SPECIFICATIONS
3.
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 80°F (26.67 °C)DB / 67°F (19.44 °C)WB, and outdoor temperature of 95°F (35 °C)DB / 75°F (23.9 °C)WB.
Pipe length : 24ft.7in. (7.5 m), Height difference : 0 m.(Outdoor unit - Indoor unit)
Type
WALL MOUNTED
INVERTER COOLING ONLY
Model name
ASU30CLX1
ASU36CLX1
Power source
208/230V ~ 60Hz
Available voltage range
187-253V ~ 60Hz
Capacity
Cooling
Rated
kW
9.00
9.70
BTU/h
30,800
33,000
Min-Max
kW
2.90 - 9.50
2.90 - 10.00
BTU/h
9900 - 32400
9900 - 34100
Heating
Rated
kW
-
-
BTU/h
-
-
Min-Max
kW
-
-
BTU/h
-
-
Input power
Cooling
Rated
kW
3.24
3.88
Max
3.87
4.10
Heating
Rated
-
-
Max
-
-
Current
Cooling
Rated
A
14.2
17.0
Max
17.0
18.0
Heating
Rated
-
-
Max
-
-
EER
Cooling
kW/kW
2.78
2.50
BTU/hW
9.5
8.5
COP
Heating
kW/kW
-
-
BTU/hW
-
-
SEER
Cooling
BTU/hW
16.5
15.5
HSPF
Heating
BTU/hW
-
-
SENSIBLE CAPACITY
Cooling
kW
6.25
6.39
POWER FACTOR
Cooling
%
99
99
Heating
-
-
Moisture removal
pints/h (l/h)
9.7(4.6)
10.1(4.8)
Fan
Airflow
rate
Cooling
High
CFM
(m
3
/h)
659 (1,120)
694 (1,180)
Med
530 (900)
530 (900)
Low
435 (740)
435 (740)
Quiet
365 (620)
365 (620)
Heating
High
-
-
Med
-
-
Low
-
-
Quiet
-
-
Type × Q'ty
Cross flow fan x 1
Motor output
W
42
65
Sound pressure level
Cooling
High
dB(A)
49
50
Med
42
42
Low
37
37
Quiet
33
33
Heating
High
-
-
Med
-
-
Low
-
-
Quiet
-
-
Heat exchanger type
Dimensions
(H × W × D)
in. (mm)
Main:15-7/8 x 33-3/4 x 1-1/16 (378×832×26.6)
Sub: 3-5/16 x 33-3/4 x 17/32 (84×832×13.3)
Fin pitch
FPI
Main:21, Sub:18
Rows x Stages
Main:2×18, Sub:1×4
Pipe type
Copper
Fin type
Aluminium
Enclosure
Material
Polystyrene
Color
White
Approximate Color of MUNSELL N9.25/
Dimensions
( H×W×D)
Net
mm
320×998×228
inch
12-5/8×39-1/4×9
Gross
mm
319×1090×429
inch
12-3/5×42-15/16×16-7/8
Weight
Net
lbs.(kg)
31 (14 )
Gross
40 (18 )
Connection pipe
Size
Liquid
in. (mm)
Ø3/8 (Ø9.52)
Gas
Ø5/8 (Ø15.88 )
Method
Flare
Operation range
Cooling
°F (°C)
64 to 90 (18 to 32)
%RH
80 or less
Heating
°F (°C)
-
-
Remote controller type
Wireless
Drain pipe
Material
PVC
Size
mm
(Reference in.)
Outer diameter: 28 (1-3/32)
Inner diameter: 16 (5/8) .
Содержание Inverter Halcyon AOU30CLX1
Страница 2: ...1 INDOOR UNIT WALL MOUNTED TYPE ASU30CLX1 ASU36CLX1 DTR_AS048E_02 2011 02 10 ...
Страница 25: ...2 OUTDOOR UNIT SINGLE TYPE AOU30CLX1 AOU36CLX1 DTR_AO070E_02 2011 02 10 ...
Страница 30: ... 02 04 OUTDOOR UNIT AOU30 36CLX1 OUTDOOR UNIT AOU30 36CLX1 WIRING DIAGRAMS 444 MODEL AOU30CLX1 AOU36CLX1 ...
Страница 35: ... 02 09 OUTDOOR UNIT AOU30 36CLX1 OUTDOOR UNIT AOU30 36CLX1 SOUND LEVEL CHECK POINT 88888 3ft 3 3 8 in 1m ...