background image

10

Fig. 31

Refrigerant pipe

3-way valve

Outdoor
unit

Service hose
with valve
core

Blank cap

Charging
valve

Cap

Service hose

Gauge
manifold

Vacuum
pump

6. VACUUM  PROCESS

1. VACUUM

(1) Remove the cap, and connect the gauge manifold

and the vacuum pump to the charging valve by the
service hoses.

(2) Vacuum the indoor unit and the connecting pipes until

the pressure in them lowers to below 1.5 mmHg.

(3) Disconnect the service hoses and fit the cap to the

charging valve (Tightening torque : 70 to 90 kgf

cm).

(4) Remove the blank caps, and fully open the spindles

of the 2-way and 3-way valves with a hexagon
wrench (Torque : 2-way valve : 70 to 90 kgf 

cm,

3-way valve : 100 to 120 kgf 

cm).

(5) Tighten the blank caps of the 2-way valve and 3-way

valve to the specified torque (200 to 250 kgf 

cm).

2. ADDITIONAL CHARGE

Refrigerant suitable for a piping length of 5 m is
charged in the outdoor unit at the factory.

When the piping is longer than 5 m, additional charg-
ing is necessary.

For the additional amount, see the table below.

Between 5 m and 20 m, when using a connection pipe
other than that shown in the table, charge additional
refrigerant with 0.42 oz (12g) / 3.3 ft (1 m) as the criteria.

(1) Always pump down the piping

before use.

(2) Add refrigerant from the charging

valve after the completion of the
work.

Table 5

25 ft

33 ft

49 ft

66 ft

(7.5 m)

(10 m)

(15 m)

(20 m)

None

2.1 oz

4.2 oz

6.3 oz

(60 g)

(120 g)

(180 g)

Pipe length

Additional

refrigerant

7. HOW TO CONNECT WIRING TO THE TERMINALS

A. For solid core wiring (or F-cable)

(1) Cut the wire end with a wire cutter or wire cut-

ting pliers, then strip the insulation to about
15/16” (25 mm) to expose the solid wire. 

(2) Using a screwdriver, remove the terminal screw

(s) on the terminal board. 

(3) Using pliers, bend the solid wire to form a loop

suitable for the terminal screw. 

(4) Shape the loop wire properly, place it on the ter-

minal board and tighten securely with the termi-
nal screw using a screwdriver.

B. For strand wiring

(1) Cut the wire end with a wire cutter or wire cut-

ting pliers, then strip the insulation to about 3/8”
(10 mm) to expose the strand wiring. 

(2) Using a screwdriver, remove the terminal screw

(s) on the terminal board. 

(3) Using a round terminal fastener or pliers, securely

clamp a round terminal to each stripped wire end. 

(4) Position the round terminal wire, and replace and

tighten the terminal screw with a screwdriver.

Fig. 32 

Solid wire 

Strand wire 

Loop

Insulation

Strip 15/16”

(25 mm)

Strip 3/8”

(10 mm)

Screw with
special washer 

Round
terminal

Terminal
board

Round
terminal

Screw with
special washer 

Round terminal 

Wire

Wire

Terminal block

Содержание SPLIT TYPE AIR CONDITIONER

Страница 1: ... thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be necessary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause dripping and water damage to walls and floors In M...

Страница 2: ...1 3 8 9 53 mm dia 5 8 15 88 mm dia Outdoor Unit Indoor Unit Floor console Indoor Unit Outdoor Unit 3 8 9 53 mm dia 5 8 15 88 mm dia Under ceiling Fig 1 A Fig 1 B ...

Страница 3: ...anch circuit and provide a special switch and receptacle Do not extend the power cord 3 OPERATING RANGE Cut each pipe to the appropriate length 12 30 cm to 16 40 cm to dampen vibration between units 2 Foamed polyethylene insulation for copper pipes as required to precise length of piping Wall thickness of the insulation should not be less than 5 16 8 mm 3 Use insulated copper wire for field wiring...

Страница 4: ...ty Application STANDARD PARTS The following installation parts are furnished Use them as required 1 1 2 4 4 4 2 6 1 1 1 1 1 1 1 Cover plate left Tapping screw ø4 x 10 For positioning the indoor unit For under ceiling type Anchor bolt M12 Spring nut For suspending the indoor unit on the wall Tapping screw ø4 x 20 For fixing the wall bracket Coupler heat insulator large For indoor side pipe joint La...

Страница 5: ...rain pipe can be easily installed 7 Take servicing etc into consideration and leave the spaces shown in Fig 2 Also install the unit where the filter can be removed 2 OUTDOOR UNIT 1 If possible do not install the unit where it will be exposed to direct sunlight If necessary install a blind that does not interfere with the air flow 2 Install the outdoor unit in a place where it will be free from bei...

Страница 6: ... either the left or right side Fig 6 When the directions are selected drill a 4 10cm dia hole on the wall so that the hole is tilted downward toward the outdoor for smooth water flow When the pipe is led out from the rear make a hole in Fig 7 at the position shown Fig 4 Screw Tapping screw Intake grille Fig 7 Wall 1 4 6 mm 4 100 mm Indoor side Fig 6 Drain hose Left side Drain hose Right side Fig 5...

Страница 7: ...ide is too high Height A should be less than 5 mm Fig 12 Install the drain hose at the rear it should not be installed on the top or right side B UNDER CEILING TYPE Using the installation template drill holes for piping and anchor bolts for holes Fig 13 2 DRILLING HOLES FOR ANCHOR BOLTS AND INSTALLING THE ANCHOR BOLTS With a concrete drill drill four 1 2 12 7 mm dia holes Fig 16 Insert the anchor ...

Страница 8: ...onnected to the left or right side Fig 6 Insert the drain hose into the drain pan then secure the drain hose with a nylon fastener Fig 9 Wrap the insulation drain hose around the drain hose connection Fig 10 Be sure to arrange the drain hose so that it is leveled lower than the drain hose connecting port to the indoor unit Fig 21 Apply the indoor unit to the brackets Fig 20 Now securely tighten th...

Страница 9: ...idth across flats 4 CONNECTING THE PIPING 1 FLARE PROCESSING 1 Cut the connection pipe with pipe cutters so that the pipe is not deformed 2 Holding the pipe downward so that cuttings cannot enter the pipe and remove the burrs 3 Remove the flare nut from the indoor unit pipe and outdoor unit and assemble as shown in Table 3 and insert the flare nut onto the pipe and flare with a flaring tool 4 Chec...

Страница 10: ...que Small pipe 22 42 to 25 32 ft lbs 310 to 350 kgf cm Large pipe 54 25 to 57 86 ft lbs 750 to 800 kgf cm Table 4 Flare nut tightening torque Be sure to connect the large pipe after connecting the small pipe completely 4 CHECKING THE PIPE CONNECTIONS FOR GAS LEAKING For both the indoor and outdoor unit sides check the joints for gas leaking by the use of a gas leakage detector without fail when th...

Страница 11: ...own the piping before use 2 Add refrigerant from the charging valve after the completion of the work Table 5 25 ft 33 ft 49 ft 66 ft 7 5 m 10 m 15 m 20 m None 2 1 oz 4 2 oz 6 3 oz 60 g 120 g 180 g Pipe length Additional refrigerant 7 HOW TO CONNECT WIRING TO THE TERMINALS A For solid core wiring or F cable 1 Cut the wire end with a wire cutter or wire cut ting pliers then strip the insulation to a...

Страница 12: ...r is chafed electric leakage may occur 4 Always connect the ground wire 1 INDOOR UNIT SIDE 1 Remove the electric component box 3 Remove the electric component box cover Remove the three tapping screws Be careful not to pinch the lead wires between the electric component box and base Fig 33 Electric component box Do not remove the screws If the stays are removed the electric component box will fall...

Страница 13: ...x must be set as follows Fig 38 Microcomputer SW1 SW1 SW1 Under ceiling type Floor console type 2 OUTDOOR UNIT SIDE A To take off the panel top remove the 2 screws B Dismount the plugs on the conduit plate C Temporarily mount the conduit tubes on the con duit plate D Properly connect both the power supply and inter unit lines to the corresponding terminals on the ter minal board Refer to the wirin...

Страница 14: ...l a leakage circuit breaker in accordance with the related laws and regulations and electric com pany standards Short circuit will occur after approx 3 minutes and the power circuit fuse blows Disconnect switch Grounding line Indoor unit Outdoor unit Fig 40 Problem 1 Air conditioner will not operate Compressor will not start only indoor unit will operate Connector trade size for this unit is 1 2 T...

Страница 15: ... wall pillar etc with the tapping screw Fig 43 Fig 43 Screws Insert Slide up q Mount the Holder w Set the Remote Control Unit e To remove the Remote Control Unit when use at hand For use as Wall Fixing Type Screws Insert Slide q Mount the Holder w Set the Remote Control Unit e Attach the unit to the holder as shown Screws For use as Handy Type 2 REMOTE CONTROL UNIT CODE SWITCHING If the jumper wir...

Страница 16: ...eated TIMER LAMP ON OFF 0 1 sec 0 1 sec 0 1sec ON OFF repeated Error display Error contents Room temperature thermistor abnormal temperature detected OPERATION LAMP ON OFF 0 5 sec 0 5 sec 5 sec Three quick flashes repeated TIMER LAMP ON OFF 0 1 sec 0 1 sec 0 1sec ON OFF repeated Piping thermistor abnormal temperature detected Table 7 2 OUTDOOR UNIT 1 Is there any abnormal noise and vibration durin...

Страница 17: ... 49 13 MOUNT THE COVER PLATE AND THE INTAKE GRILLE 2 MOUNT THE COVER PLATE LEFT 1 Join the cover plates left and mount with screws 3 MOUNT THE INTAKE GRILLE 1 Cut the right side of the intake grille This is only when the pipe exits from the right side Fig 51 2 Insert the hinges on the bottom of the intake grille into the holes in the base assembly Then mount the arms to the three areas on the top ...

Страница 18: ...June 2000 353 Rt 46 W Fairfield NJ 07004 888 888 FGAI www fujitsugeneral com ...

Отзывы: