En-5

2.4. Pipe requirement

Model

Gas pipe size (thickness) [mm]

Luquid pipe size (thickness) [mm]

07, 09, 12, 14

Ø 9.52 (0.80)

Ø 6.35 (0.80)

18, 22, 24

Ø 12.70 (0.80)

Ø 6.35 (0.80)

 CAUTION

Refer to the installation manual for the outdoor unit for description of allowable pipe 
length and height difference.

•  Use pipe with water-resistant heat insulation.

 CAUTION

•  Wrap heat insulation around both gas pipe and liquid pipe.  

No heat-insulation work or incorrect heat-insulation work may cause water leaks.

•  In a reverse cycle model, use heat insulation with heat resistance above 120 °C.
•  If expected humidity of the installation location of refrigerant pipes is higher than 

70 %, wrap the heat insulation around the refrigerant pipes. 
If the expected humidity is between 70 % and 80 %, use heat insulation that has 
a thickness of 15 mm or more. 
If the expected humidity is higher than 80 %, use heat insulation that has a thickness 
of 20 mm or more.

•  The use of thinner heat insulation than speci

fi

 ed above, may cause a condensation 

on the surface of the insulation.  

•  Use heat insulation with thermal conductivity of 0.045 W/(m•K) or less, at 20 °C.

 2.5. Electrical requirement

The indoor unit is powered from the outdoor unit. Do not power indoor unit from separate 
power source.

 WARNING

Standard for electrical wiring and equipment differs in each country or region. Before you 
start electrical working, con

fi

 rm related regulations, codes, or standards.

Cable

Conductor size [

mm

2

]

Type

Remarks

Connection cable

1.5 (Min)

Type 60245 IEC 57

3 cable + Earth (Ground), 

1 Ø 230 V

Cable Length:  Limit voltage drop to less than 2%. Increase cable gauge if voltage drop is 

2% or more.

2.6. Optional parts

Refer to each installation manual for the method of installing optional parts.

Wired remote controller (*1)

UTY-RNR*Z*

For air conditioner operation
(2-wired type)

UTY-RLR*

UTY-RVN*M

For air conditioner operation
(3-wired type)

UTY-RNN*M

Wireless remote controller

UTY-LNT*

For air conditioner operation

Fresh air intake kit

UTZ-VZAA

To take fresh air

Air outlet shutter plate

UTR-YDZB

Install the plate at outlet when carrying 
out 3-way direction operation

Insulation kit for High hu-
midity

UTZ-KXGC

Install when the condition under the roof 
is over 80% in humidity and over 30°C in 
temperature.

External connect kit

PCB terminal

For control input port

UTY-XWZXZG For control output port

W-LAN interface

UTY-TFSXZ1

For wireless LAN control

*1: Wired remote controller is recommended using simultaneous twin or triple connection.

3. INSTALLATION WORK

 WARNING

Do not move the appliance by holding the indoor unit pipes. 
(The stress applied to the pipe joints may cause the 

fl

 ammable gas to leak during 

operation.)

Especially, the installation place is very important for the split type air conditioner because 
it is very dif

fi

 cult to move from place to place after the 

fi

 rst installation.

 3.1. Selecting an installation location

 WARNING

Select installation locations that can properly support the weight of the indoor unit. 
Install the units securely so that they do not topple or fall.

 CAUTION

•  Do not install the unit in the following areas:

-  Area with high salt content, such as at the seaside. It will deteriorate metal parts, 

causing the parts to fail or the unit to leak water.

-  Area 

fi

 lled with mineral oil or containing a large amount of splashed oil or steam, 

such as a kitchen. It will deteriorate plastic parts, causing the parts to fail or the 
unit to leak water. 

-  Area where is close to heat sources. 
-  Area that generates substances that adversely affect the equipment, such as 

sulfuric gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed 
joints to corrode, which can cause refrigerant leakage.

-  Area that can cause combustible gas to leak, contains suspended carbon 

fi

 bers or 

fl

 ammable dust, or volatile in 

fl

 ammables such as paint thinner or gasoline.

-  If gas leaks and settles around the unit, it can cause a 

fi

 re.

-  Area where animals may urinate on the unit or ammonia may be generated.

•   Do not use the unit for special purposes, such as storing food, raising animals, grow-

ing plants, or preserving precision devices or art objects. It can degrade the quality 
of the preserved or stored objects.

•  Install the unit where drainage does not cause any trouble.
•  Do not install where there is the danger of combustible gas leakage.
•  Do not install the unit near a source of heat, steam, or 

fl

 ammable gas.

•  Install the indoor unit, outdoor unit, power supply cable, transmission cable, and 

remote control cable at least 1 m away from a television or radio receivers. The 
purpose of this is to prevent TV reception interference or radio noise.
(Even if they are installed more than 1 m apart, you could still receive noise under 
some signal conditions.)

•  If children under 10 years old may approach the unit, take preventive measures so 

that they cannot reach the unit.

•  Use the “Insulation kit for high humidity” (option), when the condition under the roof 

is over 80% in humidity and over 30°C in temperature. Otherwise, there is a risk of 
condensation on the ceiling.

Decide the mounting position together with the customer as follows:
(1)  Install the indoor unit in a location having suf

fi

 cient strength to support the weight of 

the indoor unit.

(2)  The inlet and outlet ports should not be obstructed; the air should be able to blow all 

over the room.

(3) Leave the space required to service the air conditioner.
(4) Locate where the air can be distributed evenly throughout the room by the unit.
(5) Install the unit where connection to the outdoor unit is easy. 
(6) Install the unit where the connection pipe can be easily installed. 
(7) Install the unit where the drain pipe can be easily installed.
(8) Install the unit where noise and vibration is not ampli

fi

 ed. 

(9)  Take servicing, etc., into consideration and leave the spaces. Also install the unit 

where the 

fi

 lter can be removed.

 3.2. Installation dimensions

• The ceiling rear height as shown in the 

fi

 gure.

Strong and durable ceiling

262 or 
more 

1,000 or 
more 

1,800 or 

more 

1,000 or 

more 

(Unit: mm)

Floor

Obstruction

•  This product can be installed at a height of up to 3,000mm.

However, 7000, 9000 Btu/h model can not be installed in high places.

Perform the Function Setting on the remote control in accordance with the installed height. 
(Refer to “7. FUNCTION SETTING”)

9379124119-03_IM.indb   5

9379124119-03_IM.indb   5

2019/2/22   16:51:37

2019/2/22   16:51:37

Содержание AUXG-KVLA Series

Страница 1: ...is not explosion proof and therefore should not be installed in an explo sive atmosphere To avoid getting an electric shock never touch the electrical components soon after the power supply has been turned off After turning off the power always wait 5 min utes or more before you touch the electrical components This product contains no user serviceable parts Always consult experienced service techn...

Страница 2: ...m which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion All possible ignition sources including cigarette smoking should be kept sufficiently far away from the site of installation repairing removing and disposal during which flammable refrigerant can possibly b...

Страница 3: ...the system it shall be pressure tested with OFN The system shall be leak tested on completion of charging but prior to commission ing A follow up leak test shall be carried out prior to leaving the site CAUTION 10 Decommissioning Before carrying out this procedure it is essential that the technician is completely familiar with the equipment and all its details It is recommended good practice that ...

Страница 4: ...ir or ap plication of unspecified material makes the internal pressure of the refrigerant cycle too high and may cause product malfunction burst of piping or injury For installation purposes be sure to use the parts supplied by the manufacturer or other prescribed parts The use of non prescribed parts can cause serious accidents such as the unit falling water leakage electric shock or fire Do not ...

Страница 5: ...he following areas Area with high salt content such as at the seaside It will deteriorate metal parts causing the parts to fail or the unit to leak water Area filled with mineral oil or containing a large amount of splashed oil or steam such as a kitchen It will deteriorate plastic parts causing the parts to fail or the unit to leak water Area where is close to heat sources Area that generates sub...

Страница 6: ...ks onto the hanging bolt between the special nuts 3 Turn special nut B to adjust the height of the body WARNING Perform final tightening by tightening the double nut firmly Be sure to install the body horizontally and adjust the height below the body and the ceiling surface properly Special nut A accessories After installing the body tighten the nuts Hook Ceiling Unit mm 30 or more Special nut B a...

Страница 7: ...1 9 52 3 8 13 2 12 70 1 2 16 6 15 88 5 8 19 7 19 05 3 4 24 0 When using conventional flare tools to flare R32 pipes the dimension A should be approx imately 0 5 mm more than indicated in the table for flaring with R32 flare tools to achieve the specified flaring Use a thickness gauge to measure the dimension A Width across flats Pipe outside diameter mm in Width across flats of Flare nut mm 6 35 1...

Страница 8: ...he electrical box cover on the unit An improperly installed electrical box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Install sleeves into any holes made in the walls for wiring Otherwise a short circuit could result Use the included connection cables and power cables or ones specified by the manufacturer Improper connections insufficient ins...

Страница 9: ...f it has a earth ground line Wired remote controller Wired remote controller UNIT A UNIT B Simultaneous twin 18 model only Connection cable Indoor unit Primary Outdoor unit Indoor unit Primary Indoor unit Secondary Indoor unit Secondary Junction box Locally purchased Earth Ground line Control line Power line Earth Ground line Wired remote controller cable 3 wire type only Wired remote controller R...

Страница 10: ...amp the ring terminals to the wires by using an appropriate tool so that the wires do not come loose Strip 10 mm Ring terminal Sleeve 3 Connect specified wires securely and fasten them so that there is no stress applied on the terminals 4 Use a screwdriver with an appropriate bit size to tighten the terminal screws Using of screwdriver with inappropriate bit size will damage the screw heads and th...

Страница 11: ...e outlet or other gaps with putty to prevent dew condensation or insect from entering the electric control box 5 Replace the control box cover CAUTION Do not bundle the remote controller cable or wire the remote controller cable in paral lel with the indoor unit connection wire to the outdoor unit and the power supply cable It may cause erroneous operation 3 7 Remote controller setting To install ...

Страница 12: ... Function No 60 in 7 FUNCTION SET TING 2 Other options WLAN adapter converters etc may be connectable Please refer to the technical data for details NOTES Options connecting to CN47 or CN65 cannot be used at the same time 5 2 External input and output 5 2 1 External input Indoor unit functions such as Operation Stop or Forced stop can be done by using indoor unit terminals Operation Stop mode or F...

Страница 13: ...to 5 4 Other optional parts 5 3 Remote sensor Optional parts 5 3 1 Connection method Remove the existing connector and replace it with the remote sensor connector ensure that the correct connector is used The original connector should be insulated to ensure that it does not come into contact with other electrical circuitry Connection terminals and wiring arrangement Refer to 5 4 Other optional par...

Страница 14: ...e both the indoor unit and the remote controller For details please refer to the remote controller installation manual b 3 wire type DIP switch RC AD SW Factory setting 00 When connecting multiple indoor units to 1 standard wired remote controller set the address at RC AD SW in sequence from 00 Setting Setting range Switch 100 Remote controller address 00 to 15 Setting example 00 1 2 3 4 ON RC AD ...

Страница 15: ...an be used to operate the indoor units CAUTION Multiple installation method described above is prohibited to combine 3 Wired type with 2 Wired Type A I U A B I U Master Master Slave A B Remote controller cable Refer to 2 5 Electrical requirement A 500 m A B 500 m The timer and self diagnosis functions cannot be used on the secondary units 1 Wiring method indoor unit to remote controller Remote con...

Страница 16: ...AUTION Confirm whether the wiring work for outdoor unit has been finished Confirm that the cover for the electrical enclosure on the outdoor unit is in place This procedure changes to the Function settings used to control the indoor unit according to the installation conditions Incorrect settings can cause the indoor unit to malfunction After the power is turned on perform the Function setting acc...

Страница 17: ...or unit 01 Both 00 Sensor on the indoor unit is active 01 Sensors on both indoor unit and wired remote controller are active Remote controller sensor must be turned on by using the remote controller Remote controller custom code Only for wireless remote controller The indoor unit custom code can be changed Select the appropriate custom code Factory setting Function number Setting value Setting des...

Страница 18: ...ll begin in a few minutes when HEAT is selected by the remote control ler reverse cycle model only 10 FINISHING 10 1 Installing heat insulation CAUTION After checking for gas leaks refer to the Installation Manual of the outdoor unit perform this section Install heat insulation around both the large gas and small liquid pipes Failure to do so may cause water leaks Must fit tightly against body wit...

Страница 19: ... 7 1 Discharge temp sensor error 7 2 Compressor temp sensor error 7 3 Outdoor unit Heat Ex liquid temp sensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error 7 6 2 way valve temp sensor error 3 way valve temp sensor error 7 7 Heat sink temp sensor error 8 2 Sub cool Heat Ex gas inlet temp sensor error Sub cool Heat Ex gas outlet temp sensor error 8 3 Liquid pipe temp sensor e...

Отзывы: