CHAPTER 3
Small Configuration
Installing Power, Ground, and Alarm Cables
FNC-7500-0061-200
Issue 1, May 2009
FLASHWAVE 7500 Release 6.1
Equipment Installation
3-84
Fujitsu and Fujitsu Customer Use Only
3.16
Installing Power,
G
round, and Alarm Cables
This procedure provides instructions for installing power, ground, and alarm cabling for
standard rack configurations.
N
O
.
S
UBPROCEDURE
P
A
G
E
It includes the following subprocedures:
P
r
o
c
e
d
u
r
e
3.16.1
Reference Material
This subsection describes instructions for installing power, ground, and alarm cabling for
23-inch rack configurations. Fujitsu does not manufacture a 19-inch CBP. For 19-inch rack
applications, Fujitsu recommends using the N215116-N/L31 fuse panel manufactured by
Noran Tel Ltd. Refer to Noran Tel documentation for installation instructions for the
N215116-N/L31 fuse panel. This unit can be ordered through Fujitsu using part number
06-331-444.
The cables and cable harnesses used are listed in
and shown in
.
Note:
Connections to the shelf power terminal strip should use copper conductors only.
show schematics for installing power, ground,
and alarm cabling between the rack, shelves and CBP for the following standard rack
configurations:
■
Rack with one Universal shelf (
■
Rack with two Universal shelves (
)
■
Rack with three Universal shelves (
Each standard rack configuration includes a circuit breaker panel (CBP) with power terminals
as shown in
. The circuit breakers within the CBP are associated with
shelves as shown in
.
shows the Optical/Tributary shelf backplane.
shows the power cabling.
shows the rack alarm cable harness, which gets wire wrapped to the
CBP. Connectors along this harness mate to shelf alarm cables (
) that
plug into alarm ports on the shelf backplane.