CHAPTER 3
Small Configuration
Installing the 23-Inch (FC9682HSW2) Heat Baffle
3-45
FLASHWAVE 7500 Release 6.1
Equipment Installation
Fujitsu and Fujitsu Customer Use Only
FNC-7500-0061-200
Issue 1, May 2009
3.9
Installing the 23-Inch (FC9682HSW2) Heat Baffle
When used, the heat baffle is positioned directly above or beneath an Optical or Tributary
shelf (see
). If it is positioned above the shelf, as
shown in
, the heat baffle ensures that air pushed upward through the
shelf is deflected to the rear of the rack. If it is positioned under the shelf, the heat baffle
ensures that air entering from below comes from the front of the rack.
Figure 3-29: Typical Shelf Mounting with Heat Baffle
(Small Configuration)
7"
4"
3"
4"
Heat Baffle
m1
65
6m
i_
3
Revision 1, June 2009
Содержание FLASHWAVE 7500
Страница 8: ...Revision 1 June 2009 ...
Страница 10: ...Revision 1 June 2009 ...
Страница 16: ...Revision 1 June 2009 ...
Страница 362: ...Revision 1 June 2009 ...
Страница 386: ...Revision 1 June 2009 ...