch on in order 
to heat when the temperature falls below 29.0 °C (30.0 - 1.0 = 29.0).

Access code
Preferred indication
Differential (T1-T2) to turn on the pump
Differential (T1-T2) to switch off the pump
Antifreeze temperature (T1) to switch the pump on
Minimum antifreeze time
Overheating temperature (T1) to switch off the pump
Cooling (T2)
Vacuum tube function
Hysteresis of the pool heating temperature (T2)
Filtering manual override time
Filtering events schedule operating mode
T1 sensor indication offset
T2 sensor indication offset
Function lock time
Intensity of the display backlight

0

DIF

1.0
1.0

no (-19)

no (0)

0.0
Off
Off
0.1

0

1b1
-5.0
-5.0

4
1

999

T2

40.0
40.0
10.0

600
200

On
On

20.0

24

1t7
5.0
5.0

30
10

-
-

ºC
ºC
ºC

s

ºC

-
-

ºC

H

-

ºC
ºC

s

-

0

T2

8.0
4.0
8.0

60

90.0

Off
Off
1.0

8

1t7
0.0
0.0

4
8

0

DIF

1
1

no (-2)

no(0)

32

Off
Off

1
0

1b1

-9
-9

4
1

999

T2
72
72
50

600
392

On
On

36
24

1t7

9
9

30
10

-
-

ºF
ºF
ºF

s

ºF

-
-

ºF

H

-

ºF
ºF

s

-

0

T2
14

7

46
60

194

Off
Off

1
8

1t7

0
0
4
8

[,F10]

– Filtering manual override time:

Used when you wish to activate the filtering output outside the hours set in the events schedule. 
When using manual override, the mode returns to AUT (automatic) after the time programmed in 
this parameter. To disable this function, move the setting to the minimum until 

[,,No]

 appears.

[,F11]

– Filtering events schedule operating mode:

Sets the operating mode of the events schedule:

[,1b1]

– Weekly Programming – in this mode, the instrument can set up to 4 different 

events for each day of the week.

[,2t6]

– Weekday Programming – in this mode, the instrument keeps events the 

same on weekdays (Monday to Friday) and allows you to program different events for 
Saturday and Sunday.

[,1t7]

– Daily Programming – in this mode, the instrument keeps the events the same 

for every day of the week.

[,F12]

– T1 sensor indication offset:

[,F13]

– T2 sensor indication offset:

Used to compensate for possible deviations in the T1 sensor (collector) or T2 sensor (pool) 
reading as a result of sensor replacement or changing the cable length.

[,F14]

– Function lock time:

Sets the time that the increment button must be pressed in order to lock/unlock parameter 
changes. For more information see item 5.8 – Function Lock. To disable this function, move the 
setting to the minimum until 

[,,No] 

appears.

[,F15]

– Intensity of the display backlight:

Sets the intensity of the display backlight in order to set contrast.

7. SIGNALS

- Motive: 

Sensor 1 disconnected or out of the specified range.  

- Motive: 

Sensor 2 disconnected or out of the specified range.  

- Motive: 

Dis-programmed clock due to prolonged energy absence.

- Corrective measures: 

Check the connections and sensor operation.

- Corrective measures: 

Check the connections and sensor operation.

- Corrective measures:

 Adjust time and day, see article 5.5.

am

- Motive: 

Filtering manual override

 with setting of parameter

[,F10]

=

[,,no]

.

- Corrective measures

: Adjust parameter value F10 - 

Filtering manual 

override time

Obs.: 

In the occurrence of any error information the controller signals the user, flashing the 

display's backlight shortly, in order to grab attention.

6.4 UNIT SELECTION

To define the temperature unit with which the instrument is going to operate you should 
access the 

[Code]

 function (see article 6.1 to find out how to access this function), insert 

the 231 code and press the key. The user may select the unit by pressing the keys      or    , 
where the messages 

[,=C,]

or

[,=F,]

are alternated. Press the 

SET

 key to confirm 

the  desired  unit.  Next  the  message

[----]

will  be  displayed  and  the

{

or 

}

icons 

corresponding to the unit will be turned on.

Obs.:

 While changing the unit, the controller carries the factory values in its parameters, 

[,FAC]

, being necessary to perform their setting.

 

Standard

Standard

Description

- Corrective measures: 

Contact the technician responsible for 

installation.

- Corrective measures: 

Contact the technician responsible for 

installation.