En-3

 CAUTION

Install heat insulation around both the gas and liquid pipes. Failure to do so may 
cause water leaks.
Use heat insulation with heat resistance above 248 °F (120 °C). Reverse cycle model 
only.
In addition, if the humidity level at the installation location of the refrigerant piping 
is expected to exceed 70%, install heat insulation around the refrigerant piping. If 
the expected humidity level is 70-80%, use heat insulation that is 3/4 in. (15 mm) or 
thicker and if the expected humidity exceeds 80%, use heat insulation that is 13/16 in. 
(20 mm) or thicker.
If heat insulation is used that is not as thick as speci

fi

 ed, condensation may form on 

the surface of the insulation. In addition, use heat insulation with heat conductivity of 
0.045 W/(m•K) or less (at [68 °F (20 °C)]).

2.6. Electrical requirement

The indoor unit is powered from the outdoor unit or branch box. Do not power indoor unit 
from separate power source.

 WARNING

Standard for electrical wiring and equipment differs in each country or region. Before you 
start electrical working, con

fi

 rm related regulations, codes, or standards.

Cable

Cable size

Remarks

Connection cable

14AWG

3 cable+Earth (Ground), 

1

φ

 208/230 V

Max. Cable Length: Limit voltage drop to less than 2%. Increase cable gauge if voltage 

drop is 2% or more.

2.7. Optional parts

Refer to each installation manual for the method of installing optional parts.

Parts name

Model No.

Application

Wired remote controller (*1) (*3)

UTY-RNR

Z

For air conditioner operation
(2-wired type)

Simple remote controller (*1)

UTY-RSR

UTY-RHR

External input and output PCB 
(*2)

UTY-XCSXZ2

For control input/output port

External connect kit (*2)

UTY-XWZXZ5

Communication kit

UTY-TWRXZ2

For the installation of optional parts

WLAN adapter (*2) 
[For LZBS series]

UTY-TFSXF1

For wireless LAN control

*1: Optional Communication kit (UTY-TWRXZ2) is necessary for installation.
*2:  The External input and output PCB and the WLAN adapter cannot be used 

simultaneously.

*3:  The wired remote controller (UTY-RNR

Z

) and the wireless controller cannot be 

used simultaneously.

3. INSTALLATION WORK

 CAUTION

•  Do not hit or push the human sensor. This may lead to damage or malfunction.
•  Do not touch the human sensor. Any scratches or dirt may lead to incorrect detection.

•  Do not place large objects near the human sensor. Also keep heating units outside the 

sensor’s detection area.

Detection range of the human sensor is as follows.

Vertical angle 90° (Side view)

90°

50°

50°

22 feet
( 7 m )

22 feet
( 7 m )

Horizontal angle 100° (Top view)

3.1. Selecting an installation location

Decide the mounting position with the customer as follows:

(1)  Install the indoor unit level on a strong wall which is not subject to vibration.
(2)  The inlet and outlet ports should not be obstructed: the air should be able to blow all 

over the room.

(3)  Install the unit a dedicated electrical branch circuit.
(4)  Do not install the unit where it will be exposed to direct sunlight.
(5)  Install the unit where connection to the outdoor unit or branch box is easy.
(6)  Install the unit where the drain pipe can be easily installed.
(7) Take servicing, etc. into consideration and leave the spaces shown in “3.1.1. 

Installation dimensions”. Also install the unit where the 

fi

 lter can be removed.

Correct initial installation location is important because it is dif

fi

 cult to move unit after it is 

installed.

 WARNING

 Install the air conditioner in a location which can withstand a load of at least 3 times the 
weight of the main unit and which will not amplify sound or vibration. If the installation 
location is not strong enough, the indoor unit may fall and cause injuries.

Withstandable weight (Unit weight x 3*)

86 lbs (39 kg)

*In accordance with UL standards.

 CAUTION

• Do not install the unit in the following areas:

- Area with high salt content, such as at the seaside. It will deteriorate metal parts, 

causing the parts to fail or the unit to leak water.

-  Area 

fi

 lled with mineral oil or containing a large amount of splashed oil or steam, such 

as a kitchen. 
It will deteriorate plastic parts, causing the parts to fail or the unit to leak water.

-  Area that generates substances that adversely affect the equipment, such as sulfuric 

gas, chlorine gas, acid, or alkali. 
It will cause the copper pipes and brazed joints to corrode, which can cause 
refrigerant leakage.

-  Area that can cause combustible gas to leak, contains suspended carbon 

fi

 bers or 

fl

 ammable dust, or volatile in

fl

 ammables such as paint thinner or gasoline.

  If gas leaks and settles around the unit, it can cause a 

fi

 re.

-  Area where animals may urinate on the unit or ammonia may be generated.
•  Do not use the unit for special purposes, such as storing food, raising animals, 

growing plants, or preserving precision devices or art objects.
It can degrade the quality of the preserved or stored objects.

•  Do not install where there is the warning of combustible gas leakage.
•  Do not install the unit near a source of heat, steam, or 

fl

 ammable gas.

•  Install the unit where drainage does not cause any trouble.
• Install the indoor unit, outdoor unit, branch box, power supply cable, connection 

cable, and remote controller cable at least 40 in. (1m) away from a television or radio 
receivers. The purpose of this is to prevent TV reception interference or radio noise. 
(Even if they are installed more than 40 in. (1m) apart, you could still receive noise 
under some signal conditions.)

•  If children under 10 years old may approach the unit, take preventive measures so 

that they cannot reach the unit.

•  Install the indoor unit on the wall where the height from the 

fl

 oors more than 70 in. 

(1.8 m).

 

3. 1.1. Installation dimensions

Keep the distance between the wall hook bracket or indoor unit to the surrounding walls 
as indicated in the following 

fi

 gure. 

Wall hook bracket

Outline of the indoor unit

[ 1-15/16 (50) 

or more ]

2-13/16 (71) 

or more

[ 1-9/16 (40) 

or more ]

[ 2-3/4 (70) 

or more ]

4-5/8 (117) 

or more

60 (1500) 

or more

71 (1800) or more

Unit: in (mm)

6-5/16 (160) 

or more

9387603187_IM.indb   3

9387603187_IM.indb   3

16-Feb-21   13:22:41

16-Feb-21   13:22:41

Содержание ASUG09LZBS

Страница 1: ... grounding can cause accidental injury or death Earth Ground the unit following local electrical codes Connect all wiring tightly Loose wiring may cause overheating at connection points and a possible fire hazard When Transporting Be careful when picking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or th...

Страница 2: ...ventional refrigerant R22 models However pay careful attention to the following points Since the working pressure is 1 6 times higher than that of conventional refrigerant R22 models some of the piping and installation and service tools are special Refer to the following table Especially when replacing a conventional refrigerant R22 model with a new refriger ant R410A model always replace the conv...

Страница 3: ...l the unit where it will be exposed to direct sunlight 5 Install the unit where connection to the outdoor unit or branch box is easy 6 Install the unit where the drain pipe can be easily installed 7 Take servicing etc into consideration and leave the spaces shown in 3 1 1 Installation dimensions Also install the unit where the filter can be removed Correct initial installation location is importan...

Страница 4: ... places CAUTION Please take caution when removing or installing the front panel If the front panel falls there is a risk of injury 3 2 3 Uninstalling the indoor unit Remove the indoor unit from the wall hook bracket as follows 1 Remove the under covers Refer to 3 2 2 Front panel control cover removal and installation 2 Insert your fingers in the opening shown in the figure While pushing down on th...

Страница 5: ...at the projection at the end of the cap with pliers etc No gap Hexagonal wrench Drain cock Drain cap Removing the drain hose Remove the screw at the left of drain hose and pull out drain hose Installing the drain hose Vertically insert the drain hose toward the inside so that the drain fixture white can ac curately align with the screw hole around the drain cock After inserting and before replacin...

Страница 6: ...at its grip keeping it in the right angle with the pipe in order to tighten the flare nut correctly Tighten the flare nuts with a torque wrench using the specified tightening method Otherwise the flare nuts could break after a prolonged period causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a flame Connect the piping so that the control box cover c...

Страница 7: ...e matching custom code 1 Press START STOP until only the clock is dis played on the remote controller display 2 Press MODE for at least 5 seconds to display the cur rent custom code initially set to A 3 Press TEMP to change the custom code between A B C D Match the code on the display to the air conditioner custom code 4 Press MODE again to return to the clock display The custom code will be chang...

Страница 8: ...lock as shown in the figure Cable tie accessory for option Connector CN300 Connector CN301 Screw small accessory for option Wire with connector accessory for option Connector CN13 Cable clamp accessory for option Wired remote controller cable Screw large accessory for option Terminal block Tab 7 Replace the control cover front panel and Intake grille 5 FUNCTION SETTING Perform the Function setting...

Страница 9: ...wer saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation Factory setting Function number Setting value Setting description 49 00 Disable 01 Enable 02 Remote controller 00 When the outdoor unit is stopped the indoor unit fan operates continuously following the setting on the remote controller 01 When the outdoor unit is stopped the in...

Страница 10: ...operation of each button on the remote control unit normal 2 Does each lamp light normally 3 Do air flow direction louvers operate normally 4 Is the drain normal 5 Do not have an abnormal noise and vibration during operation Do not operate the air conditioner in test run for a long time Operation method Before starting the test run wait for 1 minute after connecting the power supply By the wireles...

Страница 11: ...troller error 4 1 41 Room temp sensor error 4 2 42 Indoor unit heat ex middle temp sensor error 4 4 44 Human sensor error 5 1 51 Indoor unit fan motor error 5 3 53 Drain pump error 5 4 54 Electric air cleaner reverse VDD error 5 5 55 Filter set error Error display Error code Description OPERATION lamp green TIMER lamp orange ECONOMY lamp green 5 7 57 Damper error 5 8 58 Intake grille error 5 9 59 ...

Страница 12: ...CONOMY lamp green 10 5 A5 Low pressure error 13 2 J2 Branch boxes error Flexible multi split type Display mode 0 5s ON 0 5s OFF 0 1s ON 0 1s OFF Number of flashing Error display on the indoor unit OPERATION indicator lamp green TIMER indicator lamp orange ECONOMY indicator lamp green ...

Отзывы: