Installation Instructions
FHSCP-UNV Series System Coordination Guidelines
These guidelines were developed to allow the lighting system Designer/Specifier to predict the
operating performance levels of LED luminaires when powered by an electrically compatible FHSCP-
UNV Series model. It is ultimately the responsibility of the Designer/Specifier to insure that the as
installed system delivers code-compliant path of egress illumination.
1) Determine Electrical Compatibility
A) Verify that the Luminaire LED Driver, where applicable, is Class 2 compliant.
B) Verify that the Luminaire LED Lamp(s) have an operating voltage between 10Vdc and 55Vdc.
C) Verify that the Luminaire LED Lamp(s) have a power rating equal to, or greater than, the
emergency power rating of the FHSCUNV model under consideration.
Refer to Table 1 below.
TABLE 1
FHSCP-UNV MODEL
EMERGENCY OUTPUT (CONSTANT)
FHSCP-UNV-5WL
5.0 WATTS
FHSCP-UNV-7.8WL
7.8 WATTS
FHSCP-UNV-10.7WL
10.7 WATTS
FHSCP-UNV-13.7WL
13.7 WATTS
FHSCP-UNV-17WL
17.0 WATTS
2) Calculate Lumen Output During Emergency Operation
A) Access luminaire data by logging onto Design Lites Consortium (www.designlights.org).
B) Select “Search the DLC Qualified Product List ” on the DLC homepage.
C) Enter manufacture name and P/N of luminaire under consideration in the “search by keyword ”
text window.
D) Select “Search ” tab to open the “Qualified Products List ”.
E) Determine luminaire Lumens per Watt efficacy in “Rated Data ” specifications.
F) Multiply luminaire Lumens per Watt by Emergency Output of the FHSCP-UNV model under
consideration.
Refer to Table 1 above.
This figure is the Lumens available from the luminaire during emergency operation.
3) Determine Suitability of Means of Egress Lighting Levels
A) Using industry standard lighting design software, along with IES files for the luminaire under
consideration,
verify that the as installed available Lumens (as calculated in 2F above) are
sufficient to meet Code-compliant
path of egress illumination levels.
While the FHSCP-UNV series has been found compliant with the requirements of UL
Standard 924, it is ultimately the responsibility of the Designer/Specifier to assure the
as-installed system delivers code-compliant path of egress illumination in accordance with
Federal, State or local municipal requirements
.
NiCd
2020 REV D2
Fulham extends a limited warranty only to the original purchaser or to the first user for a period of 5 years from the date of manufacture when properly installed
and operated under normal conditions of use. For complete terms and conditions, please reference the Fulham Product Catalog (www.fulham.com).
Due to a program of continuous improvement, Fulham reserves the right to make modifications or variations in design or construction to the
equipment described. © Fulham Company Limited, All Rights Reserved.
Page 6 of 8