SPLIT TYPE ROOM AIR CONDITIONER

INSTALLATION MANUAL

(P/N 9314252136-02)

ENGLISH

   MODEL: ASU12R2/AOU12R2

ASU9R2/AOU9R2

IMPORTANT!
Please Read Before Starting

This air conditioning system meets strict safety and operating standards.
As  the  installer  or  service  person,  it  is  an  important  part  of  your  job  to
install or service the system so it operates safely and efficiently.

For safe installation and trouble-free operation, you must:

Carefully read this instruction booklet before beginning.

Follow each installation or repair step exactly as shown.

Observe all local, state, and national electrical codes.

Pay close attention to all danger, warning, and caution notices given in
this manual.

WARNING:

This symbol refers to a hazard or unsafe practice which
can result in severe personal injury or death.

CAUTION:

This symbol refers to a hazard or unsafe practice which
can result in personal injury and the potential for product
or property damage.

Hazel alerting symbols

Electrical

Safety / alert

If Necessary, Get Help

These instructions are all you need for most installation sites and mainte-
nance conditions. If you require help for a special problem, contact our
sales/service outlet or your certified dealer for additional instructions.

In Case of Improper Installation

The manufacturer shall in no way be responsible for improper installation
or maintenance service, including failure to follow the instructions in this
document.

SPECIAL PRECAUTIONS

When Wiring

ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL
INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED
ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.

Do not supply power to the unit until all wiring and tubing are completed
or reconnected and checked.

Highly dangerous electrical voltages are used in this system. Carefully
refer to the wiring diagram and these instructions when wiring. Improper
connections  and  inadequate  grounding  can  cause  accidental  injury
or death.

Ground the unit following local electrical codes.

Connect all wiring tightly. Loose wiring may cause overheating at con-
nection points and a possible fire hazard.

When Transporting

Be careful when picking up and moving the indoor and outdoor units. Get
a partner to help, and bend your knees when lifting to reduce strain on
your back. Sharp edges or thin aluminum fins on the air conditioner can
cut your fingers.

When Installing...

...In a Ceiling or Wall

Make sure the ceiling/wall is strong enough to hold the unit’s weight. It
may be necessary to construct a strong wood or metal frame to provide
added support.

...In a Room

Properly insulate any tubing run inside a room to prevent “sweating” that
can cause dripping and water damage to walls and floors.

...In Moist or Uneven Locations

Use  a  raised  concrete  pad  or  concrete  blocks  to  provide  a  solid,  level
foundation for the outdoor unit. This prevents water damage and abnor-
mal vibration.

...In an Area with High Winds

Securely anchor the outdoor unit down with bolts and a metal frame. Pro-
vide a suitable air baffle.

...In a Snowy Area (for Heat Pump-type Systems)

Install  the  outdoor  unit  on  a  raised  platform  that  is  higher  than  drifting
snow. Provide snow vents.

When Connecting Refrigerant Tubing

Keep all tubing runs as short as possible.

Use the flare method for connecting tubing.

Apply  refrigerant  lubricant  to  the  matching  surfaces  of  the  flare  and
union tubes before connecting them, then tighten the nut with a torque
wrench for a leak-free connection.

Check carefully for leaks before starting the test run.

NOTE:

Depending on the system type, liquid and gas lines may be either narrow
or wide. Therefore, to avoid confusion the refrigerant tubing for your par-
ticular model is specified as either “small” or “large” rather than as “liquid”
or “gas”.

When Servicing

Turn the power OFF at the main circuit breaker panel before opening
the unit to check or repair electrical parts and wiring.

Keep your fingers and clothing away from any moving parts.

Clean up the site after you finish, remembering to check that no metal
scraps or bits of wiring have been left inside the unit being serviced.

After installation, explain correct operation to the customer, using the
operating manual.

 (

)

Содержание Inverter Halcyon AOU12R2

Страница 1: ... Connect all wiring tightly Loose wiring may cause overheating at con nection points and a possible fire hazard When Transporting Be careful when picking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Mak...

Страница 2: ...an air conditioner using R410A incurs pressure higher than when using R22 it is necessary to choose adequate materials Thicknesses of copper pipes used with R410A are as shown in Table1 Never use copper pipes thinner than 0 8mm even when it is available on the market Contents of change Pressure is high and cannot be measured with a conventional gauge To prevent erroneous mixing of other refrigeran...

Страница 3: ... and must be purchased separately CAUTION 9000 BTU h 12000 BTU h MINIMUM CIRCUIT AMPACITY 12 A 15 A MAXIMUM OVERCURRENT PROTECTION 15 A 20 A TIME DELAY FUSE OR HACR TYPE CIRCUIT BREAKER Cut each pipe to the appropriate length 12 30 cm to16 40 cm to dampen vibration between units B Foamed polyethylene insulation for copper pipes as required to precise length of piping Wall thickness of the insulati...

Страница 4: ... noise 5 Provide the space shown in Fig 2 so that the air flow is not blocked Also for efficient operation leave open three of the four direc tions front rear and both sides WARNING Install at a place that can withstand the weight of the indoor and outdoor units and install positively so that the units will not topple or fall CAUTION 1 Do not install where there is the danger of com bustible gas l...

Страница 5: ...e is not used the cord interconnecting the indoor and outdoor units may touch metal and cause electric leakage CAUTION Install the wall hook bracket horizontally and perpen dicularly Fig 2 Wall hook bracket Tapping screw Center notch String Rear piping Right piping Bottom piping Install the indoor unit piping in the direction of the wall hole and bind the drain hose and pipe together with vinyl ta...

Страница 6: ...ut Indoor unit pipe Connection pipe To prevent gas leakage coat the flare surface with refrigerator oil BENDING PIPES The pipes are shaped by your hands Be careful not to collapse them Do not bend the pipes in an angle more than 90 When pipes are repeatedly bent or stretched the material will harden making it difficult to bend or stretch them any more Do not bend or stretch the pipes more than thr...

Страница 7: ...ecurely 10 Fully open the valve stems of the 2 way valve and 3 way valve using a hexagon wrench After the valve stem begins to turn turn it with a torque of less than 2 17ft lbs 30 kgf cm until it stops turning 11 Firmly tighten the 2 way valve and 3 way valve blank cap and the charging port cap Fig 9 Tapping screw Rear hook Connector cover Always use the screws as shown above Do not select the to...

Страница 8: ...st Therefore be sure all wiring is tightly connected Connect wires to the matching numbers of terminals NOTE Connector trade size for this unit is 1 2 12 7 mm The connec tor can be bought at a hardware store Refer to How to connect wiring to the terminals for instructions on connecting depend ing on the wire type you are using The fuse located in the outdoor unit provides power supply pro tection ...

Страница 9: ...to the terminal Refer to the wiring diagram 3 Use the screws to install the cord clamp Connection cord Screw Cord clamp There is a terminal block inside Connection cord Screw Cord clamp A For solid core wiring or F cable 1 Cut the wire end with a wire cutter or wire cutting pliers then strip the insulation to about 15 16 25 mm to expose the solid wire 2 Using a screwdriver remove the terminal scre...

Страница 10: ...ape Pipe Drain hose Cloth tape Wrap with cloth tape Wall Check the following View from indoors Left piping Connection cord Pipe Drain hose GOOD Lifted up Saddle Wave End in water BAD Drain hose BAD BAD For connection from the left rear Connection cord Drain hose Wall pipe Connection pipe FRONT PANEL REMOVAL AND INSTALLATION THE INTAKE GRILLE REMOVAL 1 Open the intake grille 2 Pull down the knob 3 ...

Страница 11: ... button on the remote control unit while the air conditioner is running use a melallic object to short the two metal contacts under the battery compartment lid and send the TEST RUN sig nal from the remote control unit To end test operation press the remote control unit START STOP button When the air conditioner is run by pressing the test run button the OP ERATION indicator lamp and TIMER indicat...

Страница 12: ...er unit wire harness to the terminal correctly please refer to fig 20 to adjust the length of the part of Inter unit Wire har ness ahead from conduit holder 5 1 2 140mm 15 16 25mm 15 16 25mm 4 3 16 105mm 1 1 14AWG EARTH WIRE CONDUIT PLATE CONDUIT CONNECTOR Fig 20 ...

Страница 13: ...ting the cooling operation by the remote control unit Refer to TEST RUNNING The operation indicator lamp and timer indicator lamp will begin to flash simultaneously during test run 4 Close the valve stem of 3 way valve when the reading on the compound pressure gage becomes 0 05 0 Mpa 0 5 0 kg cm2 5 Stop the operation Press the START STOP button of the remote control unit to stop the operation CAUT...

Отзывы: