5.3.17
Performing a fan test
Notes on replacing a defective fan
After replacing a defective system fan or PSU containing a defective fan,
the fan error indicators will stay lit until the next fan test. By default, a fan
test is automatically started every 24 hours. The first automatic fan test
being performed after replacing a fan will turn off the fan error indicator.
If you want to start the fan test manually, you can do so by following the
description below:
Executing the fan test via the iRMC S5 web interface
▶
Log into the iRMC S5 web interface.
The
System
menu is displayed on default.
▶
Open the
Cooling
page.
▶
Expand the
Cooling Devices
group.
▶
Click
Start Fan Test
.
For more information on iRMC settings, see the iRMC user guides.
Executing the fan test via ServerView Operations Manager
▶
Open the ServerView Operations Manager and log in.
▶
Under
Administration
select
Server Configuration
.
▶
In the hierarchy tree of the
Server list
tab, select the server to be
configured.
▶
In the right-hand side of the window, specify the details on the selected
server and confirm your entries by clicking
GO...
. In the left-hand section of
the window, the
Configuration
tab is being activated.
▶
In the navigation area of the
Configuration
tab, select
Other Settings
.
▶
Under
Daily Fan Test
, set the daily fan test time to a few minutes from the
current time. (Ensure to note down your previous setting.)
Basic software procedures
RX2530 M6
Upgrade and Maintenance Manual
103
Содержание PRIMERGY RX2530 M5
Страница 18: ...Content Upgrade and Maintenance Manual RX2530 M6 ...
Страница 194: ...Fans 194 Upgrade and Maintenance Manual RX2530 M6 ...
Страница 262: ...Expansion cards and backup units 262 Upgrade and Maintenance Manual RX2530 M6 ...
Страница 278: ...Main memory 278 Upgrade and Maintenance Manual RX2530 M6 ...
Страница 324: ...Accessible drives 324 Upgrade and Maintenance Manual RX2530 M6 ...
Страница 336: ...Front panel 336 Upgrade and Maintenance Manual RX2530 M6 ...
Страница 344: ...Serial interface 344 Upgrade and Maintenance Manual RX2530 M6 ...
Страница 428: ...FUJITSU Server PRIMERGY RX2530M6 Reference Manual Reference Manual English Cable plan for April 2021 ...
Страница 438: ...11 RX2530 M6 Basic OOB 4x3 5 Cable plan System Board D3890 A SMB1 4x 3 5 HDD Backplane SMB1 CA05950 2054 SB BP ...
Страница 439: ...12 RX2530 M6 Basic OOB 8x2 5 Cable plan System Board D3890 A SMB1 8x 2 5 HDD Backplane SMB1 CA05950 2054 SB BP ...
Страница 440: ...13 RX2530 M6 Basic OOB 10x2 5 Cable plan System Board D3890 A SMB1 10x 2 5 HDD Backplane SMB1 CA05950 2054 SB BP ...
Страница 444: ...17 RX2530 M6 Power 4x3 5 Cable plan CA05950 2050 System Board D3890 A PWR 2 4x3 5 HDD Backplane PWR1 ...
Страница 445: ...18 RX2530 M6 Power 8x2 5 Cable plan CA05950 2050 System Board D3890 A PWR 2 8x2 5 HDD Backplane PWR1 ...
Страница 446: ...19 RX2530 M6 Power 10x2 5 Cable plan CA05950 2052 System Board D3890 A PWR 2 10x2 5 HDD Backplane PWR1 ...
Страница 449: ...22 RX2530 M6 Power Rear 2x2 5 Cable plan System Board D3890 A PWR 1 2x2 5 rear HDD Backplane CA05950 2077 PWR 5 ...
Страница 450: ...23 RX2530 M6 Power Internal RAID Riser Cable plan CA05950 2051 System Board D3890 A PWR 1 Internal RAID Riser PWR 1 ...
Страница 478: ...51 RX2530 M6 Data Dual microSD 64GB Enterprise Cable plan Dual microSD 64GB Enterprise A ROC CON1 Y4018 V8 ...
Страница 480: ...List of all used screws for PRIMERGY Servers Assembled in Germany and Japan February 2019 ...