Installation Instructions

FHSCP-UNV Series System Coordination Guidelines

These guidelines were developed to allow the lighting system Designer/Specifier to predict the
operating performance levels of LED luminaires when powered by an electrically compatible FHSCP-
UNV Series model. It is ultimately the responsibility of the Designer/Specifier to insure that the as
installed system delivers code-compliant path of egress illumination.

1) Determine Electrical Compatibility

A) Verify that the Luminaire LED Driver, where applicable, is Class 2 compliant.
B) Verify that the Luminaire LED Lamp(s) have an operating voltage between 10Vdc and 55Vdc.
C) Verify that the Luminaire LED Lamp(s) have a power rating equal to, or greater than, the

emergency power rating of the FHSCUNV model under consideration.

Refer to Table 1 below.

TABLE 1

FHSCP-UNV MODEL

EMERGENCY OUTPUT (CONSTANT)

FHSCP-UNV-5WL

5.0 WATTS

FHSCP-UNV-7.8WL

7.8 WATTS

FHSCP-UNV-10.7WL

10.7 WATTS

FHSCP-UNV-13.7WL

13.7 WATTS

FHSCP-UNV-17WL

17.0 WATTS

2) Calculate Lumen Output During Emergency Operation

A) Access luminaire data by logging onto Design Lites Consortium (www.designlights.org).
B) Select “Search the DLC Qualified Product List ” on the DLC homepage.
C) Enter manufacture name and P/N of luminaire under consideration in the “search by keyword ”

text window.

D) Select “Search ” tab to open the “Qualified Products List ”.
E) Determine luminaire Lumens per Watt efficacy in “Rated Data ” specifications.
F) Multiply luminaire Lumens per Watt by Emergency Output of the FHSCP-UNV model under

consideration.

Refer to Table 1 above.

This figure is the Lumens available from the luminaire during emergency operation.

3) Determine Suitability of Means of Egress Lighting Levels

A) Using industry standard lighting design software, along with IES files for the luminaire under

consideration,

verify that the as installed available Lumens (as calculated in 2F above) are

sufficient to meet Code-compliant

path of egress illumination levels.

While the FHSCP-UNV series has been found compliant with the requirements of UL
Standard 924, it is ultimately the responsibility of the Designer/Specifier to assure the
as-installed system delivers code-compliant path of egress illumination in accordance with
Federal, State or local municipal requirements

.

NiCd

     

2020 REV D2

Fulham extends a limited warranty only to the original purchaser or to the first user for a period of 5 years from the date of manufacture when properly installed 
and operated under normal conditions of use.  For complete terms and conditions, please reference the Fulham Product Catalog (www.fulham.com).

Due to a program of continuous improvement, Fulham reserves the right to make modifications or variations in design or construction to the 
equipment described. © Fulham Company Limited, All Rights Reserved.

Page 6 of 8

Содержание Hotspot FHSCP-UNV Series

Страница 1: ...ct FHSCP UNV converter connector until installation is complete and AC power is applied to the luminaire 9 The FHSCP UNV has more than one power source To reduce the risk of electrical shock remove th...

Страница 2: ...3 7WL 13 7 WATTS FHSCP UNV 17WL 17 0 WATTS SAVE THESE IMPORTANT SAFETY INSTRUCTIONS The installation and use of this product must comply with all national federal state municipal or local codes that a...

Страница 3: ...the FHSCP UNV to the LCTS Violet to Violet Brown to Brown Refer to Figure 3 at right Strip Luminaire Select a convenient location on the xture where the LCTS will be visible after installation Allow...

Страница 4: ...ressing the LCTS simulates an AC power failure and forces the system into the Emergency Mode Only the emergency LED lamp s will be illuminated Testing may also be performed by opening circuit breaker...

Страница 5: ...extends a limited warranty only to the original purchaser or to the rst user for a period of 5 years from the date of manufacture when properly installed and operated under normal conditions of use Fo...

Страница 6: ...text window D Select Search tab to open the Quali ed Products List E Determine luminaire Lumens per Watt ef cacy in Rated Data speci cations F Multiply luminaire Lumens per Watt by Emergency Output of...

Страница 7: ...te of manufacture when properly installed and operated under normal conditions of use For complete terms and conditions please reference the Fulham Product Catalog www fulham com Due to a program of c...

Страница 8: ...t example lm w x 5 watts Refer to table FHSCP UNV MODEL SPECIFICATION CHART below for the wattage of the speci c FHSCP UNV model to be used in the luminaire lm w x FHSCP UNV Watts Minimum emergency lu...

Отзывы: