background image

En-5

8.  TURNING ON THE POWER

 

CAUTION

Recheck the wiring. Incorrect wiring will cause trouble.

(1)  Check the wiring of this product.
(2)  Check the wiring and switches of units connected to convertor before 

tuning on the power.

(3)  Check that the switches of this product are correct.
(4)  Refer to the indoor unit operating manual and turn on the power of 

indoor unit.

• This product is initialized for a period of approximately a few seconds 

after the power is turned on.
LED5 (green) and LED6 (orange) 

fl

 ash.

• After initial setting is completed, operation will be restarted automati-

cally. LED5 (green) lights.

* This product does not operate during initialization.

If an error occurs, the LED5, LED6, LED7, Prog LED lights or 

fl

 ashes.

Please refer to the “Error code” below.

9. LED DISPLAY

9.1. Normal code

Normal indications

Normal contents

LED5 

(green)

LED6  

(orange)

LED7 

(red)

Prog LED 

(red)

Normal starting

(Flashes alternately)

Start sequence or address 
rewriting

Programming mode display

Display mode 

 : On

 

 : Off

 

  : 1.0s ON / 1.0s OFF

 

 : State unconcerned

9.2. Error code

For the error indications of devices connected to the convertor, refer to 
each manual.

Error indications

Error contents

LED5 

(green)

LED6  

(orange)

LED7 

(red)

Prog LED 

(red)

 (11)

 (1)

Peripheral unit main PCB 
error

KNX bus error

Display mode 

  : 0.5s ON / 0.5s OFF

 

 : 0.1s ON / 0.1s OFF

 

( )  : Number of 

fl

 ashing

 

 : State unconcerned

 

 : Blinking (continuously)

9374707171-02_IM.indb   Sec1:5

9374707171-02_IM.indb   Sec1:5

28/4/2017   AM 11:14:48

28/4/2017   AM 11:14:48

Содержание UTY-VKSX

Страница 1: ...autorizado MANUALE DI INSTALLAZIONE CONVERTITORE KNX PER UNITÀ INTERNE A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΜΕΤΑΤΡΟΠΕΑΣ KNX ΓΙΑ ΕΣΩΤΕΡΙΚΉ ΜΟΝΆΔΑ Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO CONVERSOR KNX PARA UNIDADE INTERIOR Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ КОНВЕРТОР KNX ДЛЯ ВНУТРЕННЕГО МОДУЛЯ Только для авторизованн...

Страница 2: ...e quality of the preserved or stored objects Install the unit in a well ventilated place avoiding rains and direct sun light Do not operate this unit when your hands are wet Touching the unit with wet hands will cause an electric shock If children may approach the unit take preventive measures so that they cannot reach the unit CAUTION This mark indicates procedures which if improp erly performed ...

Страница 3: ...and outdoor units It may cause erroneous operation When performing wiring work be careful not to damage the cable or injure yourself Also connect the connectors securely Loose connec tors will cause trouble heating fire or electric shock Install the indoor and outdoor units power supply cable transmission cable and remote control cable 1 m 40 in away from television and ra dio to avoid distorted i...

Страница 4: ...dent or trouble Use an insulated screwdriver to set the DIP switches Before opening the cover of this unit completely discharge static electricity charged on your body Otherwise failure or malfunction could result Do not touch the circuit board and circuit board parts directly with your hands Otherwise injury or electric shock could result Tightening the mounting screws too tight will damage the b...

Страница 5: ...ted fit the 2 hooks of top cover and close the cover 2 hooks The hole for a cable can be widened as necessary When passing the thick cable through the hole widen it Connector cable to Indoor unit KNX cable KNX connector Cable tie Tightening strength Cable tie 0 3 to 0 5 N 2 7 to 4 4 lbf 3 to 5 kgf Fix the connector cable even outside the main unit as necessary Fix the cable with cable tie using 3 ...

Страница 6: ...ng initialization If an error occurs the LED5 LED6 LED7 Prog LED lights or flashes Please refer to the Error code below 9 LED DISPLAY 9 1 Normal code Normal indications Normal contents LED5 green LED6 orange LED7 red Prog LED red Normal starting Flashes alternately Start sequence or address rewriting Programming mode display Display mode On Off 1 0s ON 1 0s OFF State unconcerned 9 2 Error code For...

Отзывы: