Fulham Hotspot FHSCP-UNV Series Скачать руководство пользователя страница 2

NiCd

19)

The Driver is intended for ordinary locations and for permanent installation into one or more Listed
emergency luminaires.

20)

For use with a metal enclosed wiring system.

21)

FIXTURE

The FHSCP-UNV can be used with most LED loads that operate at 10-55 VDC. See the FHSCP-
UNV Model Specification Chart for output specifications of the unit being installed.

A)

The FHSCP-UNV series has been evaluated to and found compliant to UL standard
924. The as-installed performance of system must meet or exceed all Federal, State,
and Local code requirements.

B)

Refer to Addendum 11152019 for detailed specifications and methods to calculate emergency light
levels.

FHSCP-UNV MODEL SPECIFICATION CHART

MODEL #

OUTPUT POWER (CONSTANT)

FHSCP-UNV-5WL

5.0 WATTS

FHSCP-UNV-7.8WL

7.8 WATTS

FHSCP-UNV-10.7WL

10.7 WATTS

FHSCP-UNV-13.7WL

13.7 WATTS

FHSCP-UNV-17WL

17.0 WATTS

SAVE THESE IMPORTANT SAFETY INSTRUCTIONS

The installation and use of this product must comply with all national, federal, state,
municipal, or local codes that apply. Please read this manual thoroughly before installing or
operating FHSCP-UNV Emergency LED Drivers.

     

2020 REV D2

Fulham extends a limited warranty only to the original purchaser or to the first user for a period of 5 years from the date of manufacture when properly installed 
and operated under normal conditions of use.  For complete terms and conditions, please reference the Fulham Product Catalog (www.fulham.com).

Due to a program of continuous improvement, Fulham reserves the right to make modifications or variations in design or construction to the 
equipment described. © Fulham Company Limited, All Rights Reserved.

Page 2 of 8

18)

Use with grounded, UL Listed, damp location rated fixtures and case should be grounding.

17)

The FHSCP-UNV contains a non-replaceable NiCd battery that must be recycled properly

Содержание Hotspot FHSCP-UNV Series

Страница 1: ...ct FHSCP UNV converter connector until installation is complete and AC power is applied to the luminaire 9 The FHSCP UNV has more than one power source To reduce the risk of electrical shock remove th...

Страница 2: ...3 7WL 13 7 WATTS FHSCP UNV 17WL 17 0 WATTS SAVE THESE IMPORTANT SAFETY INSTRUCTIONS The installation and use of this product must comply with all national federal state municipal or local codes that a...

Страница 3: ...the FHSCP UNV to the LCTS Violet to Violet Brown to Brown Refer to Figure 3 at right Strip Luminaire Select a convenient location on the xture where the LCTS will be visible after installation Allow...

Страница 4: ...ressing the LCTS simulates an AC power failure and forces the system into the Emergency Mode Only the emergency LED lamp s will be illuminated Testing may also be performed by opening circuit breaker...

Страница 5: ...extends a limited warranty only to the original purchaser or to the rst user for a period of 5 years from the date of manufacture when properly installed and operated under normal conditions of use Fo...

Страница 6: ...text window D Select Search tab to open the Quali ed Products List E Determine luminaire Lumens per Watt ef cacy in Rated Data speci cations F Multiply luminaire Lumens per Watt by Emergency Output of...

Страница 7: ...te of manufacture when properly installed and operated under normal conditions of use For complete terms and conditions please reference the Fulham Product Catalog www fulham com Due to a program of c...

Страница 8: ...t example lm w x 5 watts Refer to table FHSCP UNV MODEL SPECIFICATION CHART below for the wattage of the speci c FHSCP UNV model to be used in the luminaire lm w x FHSCP UNV Watts Minimum emergency lu...

Отзывы: