36
9.0 DIAGNOSTICS & TROUBLESHOOTING
9.1 Defrost Control Diagnostic Codes
9.2 Outdoor Ambient and Coil Sensor
Temperature vs. Resistance Table
LED 1
LED 2
Control Board Status
OFF
OFF
No Power
ON
ON
Coil Sensor Failure
OFF
ON
Ambient Sensor Failure
FLASH
FLASH
Normal
OFF
FLASH
Low Pressure Lockout (short test pins to reset)
FLASH
OFF
High Pressure Lockout (short test pins to reset)
ON
FLASH
Low Pressure Control Open
FLASH
O
ON
OFF
N
H
In Defrost Mode
igh Pressure Control Open
Alternate Flashing
5 Minute Time Delay
Degrees C
Degrees F
Ohms
-20
-4
96,974
-10
14
55,298
0
32
32,650
10
50
19,903
20
68
12,493
25
77
10,000
30
86
8,056
40
104
5,324
Diagnostics