Full Gauge Controls d-core Скачать руководство пользователя страница 6

9.2 Wiring Diagram

- Base module

Attach the base module with screws*;

To place the front module in the
panel, press until it clicks;

2

To remove it, simply press the side
locks;

3

Remove the controller
from the front of the
panel;

9.1 Attaching the base and front modules

- Front module

Cut out the panel with the measurements
indicated. See item 3;

1

- Front module

- Base module

*screws not included;

*

must be in the

inet.

Sensor S1

cab

**

must be attached to the evaporator

Sensor S2

using a metal clamp.

Interconnection cable

Sensor S1*

Sensor S2**

Digital input

(Door switch)

9. INSTALLATION

The main function of this accessory is to store the parameters of the controllers. You can load new parameters
from a controller and download to a production line at any time (from the same controller).
The controller has a USB connection to upload or download the parameters:

- USB:

it can be connected to the computer with the USB port, using the Sitrad Recipe Editor the parameters

can be copied, edited and saved in

The USB port can also have the function to

.

EasyProg

ver. 02

supply power to

and the controller (when used in USB and Serial TTL set).

EasyProg

ver. 02

*Sold separately

8. PROGRAMMING KEY - EasyProg ver.02 or higher

Base module

EasyProg*

Reason:

Exceeded maximum compressor on time without reaching control

temperature (setpoint).

Provisions:

Check compressor and refrigeration system;

Check door seal;
Check function

.

[a7]

Reason:

Cabinet temperature sensor disconnected or short-circuited.

Provisions:

Check the connection on the controller. If necessary, replace the sensor.

Reason:

Evaporator temperature sensor disconnected or short-circuited.

Provisions:

Check the connection on the controller. If necessary, replace the sensor.

Reason:

Low temperature on cabinet sensor (S1).

heck sensor S1 connection and functioning (room);

Provisions:

C

Check refrigeration system;
Check function

.

[a2]

Reason:

High mains voltage (S1).

Provisions:

Check sensor S1 connection and functioning (room);

Check refrigeration system and/or door seal;
Check function

.

[a3]

Reason:

Low mains voltage.

Provisions:

Bad power grid quality and voltage below the one configured in

.

[U1]

Reason:

High voltage alarm in the mains.

Provisions:

Bad power grid quality and voltage above the that configured in

.

[U2]

7. SIGNALS

Reason:

Invalid voltage reading.

Provisions:

Check the supply voltage of the instrument.

Provisions:

Reset the values of the functions.

Reason:

Open door alert.

Provisions:

Make sure the door is properly closed;

Check limit switch micro or magnetic sensor (reed switch) of the
closed-door detection (if applicable), plus the connection to the controller.

Reason:

Control functions turned off.

Provisions:

See item 6.4.

Reason:

. The dot in the

Alert of defrost concluded by time rather than by temperature

lower hight corner of the display will flash until the next defrost (if enabled in
the function

).

[A8]

Provisions:

Check that there are no burnt heating elements;

Check if hot gas is circulating;
Check that the fan is not inoperative or shorted;
Check that the maximum time for defrost duration is not too short (

).

[B6]

Provisions:

Contact Full Gauge Controls.

Reason:

External alarm (digital input)

Provisions:

Check the control accessory connected to the digital input;

Check the connection on the controller;
Check function

.

[P1]

4

Reason:

Function lock on.

Provisions:

See item 6.3.

Reason:

Easyprog connected by sending data to the controller.

Reason:

Communication failure between the front module and the base.

Measures:

Check the interconnection cable.

Содержание d-core

Страница 1: ...que that reduces thefinaltemperatureoftheelectricalresistanceandtheamountofheatemitted Using its digital input door opening can be monitored and economic setpoint defrost or Fast Freezing can be activ...

Страница 2: ...m temperature 2 0 C ex Minimum temperature 1 2 C ex Hundred Unit ex 135 Maximum temperature 2 0 C ex Door opening number Minimum voltage ex 112V Maximum voltage ex 125V release the key release the key...

Страница 3: ...or S1 and the temperature of the evaporator sensor S2 reaches the value configured in this function the controller startsconfirmationtimecounttostartthedefrost d7 If the controller is configured to pe...

Страница 4: ...shut down compressor and fan Defines the unit of time used in parameter P5 0 Seconds 1 Minutes 2 Hours With the door closed this parameter defines how long It ontributes to energy for light turn off c...

Страница 5: ...current setpoint to activate the alarm buzzer forLOWroomtemperature Example Setpoint Inthiscase thealarmwillonlybe if 3 0 A2 2 0 active cabinet temperatureisbelow 1 0 3 0 2 0 Low temperature alarm di...

Страница 6: ...Checktheconnectiononthecontroller Ifnecessary replacethesensor Reason Lowtemperatureoncabinetsensor S1 hecksensorS1connectionandfunctioning room Provisions C Checkrefrigerationsystem Checkfunction a2...

Страница 7: ...rge WARRANTY USE In order to receive the warranty the customer must send the duly packaged product along with the corresponding purchase Tax Receipt to Full Gauge Controls The shipping charge of the p...

Отзывы: