background image

En-17

OPERATING TIPS

Multi-type Air conditioner

This indoor unit can be connected to a multi-type outdoor unit. The multi-type air conditioner allows multiple indoor units to
be operated in multiple locations. The indoor units may be operated simultaneously, in accordance with their respective
output.

Operation can be done in the following different operat-
ing modes.

Cooling mode and dry mode

Cooling mode and fan mode

Dry mode and fan mode

The operating mode (heating mode or cooling (dry)
mode) of the outdoor unit will be determined by the op-
erating mode of the indoor unit that was operated first.
If the indoor unit was started in fan mode, the operating
mode of the outdoor unit will not be determined.

For example, if indoor unit (A) was started in fan mode
and then indoor unit (B) was then operated in heating
mode, indoor unit (A) would temporarily start opera-
tion in fan mode but when indoor unit (B) started oper-
ating in heating mode, the OPERATION indicator lamp
(green) for indoor unit (A) would begin to flash (1 sec-
ond on, 1 second off) and it would go into standby mode.
Indoor unit (B) would continue to operate in heating
mode.

During use of the heating mode, the top of the indoor
unit may become warm, but this is due to the fact that
coolant is circulated through the indoor unit even when
it is stopped; it is not a malfunction.

Notice

Simultaneous Use of Multiple Units

When using a multi-type air conditioner, the multiple
indoor units can be operated simultaneously, but when
two or more indoor units of the same group are oper-
ated simultaneously, the heating and cooling efficiency
will be less than when a single indoor unit is used alone.
Accordingly, when you wish to use more than one in-
door unit for cooling at the same time, the use should
be concentrated at night and other times when less out-
put is required. In the same way, when multiple units
are used simultaneously for heating, it is recommended
that they be used in conjunction with other auxiliary
space heaters, as required.

Seasonal and outdoor temperature conditions, the struc-
ture of the rooms and the number of persons present
may also result in differences of operating efficiency.
We recommend that you try various operating patterns
in order to confirm the level of heating and cooling out-
put provided by your units, and use the units in the way
that best matches your family’s lifestyle.

If you discover that one or more units delivers a low
level of cooling or heating during simultaneous
operation, we recommend that you stop simultaneous
operation of the multiple units.

Operation cannot be done in the following different op-
erating modes.

If the indoor unit is instructed to do an operating mode
that it cannot perform, the OPERATION indicator lamp
(green) on the indoor unit will flash (1 second on, 1 sec-
ond off) and the unit will go into the standby mode.

Heating mode and cooling mode (or dry mode)

Heating mode and fan mode

During use of the heating mode, the outdoor unit will
occasionally commence the defrost operation for brief
periods. During the defrosting operation, if the user sets
the indoor unit for heating again, the defrosting mode
will continue, and the heating operation will begin after
completion of defrosting, with the result that some time
may be required before warm air is emitted.

AUTO Restart

In Event of Power Interruption

The power supply to the air conditioner is stopped by a
power interruption. The air conditioner will then restart
automatically in its previous mode when the power is
restored.

If a power interruption occurs during TIMER operation, the
timer will be reset and the indoor unit will begin (or stop)
operation at the new time setting. In the event that this kind
of timer fault occurs, the TIMER Indicator Lamp will flash
(see Page. 3).

Use of other electrical appliances (electric shaver, etc.) or
nearby use of a wireless radio transmitter may cause the
air conditioner to malfunction. In this event, temporarily
turn off the circuit breaker, turn it on and then use the
Remote Controller to resume operation.

Содержание ASTG09LVCA

Страница 1: ...r Conditioner contains and operates with refrigerant R410A and Polyol Ester oil THIS PRODUCT MUST ONLY BE INSTALLED OR SERVICED BY QUALIFIED PERSONNEL Refer to Commonwealth State Territory and local legislation regulations codes installation operation manuals before the installation maintenance and or service of this product English ...

Страница 2: ...not climb on or place objects on the air conditioner Do not hang objects from the indoor unit Do not set flower vases or water containers on top of air conditioners Do not expose the air conditioner directly to water Do not operate the air conditioner with wet hands Do not pull power supply cord Turn off power supply when not using the indoor unit for extended periods Check the condition of the in...

Страница 3: ...timer to ON timer or from ON timer to OFF timer within a twenty four hour period SLEEP TIMER When the SLEEP button is pressed during Heating mode the indoor unit s thermostat setting is gradually lowered during the period of operation during cooling mode the thermostat setting is gradually raised during the period of operation When the set time is reached the indoor unit au tomatically turns off W...

Страница 4: ...tate explanation the accompanying illus tration has been drawn to show all possible indica tors in actual operation however the display will only show those indicators appropriate to the current operation Fig 5 Fig 2 Fig 3 Fig 4 ...

Страница 5: ...er behind Airflow Direction Louver D Drain Hose E Air Cleaning Filter F Remote Controller Wired Option NAME OF PARTS Fig 5 Remote Controller G Signal Transmitter H MODE button I 10 C HEAT button J SET TEMP button K ECONOMY button L SLEEP button M TIMER MODE button N FAN button O START STOP button P SET button Q SWING button R TIMER SET button S CLOCK ADJUST button T TEST RUN button This button is ...

Страница 6: ... side to open it Slide in the direction of the arrow while pressing the mark 2 Insert batteries Be sure to align the battery polarities correctly 3 Close the battery compartment lid Set the Current time 1 Press the CLOCK ADJUST button Fig 5 S Use the tip of a ball point pen or other small object to press the button 2 Use the TIMER SET buttons Fig 5 R to adjust the clock to the current time button ...

Страница 7: ...e FAN button Fig 5 N Each time the button is pressed the fan speed changes in the following order AUTO HIGH MED LOW QUIET About three seconds later the entire display will reappear When set to AUTO Heating Fan operates so as to optimally circulate warmed air However the fan will operate at very low speed when the tempera ture of the air issued from the indoor unit is low Cooling As the room temper...

Страница 8: ... is selected the indoor unit will operate at very low fan speed for about 3 to 5 minutes after which it will switch to the selected fan setting This period of time is provided to allow the indoor unit to warm up before begin full operation When the room temperature is very low frost may form on the outdoor unit and its performance may be reduced In order to remove such frost the air conditioner wi...

Страница 9: ... later the entire display will reappear About the Program timer The program timer allows you to integrate OFF timer and ON timer operations in a single sequence The sequence can involve one transition from OFF timer to ON timer or from ON timer to OFF timer within a twenty four hour period The first timer function to operate will be the one set nearest to the current time The order of operation is...

Страница 10: ...er Operation Press the START STOP button About the SLEEP Timer To prevent excessive warming or cooling during sleep the SLEEP timer function automatically modifies the thermostat setting in accordance with the set time setting When the set time has elapsed the air conditioner completely stops During Cooling Dry operation When the SLEEP timer is set the thermostat setting is auto matically raised 1...

Страница 11: ...than 30 minutes they will automatically return to position 3 When used in a room with infants chil dren elderly or sick persons the Airflow direction and room temperature should be considered carefully when making settings Vertical Airflow Direction Adjustment Press the SET button Fig 5 P Each time the button is pressed the Airflow direction range will change as follows 1 2 3 4 5 6 Types of Airflo...

Страница 12: ...ig 3 7 will go out Normal operation begins About ECONOMY Operation In case of single type air conditioner at the maximum output ECONOMY Operation is approximately 70 of normal air conditioner operation for cooling and heating During ECONOMY operation the thermostat setting automatically changes according to the temperature to avoid Unneces sary cooling and heating for the most economical operation...

Страница 13: ...be AUTO and the thermostat setting will be standard 24 C Begin air conditioner operation before performing this procedure To select SWING Operation Press the SWING button Fig 5 Q The SWING Display Fig 6 Y will light In this mode the Airflow Direction Louvers will swing automatically to direct the air flow both up and down To stop SWING Operation Press the SWING button Fig 5 Q once again The SWING ...

Страница 14: ...f neutral detergent and warm water If you wash the filter be sure to allow it to dry thoroughly in a shady place before reinstalling If dust is allowed to accumulate on the air filter airflow will be reduced lowering operating efficiency and increasing noise During periods of normal use the Air Filters should be cleaned every two weeks Don t operate the air conditioner with being opened the intake...

Страница 15: ...an the filter in the follow way once six months 1 Remove the air cleaning filter 2 Clean with water and dry in the air 1 Flush the filter with fresh or warm water Please flush with diluted neutral detergent when extremely dirty Never wash by reaming or rubbing otherwise it will damage the deodorizing effect 2 Rinse with water flow 3 Dry in shade 3 Reinstall the air cleaning filter CLEANING AND CAR...

Страница 16: ...ing operation is started fan speed is temporarily very low to allow internal parts to warm up During Heating operation if the room temperature rises above the thermostat setting the outdoor unit will stop and the indoor unit will operate at very low fan speed If you wish to warm the room further set the thermostat for a higher setting During Heating operation the indoor unit will temporarily stop ...

Страница 17: ...operates on the heat pump principle absorbing heat from outdoor air and transferring that heat to indoor unit As a result the operating performance is reduced as outdoor air temperature drops If you feel that insufficient heating performance is being produced we recommend you use this air conditioner in conjunction with another kind of heating appliance Heat pump air conditioners heat your entire ...

Страница 18: ...nded that they be used in conjunction with other auxiliary space heaters as required Seasonal and outdoor temperature conditions the struc ture of the rooms and the number of persons present may also result in differences of operating efficiency We recommend that you try various operating patterns in order to confirm the level of heating and cooling out put provided by your units and use the units...

Страница 19: ......

Страница 20: ......

Отзывы: