En-9
CAUTION
• Ground the unit.
Do not connect the ground cable to a gas pipe, water
pipe, lightning rod, or a telephone ground cable.
Improper grounding may cause electric shock.
• Do not connect power supply cables to the transmission
or remote control terminals, as this will damage the
product.
• Never bundle the power supply cable and transmission
cable together. Bundling these cables together will cause
miss operation.
• When handling PCB, static electricity charged in the body
may cause malfunction of the PCB. Follow the cautions
below:
• Establish a ground for the indoor and outdoor units and
peripheral devices.
• Cut power (breaker) off.
• Touch metal part of the indoor and outdoor units for
more than 10 seconds to discharge static electricity
charged in the body.
• Do not touch terminals of parts and patterns
implemented on PCB.
]1
6.1. Electrical requirement
Voltage rating
230 V
Operating range
198 - 264 V
Recom-
mended cable
size (mm
2
)
Cable type
Remark
Power
supply cable
2.5
Type245 IEC57
or equivalent
1ø 50 Hz
198 - 264 V
2 Cable + ground
Transmission
cable
0.33
LONWORKS
compatible cable
22 AWG
LEVEL 4 (NEMA)
non-polar 2 core,
twisted pair solid
core diameter
0.65 mm
Remote
control cable
0.33
Sheathed
PVC cable*
Polar 3 core
Twisted pair
*: Use shielded cable in accordance with local rules for
remote control cable.
]1
6.2. Wiring method
(EXAMPLE)
POWER SUPPLY
OUTDOOR UNIT
BREAKER
POWER SUPPLY
TRANSMISSION
TRANSMISSION
POWER
SUPPLY
POWER
SUPPLY
REMOTE
CONTROL UNIT
(MASTER)
REMOTE
CONTROL UNIT
POWER
SUPPLY
REMOTE
CONTROL
TRANSMISSION
TRANSMISSION
POWER
SUPPLY
POWER
SUPPLY
REMOTE
CONTROL
REMOTE
CONTROL
INDOOR UNIT
POWER SUPPLY
REMOTE
CONTROL UNIT
(SLAVE)
INDOOR UNIT
INDOOR UNIT
BREAKER
BREAKER
BREAKER
]1
6.3. Unit wiring
• Before attaching the cable to terminal block.
6.3.1. Power supply cable
Power supply cable
20 mm
Earth cable
30 mm
A. For solid core wiring
(1) To connect the electrical terminal, follow the below
diagram and connect after looping it around the end of the
cable.
(2) Use the specified cables, connect them securely, and
fasten them so that there is no stress placed on the
terminals.
(3) Use an appropriate screwdriver to tighten the terminal
screws. Do not use a screwdriver that is too small,
otherwise, the screw heads may be damaged and prevent
the screws from being properly tightened.
(4) Do not tighten the terminal screws too much, otherwise,
the screws may break.
(5) See the table for the terminal screw tightening torques.
(6) Please do not fix two power supply cables with one screw.
9373870036_02_IM_en.indd 9
25/2/2552 9:17:32
Содержание ARXC36L