5-2. Model: AOU18RLFC
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length
m
5
7.5
10
15
20
ft
16
24
32
49
65
Height difference H
Indoor unit is higher than outdoor
unit *1
15
49
—
—
—
0.951
0.950
10
32
—
—
0.979
0.967
0.966
7.5
24
—
0.988
0.983
0.971
0.970
5
16
0.994
0.992
0.987
0.975
0.974
0
0
1.002
1.000
0.995
0.983
0.982
Indoor unit is lower than outdoor
unit *2
-5
-16
1.002
1.000
0.995
0.983
0.982
-7.5
-24
—
1.000
0.995
0.983
0.982
-10
-32
—
—
0.995
0.983
0.982
-15
-49
—
—
—
0.983
0.982
HEATING
Pipe length
m
5
7.5
10
15
20
ft
16
24
32
49
65
Height difference H
Indoor unit is higher than outdoor
unit *1
15
49
—
—
—
0.994
0.979
10
32
—
—
1.012
0.994
0.979
7.5
24
—
1.000
1.012
0.994
0.979
5
16
0.969
1.000
1.012
0.994
0.979
0
0
0.969
1.000
1.012
0.994
0.979
Indoor unit is lower than outdoor
unit *2
-5
-16
0.964
0.995
1.007
0.989
0.974
-7.5
-24
—
0.993
1.004
0.986
0.972
-10
-32
—
—
1.002
0.984
0.969
-15
-49
—
—
—
0.974
0.959
- 54 -
5-2. Model: AOU18RLFC
5. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOU9-18RLFC
OUTDOOR UNIT
AOU9-18RLFC