Fujitsu AUXG-KVLA Series Скачать руководство пользователя страница 3

En-3

 CAUTION

4-Repair to intrinsically safe components

•  Do not apply any permanent inductive or capacitance loads to the circuit without 

ensuring that this will not exceed the permissible voltage and current permitted for 
the equipment in use.

•  Intrinsically safe components are the only types that can be worked on while live in 

the presence of a 

fl

 ammable atmosphere. 

•  The test apparatus shall be at the correct rating.
•  Replace components only with parts speci

fi

 ed by the manufacturer.

•  Other parts may result in the ignition of refrigerant in the atmosphere from a leak.

5-Cabling

•  Check that cabling will not be subject to wear, corrosion, excessive pressure, vibra-

tion, sharp edges or any other adverse environmental effects.

•  The check shall also take into account the effects of aging or continual vibration from 

sources such as compressors or fans.

6-Detection of 

fl

 ammable refrigerants

•  Under no circumstances shall potential sources of ignition be used in the searching 

for or detection of refrigerant leaks.

•  A halide torch (or any other detector using a naked 

fl

 ame) shall not be used.

7-Leak detection methods

•  Electronic leak detectors shall be used to detect 

fl

 ammable refrigerants, but the 

sensitivity may not be adequate, or may need re-calibration. (Detection equipment 
shall be calibrated in a refrigerant-free area.)

•  Ensure that the detector is not a potential source of ignition and is suitable for the 

refrigerant used.

•  Leak detection equipment shall be set at a percentage of the LFL of the refrigerant 

and shall be calibrated to the refrigerant employed and the appropriate percentage 
of gas (25 % maximum) is con

fi

 rmed.

• Leak detection 

fl

 uids are suitable for use with most refrigerants but the use of 

detergents containing chlorine shall be avoided as the chlorine may react with the 
refrigerant and corrode the copper pipe-work.

•  If a leak is suspected, all naked 

fl

 ames shall be removed/extinguished.

•  If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall 

be recovered from the system, or isolated (by means of shut off valves) in a part of 
the system remote from the leak. 
Oxygen free nitrogen (OFN) shall then be purged through the system both before 
and during the brazing process.

8-Removal and evacuation

•  When breaking into the refrigerant circuit to make repairs – or for any other 

purpose –conventional procedures shall be used. 
However, it is important that best practice is followed since 

fl

 ammability is a consid-

eration. 
The following procedure shall be adhered to:

• remove refrigerant
•  purge the circuit with inert gas
• evacuate
•  purge again with inert gas
•  open the circuit by cutting or brazing

•  The refrigerant charge shall be recovered into the correct recovery cylinders. 
•  The system shall be “

fl

 ushed” with OFN to render the unit safe. 

•  This process may need to be repeated several times. 
•  Compressed air or oxygen shall not be used for this task.
•  Flushing shall be achieved by breaking the vacuum in the system with OFN and 

continuing to 

fi

 ll until the working pressure is achieved, then venting to atmosphere, 

and 

fi

 nally pulling down to a vacuum. 

•  This process shall be repeated until no refrigerant is within the system. 
• When the 

fi

 nal OFN charge is used, the system shall be vented down to atmospheric 

pressure to enable work to take place.

•  This operation is absolutely vital if brazing operations on the pipe work are to take 

place.

•  Ensure that the outlet for the vacuum pump is not close to any ignition sources and 

there is ventilation available.

9-Charging procedures

•  In addition to conventional charging procedures, the following requirements shall be 

followed.

-  Ensure that contamination of different refrigerants does not occur when using 

charging equipment. 
 Hoses or lines shall be as short as possible to minimize the amount of refrigerant 
contained in them.

-  Cylinders shall be kept upright.
-  Ensure that the refrigeration system is earthed prior to charging the system with 

refrigerant.

-  Label the system when charging is complete (if not already).
-  Extreme care shall be taken not to over

fi

 ll the refrigeration system.

•  Prior to recharging the system it shall be pressure tested with OFN. 
•  The system shall be leak tested on completion of charging but prior to commission-

ing. 

•  A follow up leak test shall be carried out prior to leaving the site.

 CAUTION

10-Decommissioning

•  Before carrying out this procedure, it is essential that the technician is completely 

familiar with the equipment and all its details.

•  It is recommended good practice that all refrigerants are recovered safely.
•  Prior to the task being carried out, an oil and refrigerant sample shall be taken in 

case analysis is required prior to re-use of reclaimed refrigerant.

•  It is essential that electrical power is available before the task is commenced.

a)  Become familiar with the equipment and its operation.
b)  Isolate system electrically.
c)  Before attempting the procedure ensure that:

•  mechanical handling equipment is available, if required, for handling refriger-

ant cylinders;

•  all personal protective equipment is available and being used correctly; 
•  the recovery process is supervised at all times by a competent person; 
•  recovery equipment and cylinders conform to the appropriate standards.

d)  Pump down refrigerant system, if possible.
e)  If a vacuum is not possible, make a manifold so that refrigerant can be removed 

from various parts of the system.

f)   Make sure that cylinder is situated on the scales before recovery takes place.
g)  Start the recovery machine and operate in accordance with manufacturer’s 

instructions.

h)  Do not over

fi

 ll cylinders. (No more than 80 % volume liquid charge).

i)   Do not exceed the maximum working pressure of the cylinder, even temporarily.
j)   When the cylinders have been 

fi

 lled correctly and the process completed, make 

sure that the cylinders and the equipment are removed from site promptly and all 
isolation valves on the equipment are closed off.

k)  Recovered refrigerant shall not be charged into another refrigeration system un-

less it has been cleaned and checked.

11-Labelling

•  Equipment shall be labelled stating that it has been de-commissioned and emptied 

of refrigerant. 

•  The label shall be dated and signed. 
•  Ensure that there are labels on the equipment stating the equipment contains 

fl

 am-

mable refrigerant.

12-Recovery

•  When removing refrigerant from a system, either for servicing or decommissioning, it 

is recommended good practice that all refrigerants are removed safely.

•  When transferring refrigerant into cylinders, ensure that only appropriate refrigerant 

recovery cylinders are employed.

•  Ensure that the correct number of cylinders for holding the total system charge are 

available. 

•  All cylinders to be used are designated for the recovered refrigerant and labelled for 

that refrigerant (i.e. special cylinders for the recovery of refrigerant). 

•  Cylinders shall be complete with pressure relief valve and associated shut-off valves 

in good working order.

•  Empty recovery cylinders are evacuated and, if possible, cooled before recovery 

occurs.

•  The recovery equipment shall be in good working order with a set of instructions 

concerning the equipment that is at hand and shall be suitable for the recovery of 

fl

 ammable refrigerants.

•  In addition, a set of calibrated weighing scales shall be available and in good working 

order.

•  Hoses shall be complete with leak-free disconnect couplings and in good condition.
•  Before using the recovery machine, check that it is in satisfactory working order, has 

been properly maintained and that any associated electrical components are sealed 
to prevent ignition in the event of a refrigerant release. 
Consult manufacturer if in doubt.

•  The recovered refrigerant shall be returned to the refrigerant supplier in the correct 

recovery cylinder, and the relevant Waste Transfer Note arranged. 

•  Do not mix refrigerants in recovery units and especially not in cylinders.
•  If compressors or compressor oils are to be removed, ensure that they have been 

evacuated to an acceptable level to make certain that 

fl

 ammable refrigerant does not 

remain within the lubricant. 

•  The evacuation process shall be carried out prior to returning the compressor to the 

suppliers. 

•  Only electric heating to the compressor body shall be employed to accelerate this 

process. 

•  When oil is drained from a system, it shall be carried out safely.

9379124119-03_IM.indb   3

9379124119-03_IM.indb   3

2019/2/22   16:51:36

2019/2/22   16:51:36

Содержание AUXG-KVLA Series

Страница 1: ...is not explosion proof and therefore should not be installed in an explo sive atmosphere To avoid getting an electric shock never touch the electrical components soon after the power supply has been turned off After turning off the power always wait 5 min utes or more before you touch the electrical components This product contains no user serviceable parts Always consult experienced service techn...

Страница 2: ...m which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion All possible ignition sources including cigarette smoking should be kept sufficiently far away from the site of installation repairing removing and disposal during which flammable refrigerant can possibly b...

Страница 3: ...the system it shall be pressure tested with OFN The system shall be leak tested on completion of charging but prior to commission ing A follow up leak test shall be carried out prior to leaving the site CAUTION 10 Decommissioning Before carrying out this procedure it is essential that the technician is completely familiar with the equipment and all its details It is recommended good practice that ...

Страница 4: ...ir or ap plication of unspecified material makes the internal pressure of the refrigerant cycle too high and may cause product malfunction burst of piping or injury For installation purposes be sure to use the parts supplied by the manufacturer or other prescribed parts The use of non prescribed parts can cause serious accidents such as the unit falling water leakage electric shock or fire Do not ...

Страница 5: ...he following areas Area with high salt content such as at the seaside It will deteriorate metal parts causing the parts to fail or the unit to leak water Area filled with mineral oil or containing a large amount of splashed oil or steam such as a kitchen It will deteriorate plastic parts causing the parts to fail or the unit to leak water Area where is close to heat sources Area that generates sub...

Страница 6: ...ks onto the hanging bolt between the special nuts 3 Turn special nut B to adjust the height of the body WARNING Perform final tightening by tightening the double nut firmly Be sure to install the body horizontally and adjust the height below the body and the ceiling surface properly Special nut A accessories After installing the body tighten the nuts Hook Ceiling Unit mm 30 or more Special nut B a...

Страница 7: ...1 9 52 3 8 13 2 12 70 1 2 16 6 15 88 5 8 19 7 19 05 3 4 24 0 When using conventional flare tools to flare R32 pipes the dimension A should be approx imately 0 5 mm more than indicated in the table for flaring with R32 flare tools to achieve the specified flaring Use a thickness gauge to measure the dimension A Width across flats Pipe outside diameter mm in Width across flats of Flare nut mm 6 35 1...

Страница 8: ...he electrical box cover on the unit An improperly installed electrical box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Install sleeves into any holes made in the walls for wiring Otherwise a short circuit could result Use the included connection cables and power cables or ones specified by the manufacturer Improper connections insufficient ins...

Страница 9: ...f it has a earth ground line Wired remote controller Wired remote controller UNIT A UNIT B Simultaneous twin 18 model only Connection cable Indoor unit Primary Outdoor unit Indoor unit Primary Indoor unit Secondary Indoor unit Secondary Junction box Locally purchased Earth Ground line Control line Power line Earth Ground line Wired remote controller cable 3 wire type only Wired remote controller R...

Страница 10: ...amp the ring terminals to the wires by using an appropriate tool so that the wires do not come loose Strip 10 mm Ring terminal Sleeve 3 Connect specified wires securely and fasten them so that there is no stress applied on the terminals 4 Use a screwdriver with an appropriate bit size to tighten the terminal screws Using of screwdriver with inappropriate bit size will damage the screw heads and th...

Страница 11: ...e outlet or other gaps with putty to prevent dew condensation or insect from entering the electric control box 5 Replace the control box cover CAUTION Do not bundle the remote controller cable or wire the remote controller cable in paral lel with the indoor unit connection wire to the outdoor unit and the power supply cable It may cause erroneous operation 3 7 Remote controller setting To install ...

Страница 12: ... Function No 60 in 7 FUNCTION SET TING 2 Other options WLAN adapter converters etc may be connectable Please refer to the technical data for details NOTES Options connecting to CN47 or CN65 cannot be used at the same time 5 2 External input and output 5 2 1 External input Indoor unit functions such as Operation Stop or Forced stop can be done by using indoor unit terminals Operation Stop mode or F...

Страница 13: ...to 5 4 Other optional parts 5 3 Remote sensor Optional parts 5 3 1 Connection method Remove the existing connector and replace it with the remote sensor connector ensure that the correct connector is used The original connector should be insulated to ensure that it does not come into contact with other electrical circuitry Connection terminals and wiring arrangement Refer to 5 4 Other optional par...

Страница 14: ...e both the indoor unit and the remote controller For details please refer to the remote controller installation manual b 3 wire type DIP switch RC AD SW Factory setting 00 When connecting multiple indoor units to 1 standard wired remote controller set the address at RC AD SW in sequence from 00 Setting Setting range Switch 100 Remote controller address 00 to 15 Setting example 00 1 2 3 4 ON RC AD ...

Страница 15: ...an be used to operate the indoor units CAUTION Multiple installation method described above is prohibited to combine 3 Wired type with 2 Wired Type A I U A B I U Master Master Slave A B Remote controller cable Refer to 2 5 Electrical requirement A 500 m A B 500 m The timer and self diagnosis functions cannot be used on the secondary units 1 Wiring method indoor unit to remote controller Remote con...

Страница 16: ...AUTION Confirm whether the wiring work for outdoor unit has been finished Confirm that the cover for the electrical enclosure on the outdoor unit is in place This procedure changes to the Function settings used to control the indoor unit according to the installation conditions Incorrect settings can cause the indoor unit to malfunction After the power is turned on perform the Function setting acc...

Страница 17: ...or unit 01 Both 00 Sensor on the indoor unit is active 01 Sensors on both indoor unit and wired remote controller are active Remote controller sensor must be turned on by using the remote controller Remote controller custom code Only for wireless remote controller The indoor unit custom code can be changed Select the appropriate custom code Factory setting Function number Setting value Setting des...

Страница 18: ...ll begin in a few minutes when HEAT is selected by the remote control ler reverse cycle model only 10 FINISHING 10 1 Installing heat insulation CAUTION After checking for gas leaks refer to the Installation Manual of the outdoor unit perform this section Install heat insulation around both the large gas and small liquid pipes Failure to do so may cause water leaks Must fit tightly against body wit...

Страница 19: ... 7 1 Discharge temp sensor error 7 2 Compressor temp sensor error 7 3 Outdoor unit Heat Ex liquid temp sensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error 7 6 2 way valve temp sensor error 3 way valve temp sensor error 7 7 Heat sink temp sensor error 8 2 Sub cool Heat Ex gas inlet temp sensor error Sub cool Heat Ex gas outlet temp sensor error 8 3 Liquid pipe temp sensor e...

Отзывы: