En-3
Decide the mounting position with the customer as follows:
(1) Install the indoor unit on a place having a suf
fi
cient strength so that it withstands
against the weight of the indoor unit.
(2) The inlet and outlet ports should not be obstructed; the air should be able to blow all
over the room.
(3) Leave the space required to service the air conditioner.
(4) A place from where the air can be distributed evenly throughout the room by the unit.
(5) Install the unit where connection to the outdoor unit (or RB unit) is easy.
(6) Install the unit where the connection pipe can be easily installed.
(7) Install the unit where the drain pipe can be easily installed.
(8) Install the unit where noise and vibrations are not ampli
fi
ed.
(9) Take servicing, etc., into consideration and leave the spaces. Also install the unit
where the
fi
lter can be removed.
3.2. Installation dimensions
• Leave the space speci
fi
ed in Fig. A so that the air from the blower will cover the entire
room.
• Install the indoor unit on a place having a suf
fi
cient strength so that it withstands
against the weight of the indoor unit.
• A place from where drainage can be extracted outdoors easily.
WARNING
Never install in a room where there is the potential of leaking
fl
ammable gas. A spark
could ignite the gas and cause an explosion or
fi
re.
Avoid installing in a location with high temperature.
• The blower direction can be set for 2 directions or 3 directions. When using 2-direction
or 3-direction blower, follow Fig. B for the blower direction and space.
• This product can be installed at a height of up to 3.0 m. Perform the Function Setting
on the remote controller in accordance with the installed height.
Fig. A
Obstruction
H
1,800mm or more
1,000 mm
or more
1,000 mm
or more
Floor
Strong and durable ceiling
262 mm
or more
H (The maximum height from floor to ceiling) (mm)
Model name
AUXB07
AUXB09
AUXB12
AUXB14
AUXB18
AUXB24
Standard mode
2,700
2,700
2,700
2,700
2,700
2,700
High Ceiling
mode
-
-
3,000
3,000
3,000
3,000
3.3. Discharge direction setting
• The discharge direction can be selected as shown below.
Fig. B
(4 directions)
(3 directions)
100 mm or more
Piping position
* For a 3-way outlet, make sure to perform the Function Setting on the remote controller.
Also, make sure to use the optional shutter panel to block the outlet.
* The ceiling height cannot be set in the 3-way outlet mode. Therefore, do not change
the setting in the “Setting the Ceiling Height” at 7 FUNCTION SETTING.
* When the outlet is shut, be sure to install the optional Air outlet shutter plate kit. For
the details of installation, please refer to Installation Manual of kit.
3.4. Installing the unit
WARNING
Install the air conditioner in a location which can withstand a load of at least 5 times the
weight of the main unit and which will not amplify sound or vibration. If the installation
location is not strong enough, the indoor unit may fall and cause injuries.
If the job is done with the panel frame only, there is a risk that the unit will come loose.
Please take care.
When fastening the hangers, make the bolt positions uniform.
Perform
fi
nal tightening by tightening the double nut
fi
rmly. The product may fall if not
installed properly.
Using a level, or vinyl hose
fi
lled with water,
fi
ne adjust so that the body is level.
Install the air conditioner as follows.
INDOOR UNIT INSTALLATION
(1) Make the holes for installing in the ceiling (Fig. D).
(2) Install the hanging bolts (M10), refer to the position in Fig. C.
(3) Install special nut A, then special nut B onto the hanging bolt (Fig. D).
(4) Raise the body and mount its hooks onto the hanging bolt between the special nuts.
(5) Turn special nut B to adjust the height of the body.
(6) Be sure to leave service access for future service at the designated position.
Fig. C
530 mm (Hanging bolt position)
540 mm (Hanging bolt position)
570 mm (Indoor unit)
580 to 660 mm (Ceiling openings)
700 mm (cassette grille)
135 mm
250 mm
150 to 200 mm
Min. 450 mm
Service access
75 mm
Min. 450 mm
Fig. D
Drain pipe (O.D. ø25.4)
40 mm
99 mm
102 mm
146 mm
245 mm
30 mm
262 mm
30 mm
58 mm
123 mm
Ceiling
Control box
Liquid pipe
Gas pipe
40 mm
9371022253-01_IM.indb Sec1:3
9371022253-01_IM.indb Sec1:3
2012-7-12 14:34:41
2012-7-12 14:34:41
Содержание AUXB07GALH
Страница 17: ...9371022253 01_IM indb Sec1 16 9371022253 01_IM indb Sec1 16 2012 7 12 14 34 49 2012 7 12 14 34 49 ...
Страница 33: ...9371022253 01_IM indb Sec1 16 9371022253 01_IM indb Sec1 16 2012 7 12 14 34 57 2012 7 12 14 34 57 ...
Страница 49: ...9371022253 01_IM indb Sec1 16 9371022253 01_IM indb Sec1 16 2012 7 12 14 35 05 2012 7 12 14 35 05 ...
Страница 65: ...9371022253 01_IM indb Sec1 16 9371022253 01_IM indb Sec1 16 2012 7 12 14 35 14 2012 7 12 14 35 14 ...
Страница 81: ...9371022253 01_IM indb Sec1 16 9371022253 01_IM indb Sec1 16 2012 7 12 14 35 23 2012 7 12 14 35 23 ...
Страница 97: ...9371022253 01_IM indb Sec1 16 9371022253 01_IM indb Sec1 16 2012 7 12 14 35 32 2012 7 12 14 35 32 ...
Страница 113: ...9371022253 01_IM indb Sec1 16 9371022253 01_IM indb Sec1 16 2012 7 12 14 35 41 2012 7 12 14 35 41 ...
Страница 129: ...9371022253 01_IM indb Sec1 16 9371022253 01_IM indb Sec1 16 2012 7 12 14 35 50 2012 7 12 14 35 50 ...