ERROR STATUS OUTPUT
An air conditioner error status signal can be output.
Circuit diagram example
z
* Make the distance from the PC board to the connected unit within 10m.
Relay spec. : Max.24VDC, 10mA to less than 500mA.
Field supply
Optional parts
Ex.)Display
Indoor
control PC board Communication kit
Connected unit
Ex.)Relay unit
1
2
Signal
Relay
power
supply
V
Connector
24V DC
*33ft. (10m)
ON
OFF
Error
Normal
Error status
Output signal
Parts (Optional)
z
Parts name
Model name
External connect kit
UTY-XWZXZ5
Communication kit
UTY-TWBXF
* For operating the EXTERNAL function, the wall mounted type requires the communication kit in addition to the wire
(UTY-XWZXZ5).
Wire (External output) : UTY-XWZXZ5
Содержание Halcyon AOU9RLS2
Страница 2: ...1 INDOOR UNIT WALL MOUNTED TYPE ASU9RLS2 ASU12RLS2 ASU15RLS2 DTR_AS059E_01 2011 12 20 ...
Страница 33: ...2 OUTDOOR UNIT SINGLE TYPE AOU9RLS2 AOU12RLS2 AOU15RLS2 DTR_AO103E_01 2011 12 20 ...
Страница 38: ... 02 04 OUTDOOR UNIT AOU9 15RLS2 OUTDOOR UNIT AOU9 15RLS2 WIRING DIAGRAMS 444 MODEL AOU9RLS2 AOU12RLS2 ...
Страница 39: ... 02 05 OUTDOOR UNIT AOU9 15RLS2 OUTDOOR UNIT AOU9 15RLS2 MODEL AOU15RLS2 ...
Страница 46: ... 02 12 OUTDOOR UNIT AOU9 15RLS2 OUTDOOR UNIT AOU9 15RLS2 SOUND LEVEL CHECK POINT 88888 39 3 8in 1m ...