En-13

The remote control unit resets to signal code A when the 
batteries in the remote control unit are replaced. If you use a 
signal code other than signal code A, reset the signal code 
after replacing the batteries.
If you do not know the air conditioner signal code setting, 
try each of the signal codes (

) until you 

fi

 nd the 

code which operates the air conditioner.

STEP 2
Selecting the Function Number and Setting Value

Press the SET TEMP. (

(1) 

) (

) buttons to select the func-

tion number. (Press the MODE button to switch between 
the left and right digits.)
Press the FAN button to proceed to setting the value. 

(2) 

(Press the FAN button again to return to the function 
number selection.)
Press the SET TEMP. (

(3) 

) (

) buttons to select the set-

ting value. (Press the MODE button to switch between the 
left and right digits.)
Press the TIMER MODE button, and START/STOP button, 

(4) 

in the order listed to con

fi

 rm the settings.

Press the RESET button to cancel the function setting 

(5) 

mode.
After completing the FUNCTION SETTING, be sure to turn 

(6) 

off the power and turn it on again.

Function number 

Setting value

 CAUTION

After turning off the power, wait 30 seconds or more 

• 

before turning on it again. The FUNCTION SETTING 
doesn’t become effective if it doesn’t do so.

9. FUNCTION SETTING

 CAUTION

Con

fi

 rm whether the wiring work for outdoor unit has 

• 

been 

fi

 nished.

Con

fi

 rm whether the cap for electric control box on the 

• 

outdoor unit is close.

This procedure changes to the function settings used to con-

• 

trol the indoor unit according to the installation conditions. 
Incorrect settings can cause the indoor unit malfunction.

After the power is turned on, perform the “FUNCTION 

• 

SETTING” according to the installation conditions using the 
remote controller.

The settings may be selected between the following two: 

• 

Function Number or Setting Value.

Settings will not be changed if invalid numbers or setting 

• 

values are selected.

Refer to the installation manual enclosed with the remote 

• 

control unit when the wired remote control unit (option) is 
used.

9.1. Operation method

While pressing the FAN button and SET TEMP. (

• 

) simul-

taneously, press the RESET button to enter the function 
setting mode.

STEP 1
Selecting the Remote Control Unit Signal Code

Use the following steps to select the signal code of the remote 
control unit.
(Note that the air conditioner cannot receive a signal code if 
the air conditioner has not been set for the signal code.)
The signal codes that are set through this process are ap-
plicable only to the signals in the FUNCTION SETTING. For 
details on how to set the signal codes through the normal 
process, refer to SELECTING THE REMOTE CONTROL 
UNIT SIGNAL CODE.

Press the SET TEMP. (

(1) 

) (

) button to change the 

signal code between 

Match the code on the display to the air conditioner signal 
code. (initially set to  ) (If the signal code does not need 
to be selected, press the MODE button and proceed to 
STEP 2.)
Press the TIMER MODE button and check that the indoor 

(2) 

unit can receive signals at the displayed signal code.
Press the MODE button to accept the signal code, and 

(3) 

proceed to STEP 2.

The air conditioner signal code is factory-set to A .
Contact your retailer to change the signal code.

Содержание RCF24LBL

Страница 1: ...material 5 4 2 Pipe requirement 6 4 3 Flare connection pipe connection 6 4 4 Installing heat insulation 7 5 INSTALLING DRAIN PIPES 7 6 ELECTRICAL WIRING 6 1 Electrical requirement 8 6 2 Wiring method 9 7 REMOTE CONTROLLER SETTING 7 1 Load batteries R03 LR03 2 10 7 2 Installing the Remote control unit holder 11 8 DECORATION PANEL INSTALLATION 8 1 Remove the intake grille 11 8 2 Installing the panel...

Страница 2: ... 6 times higher than the R22 failure to use dedicated piping material or improper installation can cause rupture or injury Furthermore it can cause serious accidents such as water leakage electric shock or fire Tool name Changes Gauge manifold The pressure in the refrigerant system is extremely high and can not be measured with a conven tional gauge To prevent erroneous mixing of other refrigerant...

Страница 3: ... unit to fall water leakage electric shock or fire The following installation parts are furnished Use them as required Keep the Installation Manual in a safe place and do not dis card any other accessories until the installation work has been completed Name and Shape Q ty Description Coupler heat insulation Large 1 For indoor side pipe joint gas pipe Coupler heat insulation Small 1 For indoor side...

Страница 4: ...gh salt content such as at the seaside It will deteriorate metal parts causing the parts to fall or the unit to leak water Area filled with mineral oil or containing a large amount of splashed oil or steam such as a kitchen It will deteriorate plastic parts causing the parts to fall or the unit to leak water Area that generates substances that adversely affect the equipment such as sulfuric gas ch...

Страница 5: ...AUTION Be more careful that foreign matter oil water etc does not enter the piping than with refrigerant R410A models Also when storing the piping securely seal the openings by pinching taping etc While welding the pipes be sure to blow dry nitrogen gas through them 4 1 Selecting the pipe material CAUTION Do not use existing pipes Use pipes that have clean external and internal sides without any c...

Страница 6: ...quirement CAUTION Refer to the Installation Manual of the outdoor unit for description of the length and the diameter of connecting pipe or for difference of its elevation Use pipe with water resistant heat insulation CAUTION Install heat insulation around both the gas and liquid pipes Failure to do so may cause water leaks Use heat insulation with heat resistance above 120 C Reverse cycle model o...

Страница 7: ...rain pipe with downward gradient 1 50 to 1 100 and so there are no rises or traps in the pipe Use general hard polyvinyl chloride pipe VP25 outside di ameter 32 mm 1 1 4 and connect it with adhesive polyvi nyl chloride so that there is no leakage When the pipe is long install supporters Do not perform air bleeding Always heat insulate the indoor side of the drain pipe When desiring a high drain pi...

Страница 8: ...g sure that there are no external forces of the wires applied to the terminal connections Improperly connected or secured wires can cause seri ous accidents such as overheating the terminals electric shock or fire Do not modify the power cables use extension cables or use any branches in the wiring Improper connections insufficient insulation or exceeding the allowable current can cause electric s...

Страница 9: ... Power supply cable or Transmission cable 20 mm 40 mm or more Earth wire How to connect wiring to the terminals For strand wiring Use crimp type terminals with insulating sleeves as shown 1 in the figure below to connect to the terminal block Securely crimp the crimp type terminals to the wires using 2 an appropriate tool so that the wires do not come loose Sleeve Crimp type terminal Use the speci...

Страница 10: ...es NOTE Never mix new and used batteries or batteries of different types Batteries should last about one year under normal use If the Remote Control Unit s operating range becomes appreciably reduced replace the batteries and press the RESET button with the tip of a ballpoint pen or other small object 6 2 3 Wiring procedure Remove the control box cover and install each connection 1 wire Screw Cont...

Страница 11: ...trol unit and the photocell as the criteria However when installing the remote control unit check that it operates positively Install the remote control unit holder to a wall pillar etc with the tapping screw Mount the holder 1 Screws Set the remote control unit 2 Insert Press in To remove the remote control unit when use at hand 3 Slide up Pull out 8 DECORATION PANEL INSTALLATION Installation acc...

Страница 12: ...relative to the air conditioner body Install so that there is no gap between the grille assem bly and the air conditioner body The decoration panel equips with an accessory to prevent the grill completely open Be sure to read the INSTALLATION SHEET included with the decoration panel before installation 8 2 Installing the panel to indoor unit Install the decoration panel on the indoor unit 1 DRAIN ...

Страница 13: ...indoor unit according to the installation conditions Incorrect settings can cause the indoor unit malfunction After the power is turned on perform the FUNCTION SETTING according to the installation conditions using the remote controller The settings may be selected between the following two Function Number or Setting Value Settings will not be changed if invalid numbers or setting values are selec...

Страница 14: ...Do not change this setting in the 3 way outlet mode Setting the Outlet Directions Select the setting values in the table below for using a 3 way outlet The setting value is factory set to 00 Setting Description Function Number Setting Value 4 way 22 00 3 way 01 Setting the Filter Sign The indoor unit has a sign to inform the user that it is time to clean the filter Select the time setting for the ...

Страница 15: ...gnal code of the remote control unit Note that the air conditioner cannot receive a signal code if the air conditioner has not been set for the signal code Press the START STOP button until only the clock is 1 displayed on the remote control unit display Press the MODE button for at least five seconds to display 2 the current signal code initially set to Press the SET TEMP button to change the sig...

Страница 16: ...tting value Master Slave 9 4 Special installation methods This possible only the wired remote control Option CAUTION When setting DIP switches do not touch any other parts on the circuit board directly with your bare hands Be sure to turn off the main power 9 4 1 Simultaneous multi system operation By combining with an outdoor unit 2 units for twin and 3 units for triple indoor units can be switch...

Страница 17: ...ng Refrigerant circuit address setting Function number 02 Unit number Setting value Master Slave setting Function number 51 Unit number Setting value Make sure that the indoor unit with the unit number 00 is connected to the outdoor unit using a transmission cable 9 4 2 Group control system A number of indoor units can be operated at the same time using a single remote controller 1 Wiring method i...

Страница 18: ...nit toward the air condi tioner and press the test run button with the tip of a ball point pen etc Transmitter section Test run button To end test operation press the remote control unit START STOP button When the air conditioner is run by pressing the test run but ton the OPERATION Lamp and TIMER Lamp will simulta neously flash slowly Using the wired remote control Option For the operation method...

Страница 19: ...h abnormal Pres sure sensor abnormal 7 times 6 times Compressor temperature error 7 times 7 times Low pressure error 8 times 2 or 3 times Active filter abnormal 8 times 4 times P F C circuit error 8 times 6 times P F C printed circuit board error 9 times 2 times Refrigerant circuit address set up error 9 times 3 times Master unit Slave unit set up error 9 times 4 times Connected the indoor number ...

Страница 20: ...exchanger temperature sensor middle error 28 Indoor heat exchanger temperature sensor inlet error 09 Float switch operated 0c Outdoor discharge pipe temperature sensor error 06 Outdoor heat exchanger temperature sensor outlet error 0A Outdoor temperature sensor error 0E Heat sink thermistor Inverter error 15 Compressor temperature sensor error 1d 2 way valve temperature sensor error 1E 3 way valve...