CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND
51
HEIGHT DIFFERENCE
MODEL : AO
■
Z14LB , AO
Z18LB
COOLING
Pipe length (m)
5
7.5
10
15
20
Height difference H
(m)
1
Indoor unit is upper
than outdoor unit.
15
―
―
―
0.953
0.951
10
―
―
0.981
0.969
0.967
7.5
―
0.988
0.985
0.973
0.971
5
0.994
0.992
0.989
0.977
0.975
0
1.002
1.000
0.997
0.984
0.983
2
Indoor unit is under
than outdoor unit
-5
1.002
1.000
0.997
0.984
0.983
-7.5
―
1.000
0.997
0.984
0.983
-10
―
―
0.997
0.984
0.983
-15
―
―
―
0.984
0.983
HEATING
Pipe length (m)
5
7.5
10
15
20
Height difference H
(m)
1
Indoor unit is upper
than outdoor unit.
15
―
―
―
0.946
0.923
10
―
―
0.987
0.946
0.923
7.5
―
1.000
0.987
0.946
0.923
5
1.008
1.000
0.987
0.946
0.923
0
1.008
1.000
0.987
0.946
0.923
2
Indoor unit is under
than outdoor unit
-5
1.003
0.995
0.982
0.941
0.918
-7.5
―
0.993
0.979
0.939
0.916
-10
―
―
0.977
0.936
0.913
-15
―
―
―
0.927
0.904
Indoor unit
Height difference H
Connection pipe
H
Outdoor unit
Indoor unit
Connection pipe
H
Outdoor unit
Indoor unit is upper than outdoor unit.
1
Indoor unit is under than outdoor unit.
2