AIR CONDITIONER

Wall Mounted type

INDOOR

OUTDOOR

ASU24CL1

AOU24CL1

DESIGN & TECHNICAL MANUAL

Содержание Inverter Halcyon AOU24CL1

Страница 1: ...AIR CONDITIONER Wall Mounted type INDOOR OUTDOOR ASU24CL1 AOU24CL1 DESIGN TECHNICAL MANUAL ...

Страница 2: ...1 INDOOR UNIT WALL MOUNTED TYPE ASU24CL1 DTR_AS046E_02 2010 12 02 ...

Страница 3: ... 01 08 6 1 COOLING CAPACITY 01 08 7 FAN PERFORMANCE 01 09 7 1 AIR VELOCITY DISTRIBUTION 01 09 7 2 AIR FLOW 01 10 8 OPERATION NOISE 01 11 8 1 NOISE LEVEL CURVE 01 11 8 2 SOUND LEVEL CHECK POINT 01 12 9 ELECTRIC CHARACTERISTICS 01 13 10 SAFETY DEVICES 01 14 11 EXTERNAL INPUT OUTPUT 01 15 11 1 EXTERNAL INPUT 01 15 11 2 EXTERNAL OUTPUT 01 16 12 FUNCTION SETTING 01 17 12 1 INDOOR UNIT 01 17 13 OPTIONAL...

Страница 4: ... More compact compared with conventional model PAM technology makes a compressor more powerful PAM control b DC compressor c a DC fan motor DC fan motor Super quiet z z Air flow mode can be set in 4 steps and more detailed air flow setting is possible Easy maintenance z z Easy maintenance and always clean Troublesome maintenance has been made easy Since the front panel is easy to remove maintenanc...

Страница 5: ...cooling operation at 14 F 10 C outdoor air temperature Corresponds to maximum 98 feet 30m long piping z z Air conditioner filter features z z Organic coating fin used heat exchanger Pre Filter Antibacterial deodorizing pre filter with special ceramic powder Ion Deodorization Filter Apple catechin Filter Apple catechin Filter Long life Ion Deodorization Filter Blue fin heat exchanger z z Corrosion ...

Страница 6: ... a 24 hour period Sleep timer z z The sleep timer function automatically corrects the temperature thermostat setting according to the timer setting to prevent excessive cooling while sleeping 60min 2 F 1 C 4 F 2 C Timer setting Cooling operation dry operation When the sleep timer is set the set temperature automatically rises 2 F 1 C every hour The set temperature can rise up to a maximum of 4 F 2...

Страница 7: ...orizontal 11 SWING button 12 RESET button 13 TEST RUN button This button is used when installing the air conditioner and should not be used under normal conditions as it will cause the indoor unit s thermostat function to operate incorrectly If this button is pressed during normal operation the indoor unit will switch to test operation mode and the Indoor Unit s OPERATION Indicator Lamp and TIMER ...

Страница 8: ...TY Cooling kW 5 33 POWER FACTOR Cooling 99 Moisture removal pints h l h 6 3 3 0 Fan Airflow rate Cooling High CFM m3 h 659 1120 Med 530 900 Low 436 740 Quiet 365 620 Type Q ty Cross flow fan 1 Motor output W 40 Sound pressure level Cooling High dB A 48 Med 42 Low 37 Quiet 33 Heat exchanger type Dimensions H W D in mm Main 15 7 8 33 3 4 1 1 16 378 832 26 6 Sub 3 5 16 33 3 4 17 32 84 832 13 3 Fin pi...

Страница 9: ...ONS 444 MODEL ASU24CL1 Unit in mm INSTALLATION PLACE Unit in mm 2 15 32 63 or more 3 5 32 80 or more 2 3 32 53 or more 2 1 16 52 or more 3 5 32 80 or more Outline of unit 4 23 32 120 or more 59 1 16 1 500 or more 70 7 8 1 800 or more 39 9 32 998 8 31 32 228 12 19 32 320 ...

Страница 10: ...NTED TYPE ASU24CL1 WALL MOUNTED TYPE ASU24CL1 WIRING DIAGRAMS 555 MODEL ASU24CL1 TO OUTDOOR UNIT CONTROOL BOARD TEST CN13 CN14 2 1 CN16 EX OUT OPTION EX IN OPTION 1 2 3 BLACK WHITE RED REMOTE CONTROL UNIT OPTION 3 2 1 ...

Страница 11: ... 36 24 0 18 2 2 40 25 4 18 1 2 43 26 9 19 3 2 45 104 17 0 12 8 2 50 19 0 12 8 2 54 19 6 14 0 2 55 21 6 15 1 2 59 22 9 15 1 2 62 24 2 16 1 2 64 115 16 0 11 3 2 53 17 8 11 4 2 57 18 5 12 4 2 58 20 3 13 5 2 62 21 5 13 4 2 64 22 7 14 3 2 67 AFR 18 7 Indoor temperature CDB 17 8 21 1 23 9 26 7 29 4 32 2 CWB 12 2 15 6 17 7 19 4 21 7 22 8 Outdoor temperature CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC ...

Страница 12: ... 5 6 7 8 ft 7 14 20 27 7 3 0 3 7 ft 7 2 3 1 2 0 5 3 2 1 0 m m SIDE VIEW Vertical flap Up Horizontal flap Center Unit ft s m s 0 1 2 3 4 5 6 7 8 ft 7 14 20 27 10 7 3 0 ft 2 0 5 2 0 5 3 1 3 1 7 2 7 2 3 2 1 0 1 2 3 m m TOP VIEW Vertical flap Up Horizontal flap Right Left Unit ft s m s 0 1 2 3 4 5 6 7 8 ft 7 14 20 27 10 7 3 0 3 7 10 ft 7 2 3 1 2 0 5 3 2 1 0 m m SIDE VIEW Vertical flap Down Horizontal ...

Страница 13: ...NTED TYPE ASU24CL1 AIR FLOW 77777 MODEL ASU24CL1 Cooling z z Fan speed Number of rotations r p m Air flow HIGH 1480 1120 m3 h 311 l s 659 CFM MED 1220 900 m3 h 250 l s 530 CFM LOW 1020 740 m3 h 206 l s 436 CFM QUIET 900 620 m3 h 172 l s 365 CFM ...

Страница 14: ...888 NOISE LEVEL CURVE 88888 MODEL ASU24CL1 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 High Quiet Cooling z z Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 ...

Страница 15: ... 01 12 WALL MOUNTED TYPE ASU24CL1 WALL MOUNTED TYPE ASU24CL1 SOUND LEVEL CHECK POINT 88888 39 3 8 in 1m 31 1 2 in 0 8 m ...

Страница 16: ...TERISTICS 999 Model name ASU24CL1 Power supply Voltage V 208 230 Frequency Hz 60 Max operating current A 0 3 Wiring Spec Connection cable AWG 14 Limited wiring length ft 102 Wiring Spec Selected Sample Selected based on Japan Electrotechnical Standard and Codes Committee E0005 ...

Страница 17: ...L1 SAFETY DEVICES 1111 Protection form Model ASU24CL1 Circuit protection Current fuse PCB 3 15A 250V Terminal protection Current thermal fuse 3A 250V 215 F 102 C Fan motor protection Thermal protector program 212 27 18 F 100 15 10 C OFF 203 9 18 F 95 5 10 C ON ...

Страница 18: ...at the left Operation mode Auto changeover Mode at previous operation Set temperature 75 F 24 C Temperature at previous operation Air flow mode AUTO Mode at previous operation Up down air direction swing Standard air direction swing OFF Air direction at previous operation Left right air direction swing Standard air direction swing OFF Air direction at previous operation Circuit diagram example z z...

Страница 19: ...Field supply Ex Display Indoor control PC board Connected unit Ex Relay unit 1 2 Signal Relay power supply V Connector Make the distance from the PC board to the connected unit within 33ft 10m Relay spec Max 24VDC 10mA to less than 500mA 33 ft 10 m 24V DC ON OFF Operation Stop Indoor unit Output signal Parts Optional z z Parts name Model name External connect kit UTY XWZX Wire External output ...

Страница 20: ...ED TYPE ASU24CL1 FUNCTION SETTING 1111 INDOOR UNIT 111111 SWITCH POSITION MAIN PCB JM5 JM6 JM7 JM8 JM10 JM5 JM6 JM7 JM8 JM10 INDOOR UNIT Jumper Wire JM 5 Auto restart JM 6 Room temperature correction JM 7 JM 8 Remote controller signal code JM 10 ...

Страница 21: ...he signal code Press the START STOP button until only the clock is displayed on the remote controller display 111 Press the MODE button for at least five seconds to display the current signal code initially set to 222 Press the SET TEMP 333 button to change the signal code between Match the code on the display to the air conditioner signal code Press the MODE button again to return to the clock di...

Страница 22: ...visible mold spores and harmful microorganisms are absorbed onto the filter by static electricity and further growth is inhibited and deactivated by the polyphenol ingredient extracted from apples Ion deodorisation filter UTR FA13 2 The filter deodorizes by powerfully decomposing absorbed odors using the oxidizing and reducing effects of ions generated by the ultra fine particle ceramic External c...

Страница 23: ...2 OUTDOOR UNIT SINGLE TYPE AOU24CL1 DTR_AO068E_02 2010 12 02 ...

Страница 24: ...RIGERANT CIRCUIT 02 03 4 WIRING DIAGRAMS 02 04 5 CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE 02 05 6 ADDITIONAL CHARGE CALCULATION 02 06 7 AIR FLOW 02 07 8 OPERATION NOISE 02 08 8 1 NOISE LEVEL CURVE 02 08 8 2 SOUND LEVEL CHECK POINT 02 09 9 ELECTRIC CHARACTERISTICS 02 10 10 SAFETY DEVICES 02 11 ...

Страница 25: ...otary 1 Motor output W 1 100 Refrigerant Type R410A Charge lb oz 2 lb 13 9 oz kg 1 3 Refrigerant oil Type POE VG74 Enclosure Material Steel Color BEIGE Approximate color of MUNSELL 10YR7 5 1 0 Dimensions H W D Net mm 620 790 298 inch 24 7 16 31 1 8 11 3 4 Gross mm 712 935 400 inch 28 1 16 36 13 16 15 3 4 Weight Net lb kg 88 40 Gross 97 44 Connection pipe Size Liquid inch mm Ø1 4 Ø6 35 Gas Ø5 8 Ø15...

Страница 26: ...t in mm INSTALLATION PLACE Top view Front view Air flow Bottom view Side view 23 5 8 600 or more 3 15 16 100 or more 11 13 16 300 or more 3 15 16 100 or more 11 13 16 300 or more Service space If the space is larger that is stated the condition will be the same as that are no obstacles ...

Страница 27: ...OU24CL1 REFRIGERANT CIRCUIT 333 MODEL AOU24CL1 Cooling Muffler Sub accumulator Compressor 3 Way valve Heat exchanger INDOOR Heat exchanger OUTDOOR 2 Way valve Expansion valve Strainer Refrigerant pipe diameter Liquid 1 4 6 35 mm Gas 5 8 15 88 mm ...

Страница 28: ... 02 04 OUTDOOR UNIT AOU24CL1 OUTDOOR UNIT AOU24CL1 WIRING DIAGRAMS 444 MODEL AOU24CL1 ...

Страница 29: ...length m 5 7 5 10 15 20 25 30 16ft 25ft 33ft 49ft 66ft 82ft 98ft Height difference H m Û1 Indoor unit is upper than outdoor unit 20 66ft 0 951 0 951 0 950 10 33ft 0 980 0 966 0 967 0 967 0 966 7 5 25ft 0 988 0 984 0 970 0 971 0 971 0 970 5 16ft 0 995 0 992 0 988 0 974 0 975 0 975 0 974 0 0ft 1 003 1 000 0 996 0 982 0 983 0 983 0 982 Û2 Indoor unit is under than outdoor unit 5 16ft 1 003 1 000 0 99...

Страница 30: ...L CHARGE CALCULATION 666 MODEL AOU24CL1 Refrigerant charge z z Refrigerant type R410A Refrigerant amount lb oz 2lb 13 9oz g 1300 Pipe length ft 49 66 82 98 0 22oz ft 20g m m 15 20 25 30 Additional charge oz 0 Charge less 3 5 7 1 10 6 g 0 Charge less 100 200 300 ...

Страница 31: ... 02 07 OUTDOOR UNIT AOU24CL1 OUTDOOR UNIT AOU24CL1 AIR FLOW 777 MODEL AOU24CL1 Cooling z z Number of rotations r p m Air flow 1100 2640 m h 733 l s 1554 CFM ...

Страница 32: ...888 NOISE LEVEL CURVE 88888 MODEL AOU24CL1 Cooling z z Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 ...

Страница 33: ... 02 09 OUTDOOR UNIT AOU24CL1 OUTDOOR UNIT AOU24CL1 SOUND LEVEL CHECK POINT 88888 39 3 8 in 1m ...

Страница 34: ...cuit breaker Current A 20 Power Cable AWG 11 3 Limited wiring length ft 66 1 The maximum current is the total current of indoor unit and outdoor unit 2 Wiring spec Selected Sample Selected based on Japan Electrotechnical Standard and Codes Committee E0005 3 Limited wiring length This is the wiring length in case voltage descent is less than 2 When the wiring length becomes long please select the w...

Страница 35: ...t protection Current fuse NEAR THE TERMINAL 20A 250V 5A 250V Current fuse MAIN PRINTED CIRCUIT BOARD 15A 250V 3 15A 250V Fan motor protection Thermal protection program OFF 212 50 F 100 10 C ON 203 50 F 95 10 C Compressor protection Thermal protection program DISCHARGE TEMP OFF 230 F 110 C ON After 7 minutes ...